background image

Temperature Unit

:

 

ºC

Channel 4 (Ch4) Setting

: off (disabled)

Alarm Set Value

: 130 ºC

Trip Set Value

: 150 ºC

Fan working mode

: CH123

Fan Start Value

: 100 ºC

Fan Stop Value

              :   85 ºC

Fan ON time  (Tp)

: 1 minute

Fan OFF time (Ts)

: 1 hour

Fault (∆T) Temperature Change Value : 5 ºC/s
Password Usage

: off (disabled)

Date – Time

: Must be set.

If you press return to factory settings, the device returns to its original settings. The Language, Temperature 

Unit, Channel 4, Alarm, Trip, Fan, Fault settings are entered in order.

 

Date and time should be checked.

NOT1: 

The password is reset.

NOT2:

 After a few seconds of pressing the return to factory settings button, it will be directed to the opening screen

4. FACTORY SETTINGS

Technicial Specifications

Operating Voltage (Un)  

: 24.... 240 VAC / DC (±10%)  

Operating Frequency

: 50/60 Hz

Supply Power Consumption

 

: < 5VA

Relays (4 pieces)

: max.16A/240 Vac

Screen  

 

: 2,4” color TFT

Device Protection Class

: EN 60529    IP 40

Terminal protection class 

: IP 00

Accuracy

: ±1% fully scale ±1 digit

Sensor Type

: RTD sensor, Pt100 type, 3 wire 

  (max. 1.5mm²) 

Ambient Temperature

      

: - 20 °C .... + 60 °C

EMC - Immunity 

: EN 61000-6-2

EMC - Emission 

: EN 61000-6-3

Installation Type        

: to panel cover from front

Dimensions

 

     

: 96x96x56 mm

10

m

m

97 mm

96 mm

96

 m

m

56 mm

3.10 SCREEN SAVER

Used to activate the screen saver or to change to the otomatic screen 

protection mode. Choose one of the ON/OFF options by using the Up/Down 

buttons and press the Apply button. If the OK button is pressed, all changes 

will be saved into the memory. To discard the changes made, press the Back 

button. If Screen saver is running in the ON mode while screen shows the 

Mainpage, then the screen saver is activated after 5 minutes later and only the 

status bar is shown on the screen. If the screen saver is running in the OFF 

mode, the screen will refresh itself every 5 minutes automatically. 

11/10/2016 14:25

Apply

ON

SCREEN SAVER

Screen Saver Settings

OFF Mode

11/10/2016 14:25

Menu

Report

FAN

85

83

84

32

ch1

ch2

ch3

ch4

ºC

ºC

ºC

ºC

Press a key...

11/10/2016 14:25

 
Screen will be 
refreshed after 
5 seconds

ON Mode

Содержание TC - PT100

Страница 1: ...KAEL M hendislik Elektronik Tic ve San Ltd ti Temperature Controller For Dry Type Medium Voltage Transformers www kael com tr TC PT100...

Страница 2: ...78 Sok No 10 Ulucak Village Kemalpa a ZM R The device must be commissioned and programmed by authorized and qualified persons in accordance with the instructions in the operating instructions If nece...

Страница 3: ...cooling Continuously monitors temperature sensors for faults It detects errors Sensor cable is broken Sensor cable short circuit Sensor not attached Error detection in case of data recording center f...

Страница 4: ...s normal and returns to exclamation point when an error occurs in the system A color LCD display is used in our device to make it much easier and clearer to use If the keys are not pressed for a long...

Страница 5: ...The PT100 sensors must have 1 white 2 red output lines DIN 43760 IEC 751 Ch2 channel should always be connected to the middle column of the MV transformers The Ch4 channel can be connected to measure...

Страница 6: ...NING 1 Step Choice Of Language The next screen will appear when it is first activated Up Down buttons to select one of the Turkish English or Russian language and press Set button After the language o...

Страница 7: ...F Then click the Apply button In this case if OK is pressed the change is recorded If you want to change without recording press the Back key After recording the device starts to operate normally 11 1...

Страница 8: ...t the system would not be damaged ALARM TRIP FAULT FAN 11 10 2016 14 25 Exit RELAY TEST Set ALARM TRIP FAULT FAN Control the contactors of the relay with multimeter during the test opeation 2 SENSOR T...

Страница 9: ...own in red If the temperature value measured from the corresponding sensor is equal to or lower than the set alarm temperature setpoint the alarm of the ALARM relay is deactivated and the alarm log is...

Страница 10: ...time m T p T p T p T s T s Saving Mode Saving Mode Continuous Cooling Instantaneous temperature increase analyzes the temperature rise T value in seconds C sec The user can choose from 1 C to 30 C T...

Страница 11: ...Pass Men s Enter Your New Password Again 0 OK 14 25 Exit PASSWORD SET Change De i tirme Pass Aktif Pasif Pass Men s Enter Your New Password Again 0 Password Saved OK Correctness of the measurements an...

Страница 12: ...ction class IP 00 Accuracy 1 fully scale 1 digit Sensor Type RTD sensor Pt100 type 3 wire max 1 5mm Ambient Temperature 20 C 60 C EMC Immunity EN 61000 6 2 EMC Emission EN 61000 6 3 Installation Type...

Страница 13: ...r transformer coil wires In the distribution box 3 conductors of each PT100 sensor must be connected to the PT100 sensor inputs of the TC PT100 temperature controller with a minimum 0 50 mm cross sect...

Отзывы: