The staircase lighting function is switched on via the object “Output of staircase lighting”. And also
it is available to program the value of “Output of staircase lighting”. The staircase lighting time starts
when it is switched on and will be switched off immediately after the set time when there is no
prewarning setting.
Parameter “Duration of staircase lighting-(0...1000 minutes) / --(0...59 seconds)”
This parameter describes the duration time when switching on the staircase light function:
minutes.Options:
0…1000 min
0…59 s
NOTE: If the minute is set to “0”, and the seconds is set to “0”, the staircase lighting will be
disabled.
Parameter “Control mode of Staircase lighting”
This parameter defines the mode of the staircase lighting function. Options:
Start with “1”, OFF with “0”
Start with “1”, no action with “0”
Start with “0/1”, cannot be stopped
When selecting “Start with “1”, OFF with “0””, it will switch on the staircase lights with the value “1”
received by the object “Output of staircase lighting”; it will switch off on by the value “0”.
When selecting “Start with “1”, no action with “0””, it will switch on the staircase lights with the
value “1” received by the object “Output of staircase lighting” and no reaction with “0”.
When selecting “Start with “0/1”, cannot be stopped”, it will switch on the staircase lights either
with “0” or “1” received by the object “Output of staircase lighting” but cannot end it by the object
until
the duration time finished or changed by other operation
.
Parameter “During the lighting time, if receive the ‘start’ telegram”
Options:
Restart duration of staircase lighting
Ignored the “start” telegram