Operating Voltage (Un)
: (Phase-Neutral ) 220Vac ; (Phase-Phase) 380 Vac
Operating Range
: (0,8-1,1) x Un
Operating Frequency
: 50/60 Hz
Supply Power Consumption
: < 10VA
Power Consumption of Measurement Inputs
: < 1VA
Contact Current
: Max.3A/240 Vac
Current Measurement Range
: (as secondary current of current transformer)
0,01 - 6 Amp AC
Display Range
: (Power Factor) 0,000 - 1,000 ind.and cap.
Mimimum Current Measurement Value
: 10 mA
Measurement Accuracy
: %1±1 digit
Current Transformer Ratio
: 5/5..........10000/5 A
Display
: 3,2” coloured LCD
RS485
Baud rate
: 2400,4800,9600,19200,28800,38400,57600,115200
Stop Bits
: (0.5) , (1) , (1.5) or (2)
Parity
: no , even , odd
Device No
: 1 .....255
Device Protection Class
: IP 20
Terminal Protection Class
: IP 00
Environment Temperature
: - 5 °C .... + 50 °C
Humudity
: %15 ...... %95 (without condensation)
Device Standart : EN 55011: 2007 + A2 : 2007
EN 61326 : 2006
EN 61000-3-2 : 2006
EN 61000-3-3 : 1995 + A1 : 2001 + A2 : 2005
EN 61010-1 : 2001
Connection Type
: On the front cover of the panel
Dimensions
:
144x144x45 mm
Technical Info
37 mm
1
40
m
m
140mm
50mm
WALL
1- An outlet in square form by 140 mm x 140 mm will be made on the panel where the assembly of
the device will be made.
2- Prior to the assembly of the device, remove the apparatus of the panel.
3- Insert the device from the front window drilled at the panel.
4- Fix the device to the panel by using panel holding apparatus at the back of the device.
Installation
Make the assembly as to leave a 50 mm space between the wall and
the back of the device for ventilation.
PANEL OUTLET MEASUREMENT