Control of the contacts of the output relays, detailed testing of
the operating states of the sensors and general settings where the
settings are made. The parameters in the menu can be accessed with
the arrow keys and enter into the setting or test section with the
Select
button and exit with the
exit
or
cancel
button
NOTE-1: If the password is activated,then settings section is
entered by the password.
NOTE-2: When entered in the Menu or Report section of the
homepage, it will automatically return to the
Homepage screen if it any button was not clicked
for 2 minutes.
1. RELAY TEST
11/10/2016 14:25
Exit
MENU
Select
►
Relay Test
Sensor Test
Settings
Reset to Factory Settings
11/10/2016 14:25
Cancel
Next
11/10/2016 14:25
Exit
RELAY TEST
Set
It gives the warning message on the side before entering this section. If the
Continue
button
is pressed, the RELAY TEST section is entered. In this case, the operation of the device is stopped.
ALARM, TRIP, FAULT, FAN relays go to OFF position. The up and down arrow keys are used to
switch between relays and the relay position changes each time the
SET
key is pressed.
Exit
button
will exit this page and return to Menu page.
Never enter the Relay Test Area while the device is connected to the system. System and device
may be damaged.
ATTENTION!
The relays switch OFF if
you proceed. Ensure that
the system would not be
damaged
ALARM
TRIP
FAULT
FAN
11/10/2016 14:25
Exit
RELAY TEST
Set
ALARM
TRIP
FAULT
FAN
Control the
contactors of
the relay with
multimeter
during the test
opeation
2. SENSOR TEST
The sensor test tests the operating
states of the sensors and if an error exists
it displays the error.
The result of the test is an open circuit.
A closed circuit, an
OK
signal which means
that is not plugged in and that there is no
fault.Test start with
Start
button and it is
completed between 20-30 seconds.
Operational statuses are shown next to
the channel numbers.
Exit
button will exit
this page and return to Menu page.
11/10/2016 14:25
Exit
SENSOR TEST
Start
ch1
ch2
ch3
ch4
11/10/2016 14:25
Exit
SENSOR TEST
Start
ch1
ch2
ch3
ch4
Unplagged Sensor
Open Circuit
3. SETTINGS
This is where the settings
related to the device are made. It is
entered with password. Language,
Temperature Unit, Channel 4, Alarm,
Trip, Fan, Fault, Password and Date-
Time can be set respectively.
11/10/2016 14:25
Exit
SETTINGS
Select
►
English-Pyccкйй-Türkçe
Temprature Unit Settings
Channel 4 Settings
Alarm Settings
Trip Settings
Fan Settings
11/10/2016 14:25
Exit
SETTINGS
Select
Fault Settings
Password Settings
Date Time Settings
Fan Settings
3.1 LANGUAGE SELECTION
Available in Turkish, English, Russian languages.
This can be selected when the unit is first powered on, or it can be
entered and changed later.
11/10/2016 14:25
Set
English
LANGUAGE SET.
English – Pyccкйй – Türkçe
MENU
Control the
contactors of
the relay with
multimeter
during the test
opeation