Features

■ 

24 - 240 Vac - Vdc  50/60Hz ultra wide feed input

■ 

Easy menu design with Turkish, English and Russian language support

■ 

Color LCD display (320 x 240 pixel x 2.4 ") 

■ 

Built on embedded system and working on operating system

■ 

It has 4 Pt100 (3-Wires) RTD sensor inputs

■ 

Sensor inputs are resistant to electromagnetic interference

■ 

Cable lengths in Pt100 are not included in the calculation

■ 

It measures temperature between -10°C and 250°C and has ± 1% measurement accuracy

■ 

1 ALARM relay output

■ 

1 TRIP relay output

■ 

There is a relay output (FAULT) for errors in one device operation

■ 

1 FAN relay output for cooling

■ 

The alarms and faults received by the device are stored in the device memory (the last 40          

              records)

■ 

3VA supply available

■ 

Intelligent Fan operation and stop algorithm saves energy in transformer cooling

■ 

Continuously monitors temperature sensors for faults.

             It detects errors "Sensor cable is broken",

             "Sensor cable short circuit" 

             "Sensor not attached" 

■ 

Error detection in case of data recording center failure

■ 

Password Protection protects the Settings menu against unauthorized users

■ 

There is a button for making the alarm silent or for Manual Fan control

General

The device that is developed to protect the windings of MV transformers and high-power 

motors equipped with today's technology, is quite well equipped in terms of function richness and 

has added a new product to its sector with its advanced software. Additionally, the microprocessor 

inside is very fast and uses the operating system. This ensures that all operations can be 

synchronized simultaneously. 

Displaying the error and temperature values that may occur on the main screen during 

device operation is as follows.

85

Ch1

Menu

0

ºC

TRIP(135ºC)

95ºC

94

Ch2

91

Ch3

32

Ch4

14:25

11.10.2016

50

100

150

200

250

FAN

Report

ºC

ºC

ºC

ºC

Содержание TC - PT100

Страница 1: ...KAEL M hendislik Elektronik Tic ve San Ltd ti Temperature Controller For Dry Type Medium Voltage Transformers www kael com tr TC PT100...

Страница 2: ...78 Sok No 10 Ulucak Village Kemalpa a ZM R The device must be commissioned and programmed by authorized and qualified persons in accordance with the instructions in the operating instructions If nece...

Страница 3: ...cooling Continuously monitors temperature sensors for faults It detects errors Sensor cable is broken Sensor cable short circuit Sensor not attached Error detection in case of data recording center f...

Страница 4: ...s normal and returns to exclamation point when an error occurs in the system A color LCD display is used in our device to make it much easier and clearer to use If the keys are not pressed for a long...

Страница 5: ...The PT100 sensors must have 1 white 2 red output lines DIN 43760 IEC 751 Ch2 channel should always be connected to the middle column of the MV transformers The Ch4 channel can be connected to measure...

Страница 6: ...NING 1 Step Choice Of Language The next screen will appear when it is first activated Up Down buttons to select one of the Turkish English or Russian language and press Set button After the language o...

Страница 7: ...F Then click the Apply button In this case if OK is pressed the change is recorded If you want to change without recording press the Back key After recording the device starts to operate normally 11 1...

Страница 8: ...t the system would not be damaged ALARM TRIP FAULT FAN 11 10 2016 14 25 Exit RELAY TEST Set ALARM TRIP FAULT FAN Control the contactors of the relay with multimeter during the test opeation 2 SENSOR T...

Страница 9: ...own in red If the temperature value measured from the corresponding sensor is equal to or lower than the set alarm temperature setpoint the alarm of the ALARM relay is deactivated and the alarm log is...

Страница 10: ...time m T p T p T p T s T s Saving Mode Saving Mode Continuous Cooling Instantaneous temperature increase analyzes the temperature rise T value in seconds C sec The user can choose from 1 C to 30 C T...

Страница 11: ...Pass Men s Enter Your New Password Again 0 OK 14 25 Exit PASSWORD SET Change De i tirme Pass Aktif Pasif Pass Men s Enter Your New Password Again 0 Password Saved OK Correctness of the measurements an...

Страница 12: ...ction class IP 00 Accuracy 1 fully scale 1 digit Sensor Type RTD sensor Pt100 type 3 wire max 1 5mm Ambient Temperature 20 C 60 C EMC Immunity EN 61000 6 2 EMC Emission EN 61000 6 3 Installation Type...

Страница 13: ...r transformer coil wires In the distribution box 3 conductors of each PT100 sensor must be connected to the PT100 sensor inputs of the TC PT100 temperature controller with a minimum 0 50 mm cross sect...