Kaden Installation Manual |
23
Outdoor unit wiring
WARNING
Before performing any electrical or wiring work, turn off the
mains power to the system.
1. Prepare the cable for connection
a. You must first choose the right cable size. Be sure to
use H07RN-F cables.
Minimum cross-sectional area of power
and signal cables (For reference)
Rated current of appliance
(A)
Nominal cross-sectional
area (mm²)
> 3 and ≤ 6
0.75
> 6 and ≤ 10
1
> 10 and ≤ 16
1.5
> 16 and ≤ 25
2.5
> 25 and ≤ 32
4
> 32 and ≤ 40
6
b. Using wire strippers, strip the rubber jacket from both
ends of the signal cable to reveal approximately 15cm
of wire.
c. Strip the insulation from the ends.
d. Using a wire crimper, crimp u-lugs on the ends.
NOTE:
When connecting the wires, strictly follow the
wiring diagram found inside the electrical box cover.
2. Remove the electric cover of the outdoor unit. If there is no
cover on the outdoor unit, take off the bolts from the
maintenance board and remove the protection board.
3. Connect the u-lugs to the terminals. Match the wire
colours/labels with the labels on the terminal block. Firmly
screw the u-lug of each wire to its corresponding terminal.
4. Clamp down the cable with the cable clamp.
5. Insulate unused wires with electrical tape. Keep them away
from any electrical or metal parts.
6. Reinstall the cover of the electric control box.
Cover
Screw