3.2 TEMPERATURE UNIT ADJUSTMENT
The temperature unit can be set to
Celsius(ºC) or Fahrenheit(ºF). The system
changes the settings according to the
selected temperature unit and displays the
temperature values according to that
unit.The temperature display on the main
screen and the temperature values
required for operation of the device are
made according to this selected
parameter.
3.3 Channel 4 Option
Channel 4 (CH4), sensor number
4 can be used for different purposes. It is
possible to measure the temperature of
the transformer core, to measure the
ambient temperature, to operate the fan
according to this sensor. The parameter
must be set to On in the setting menu for
activation. If not, it should be selected Off.
11/10/2016 14:25
Apply
º
C
TEMPERATURE SET.
Select Temperature Unit
11/10/2016 14:25
Cancel
º
C
TEMPERATURE SET.
Select Temperature Unit
Save
Changes
Back
OK
3.4 ALARM ADJUSTMENT
If any of the sensors exceeds the set
temperature set in this section, the
ALARM relay is energized after 5 seconds
and the alarm log is displayed on the
notification screen. When this happens,
the date-time and channel information are
stored in the memory and can be viewed
in detail from the report screen.
11/10/2016 14:25
Apply
OFF
CHANNEL 4 SET.
Channel 4 (ch4)
11/10/2016 14:25
Kapalı
CHANNEL 4 SET.
Channel 4 (ch4)
Değişikliği
Kaydet
Cancel
Back
OK
11/10/2016 14:25
Apply
OFF
ALARM SET.
Enter Alarm Set Value
11/10/2016 14:25
Kapalı
ALARM AYARI
Enter Alarm Set Value
Cancel
Back
OK
Değişikliği
Kaydet
In the case of an alarm, the temperature value on the scale of the relevant channel on the main
screen is shown in red. If the temperature value measured from the corresponding sensor is
equal to or lower than the set alarm temperature setpoint, the alarm of the ALARM relay is
deactivated and the alarm log is removed from the notification screen. You can also use the
Reset
button to activate the Silent Alarm function and quickly cut off the power of the relay.
However, the alarm log is displayed on the screen until the temperature value falls below the set
value.
3.5 TRIP (On) SETTING
If any of the sensors exceeds
the set trip temperature setpoint in this
section, the TRIP relay is energized
immediately and the message TRIP
appears on the notification screen.When
this happens, the date-time and channel
information are stored in the memory
and can be viewed in detail from the
11/10/2016 14:25
Apply
120
º
C
TRIP SET.
Enter Trip Set Value
11/10/2016 14:25
120
º
C
TRIP SET.
Enter Trip Set Value
Cancel
Back
OK
Değişikliği
Kaydet
report screen. The temperature value of the relevant sensor
on the scale of the main display is shown in orange. If the temperature value measured from the
corresponding sensor is equal to or lower than the set trip temperature setpoint, the TRIP relay is
de-energized and the TRIP input is removed from the notification screen.
3.6 FAN ADJUSTMENT
There are 5 parameter options for fan :
Fan Modes:
Indicates the mode required for fan operation.
OFF:
The fan relay is deactivated and the fan does not operate. It can only be
operated manually.
CH123:
Fan relay operates according to temperature sensors Ch1, Ch2, Ch3.
CH4:
If channel 4 setting parameter (Ch4) is on, the fan relay operates
according to Ch4 temperature sensor.
Fan Start Value:
The temperature, at which the fan relay is energized, is the set value. It should
be higher than Fan Stop value.
Save
Changes
Save
Changes
Save
Changes