JVA ELECTRIC FENCE SYSTEMS
24
Installa
tion Pr
o
g
ramming Options
Keypad
number
Alarm
Reduce Power
0
9.0 V
8.0 V
1
9.5 V
8.5 V
2
10.0 V
9.0 V
3
10.5 V
9.5 V
4
11.0 V
10.0 V
5
11.5 V
10.5 V
6
12.0 V
11.0 V
7
12.5 V
11.5 V
8
13.0 V
12.0 V
9
13.5 V
12.5 V
Battery Alarm Voltage (07x#)
7.6.6 Battery Alarm Voltage (07x#)
This option sets the battery voltage
threshold below which the alarm will
activate. The default Battery Alarm Voltage
is 10.0 Volts and the unit will drop to low
power at 9.0 Volts (after beeping 4 times).
If the unit enters Low Power mode due
to a flat battery, the unit will automatically
return to high voltage, without warning,
when the mains voltage comes back on
and the battery voltage rises.
7.6.7 Siren On Time (08x#)
This option sets the duration of time that the
siren will remain on after a fence alarm occurs.
After this time the siren will turn off for the Siren
Off Time indicated in Table 7.6.8. The siren will
sound again if the alarm is still present after
this Siren Off Time has passed.
The default is 3 minutes. This may be the
subject of local regulations to stop an alarm
causing undue disturbance to neighbours, etc.
NOTE: The Siren On Time will be cut short if the
battery falls below the low battery level.
Value
Time
0
10 Seconds
1
30 Seconds
2
1 Minute
3
2 Minutes
4
3 Minutes
5
4 Minutes
6
5 Minutes
7
20 Minutes
8
45 Minutes
9
130 Minutes
Siren On Time (08x#)
7.6.8 Siren Off time (09x#)
This option sets the amount of time the siren
will be Off for after the Siren On Time above
has expired. If an alarm is still present after
this Off time, the siren will sound again.
Value
Time
0
10 Seconds
1
1 Minute
2
2 Minute
3
5 Minutes
4
10 Minutes
5
20 Minutes
6
30 Minutes
7
40 Minutes
8
50 Minutes
9
60 Minutes
Siren Off Time (09x#)