Application
U
V
W
TC-PT100
1 2 3 4 5 6 7 8 9 10 11 12
PT100KS
PT100KS
PT100KS
3 x PT100
PT100-KS
BOX-KS
●
3
PT100-KS
signal conductors must be connected to the distribution box
(BOX-KS)
without
terminal connection and considering the distance to be protected from high voltage. Sufficient
length and thickness provide adequate insulation for transformer coil wires.
●
In the distribution box 3 conductors of each PT100 sensor must be connected to the PT100
sensor inputs of the
TC-PT100
temperature controller with a minimum 0.50 mm² cross section,
a maximum of 1 mm² .
●
The cable shield used for each sensor should be grounded only from the nearest point to the
TC-PT100
temperature controller side. The other end should remain open.
●
To avoid sensor errors signal sensor cables must not be near medium-voltage cables and must
be laid in a linear way, without creating windings on itself.