background image

Application

U

V

W

TC-PT100

1 2 3 4 5 6 7 8 9 10 11 12

PT100KS

PT100KS

PT100KS

3 x PT100

PT100-KS

BOX-KS

●  

 PT100-KS

 signal conductors must be connected to the distribution box 

(BOX-KS) 

without 

terminal connection and considering the distance to be protected from high voltage. Sufficient 
length and thickness provide adequate insulation for transformer coil wires.

●  

In the distribution box 3 conductors of each PT100 sensor must be connected to the PT100 

sensor inputs of the 

TC-PT100

 temperature controller with a minimum 0.50 mm² cross section, 

a maximum of 1 mm² .

●  

The cable shield used for each sensor should be grounded only from the nearest point to the 

TC-PT100

 temperature controller side. The other end should remain open.

●  

To avoid sensor errors signal sensor cables must not be near medium-voltage cables and must 

be laid in a linear way, without creating windings on itself.

Содержание TC - PT100

Страница 1: ...KAEL M hendislik Elektronik Tic ve San Ltd ti Temperature Controller For Dry Type Medium Voltage Transformers www kael com tr TC PT100...

Страница 2: ...78 Sok No 10 Ulucak Village Kemalpa a ZM R The device must be commissioned and programmed by authorized and qualified persons in accordance with the instructions in the operating instructions If nece...

Страница 3: ...cooling Continuously monitors temperature sensors for faults It detects errors Sensor cable is broken Sensor cable short circuit Sensor not attached Error detection in case of data recording center f...

Страница 4: ...s normal and returns to exclamation point when an error occurs in the system A color LCD display is used in our device to make it much easier and clearer to use If the keys are not pressed for a long...

Страница 5: ...The PT100 sensors must have 1 white 2 red output lines DIN 43760 IEC 751 Ch2 channel should always be connected to the middle column of the MV transformers The Ch4 channel can be connected to measure...

Страница 6: ...NING 1 Step Choice Of Language The next screen will appear when it is first activated Up Down buttons to select one of the Turkish English or Russian language and press Set button After the language o...

Страница 7: ...F Then click the Apply button In this case if OK is pressed the change is recorded If you want to change without recording press the Back key After recording the device starts to operate normally 11 1...

Страница 8: ...t the system would not be damaged ALARM TRIP FAULT FAN 11 10 2016 14 25 Exit RELAY TEST Set ALARM TRIP FAULT FAN Control the contactors of the relay with multimeter during the test opeation 2 SENSOR T...

Страница 9: ...own in red If the temperature value measured from the corresponding sensor is equal to or lower than the set alarm temperature setpoint the alarm of the ALARM relay is deactivated and the alarm log is...

Страница 10: ...time m T p T p T p T s T s Saving Mode Saving Mode Continuous Cooling Instantaneous temperature increase analyzes the temperature rise T value in seconds C sec The user can choose from 1 C to 30 C T...

Страница 11: ...Pass Men s Enter Your New Password Again 0 OK 14 25 Exit PASSWORD SET Change De i tirme Pass Aktif Pasif Pass Men s Enter Your New Password Again 0 Password Saved OK Correctness of the measurements an...

Страница 12: ...ction class IP 00 Accuracy 1 fully scale 1 digit Sensor Type RTD sensor Pt100 type 3 wire max 1 5mm Ambient Temperature 20 C 60 C EMC Immunity EN 61000 6 2 EMC Emission EN 61000 6 3 Installation Type...

Страница 13: ...r transformer coil wires In the distribution box 3 conductors of each PT100 sensor must be connected to the PT100 sensor inputs of the TC PT100 temperature controller with a minimum 0 50 mm cross sect...

Отзывы: