KNX/EIB
Switch Actuator with Secure
25
Parameter “Control mode of flashing”
The parameter states the mode of the flashing output. Options:
Star
t
with“1”,stop with “0”
Start with “0”,stop with “1”
Start with “1/0”, can not be stopped
It will start flashing with “1” received by the object “Switch out with flashing” when selecting “Star
with ‘1’, stop with ‘0’”; it will stop flashing with “0”.
It will start flashing with “0” received by the object “Switch out with flashing” when selecting “Star
with ‘0’, stop with ‘1’”; it will stop flashing with “1”.
It will start flashing with either “1” or “0” received by the object “Switch out with flashing” when
selecting “Star with ‘1/0’
,
cannot be stopped”; Under this circumstance it cannot terminate the flashing
by sending the telegram until the preset ending time
, unless it is blocked by other operation or wait
for execution finish.
4.4.1.3
Selection “Staircase lighting”
The parameter window of the staircase lighting function in Fig. 4.4.1.3 will be visible when
selecting “Staircase lighting” in the parameter “The mode of time function”.
Fig. 4.4.1.3 Parameter window “X: Time”-Staircase lighting