KNX/EIB
Switch Actuator with Secure
20
The value (“0” or “1”) of the communication object “Reply the switch status” and “Send the switch
status” defines the current status of the relay, which can be set in the parameter “Object value of switch
status” (when selecting “Respond after read only” or “Transmit after change”).
Parameter “Object value of switch status”
This parameter will be visible when selecting “Respond after read only” or “Transmit after change”
in “Set the reply mode of switch status”. Options:
0=contact close ; 1=contact open
0=contact open ; 1=contact close
It means the contact of the relay will be closed when the value of the communication object “Reply
the switch status” and “Send the switch status” is 0 when setting “0=contact close; 1=contact open”,
while it is open when the value is “1”. It means the opposite with setting “0=contact open; 1=contact
close”.
Parameter “Output status for the telegram "1"(telegram "0" is opposite of selection)”
This parameter sets the position of the channel contact when the Switch object telegram"1" is
received. The switch operation is triggered by the communication object "switch".
. When enabling “Input
0” in the logic function, it will use the communication object “Switch,” to modify the value of “Input 0”,
rather than triggering the switch operation. Options:
Contact open
Contact close
The contact position will be off with “
Contact open
”, and on with “
Contact close
”.
If the switch object message "0" is received, it is the opposite of what is selected by this parameter
option.
NOTE: The parameter only works after receiving object “Switch”, and defines the direction of the
contact after receiving it.