CAUTION:

Do not mix:

Fan modules with different airflow labels (AIR IN and AIR OUT) in the same chassis.

Power supplies with different airflow labels (AIR IN and AIR OUT) in the same chassis.

Fan modules and power supplies with different airflow labels (AIR IN and AIR OUT) in

the same chassis.

While replacing fan modules, you must remove only one fan module at a time from the rear panel of the

chassis. The switch continues to operate for a limited period of time (30 seconds) without thermal shutdown

while a fan module is being replaced..

NOTE:

All the fan modules must be installed for optimal functioning of the switch.

The fan modules are available in two models that have different airflow directions.

Back-to-front (air enters through the back of the switch), indicated by label AIR IN and azure blue color

Front-to-back (air exhausts through the back of the switch), indicated by label AIR OUT and gold color.

QFX5120 Models and Airflow Direction

Table 12 on page 43

shows the airflow direction in QFX5120 switch models.

Table 12: Airflow Direction in QFX5120 Switch Models

Power Supplies

Direction of

Airflow in the Fan

Module

Color of the Fan

Module

Fan Modules and

Power Supply

Model Number

For switches that

have fan modules

with the AIR OUT

label, you must

install only power

supplies that have

the AIR OUT label.

Front-to-back—air

intake to cool the

chassis is through

the vents on the

front panel of the

chassis, and hot air

exhausts through

the vents on the

rear panel of the

chassis.

Juniper Gold

The switch ships

with six fan

modules and two

AC power supplies,

each with a label

AIR OUT.

QFX5120-32C-AFO

43

Содержание QFX5120 Series

Страница 1: ...QFX5120 Switch Hardware Guide Published 2019 10 15 ...

Страница 2: ...uide Copyright 2019 Juniper Networks Inc All rights reserved The information in this document is current as of the date on the title page YEAR 2000 NOTICE Juniper Networks hardware and software products are Year 2000 compliant Junos OS has no known time related limitations through the year 2038 However the NTP application is known to have some difficulty in the year 2036 END USER LICENSE AGREEMENT...

Страница 3: ...quest with JTAC xvii Overview 1 QFX5120 System Overview 21 QFX5120 Switches Hardware Overview 21 Benefits of the QFX5120 Switch 22 QFX5120 Hardware 22 System Software 27 QFX5120 Power System 27 QFX5120 Switch Models 28 Identifying QFX5120 Switch Models 30 Chassis Physical Specifications for QFX5120 Switches 31 Field Replaceable Units in QFX5120 Switches 32 QFX5120 Chassis 32 QFX5120 Cooling System...

Страница 4: ... Power Supply Specifications for QFX5120 Switches 52 AC Power Cord Specifications for QFX5120 Switches 53 AC Power Supply LEDs in QFX5120 Switches 55 DC Power Supply in QFX5120 Switches 57 Characteristics of a DC Power Supply 58 DC Power Supply Airflow 59 QFX5120 DC Power Specifications 60 DC Power Supply LEDs in QFX5120 Switches 60 Site Planning Preparation and Specifications 2 Site Preparation C...

Страница 5: ...5120 Management Cable Specifications and Pinouts 81 Console Port Connector Pinout Information 81 RJ 45 Management Port Connector Pinout Information 82 RJ 45 to DB 9 Serial Port Adapter Pinout Information 83 QSFP QSFP28 SFP SFP and SFP28 Port Connector Pinout Information 83 Initial Installation and Configuration 3 Unpacking and Mounting the QFX5120 Switch 91 Unpacking the Switch 91 Parts Inventory ...

Страница 6: ...ling a Fan Module in a QFX5120 Switch 122 Maintaining the QFX5120 Power System 124 Removing Power Supply from a QFX5120 Switch 124 Connecting AC Power to a QFX5120 Switch 126 Maintaining Transceivers 129 Removing a Transceiver 129 Removing a QSFP28 Transceiver 132 Installing a Transceiver 134 Installing a QSFP28 Transceiver 136 Maintaining Fiber Optic Cables 138 Connecting a Fiber Optic Cable 138 ...

Страница 7: ...Obtain Return Material Authorization 154 Packing a QFX5120 Switch or Component for Shipping 155 Packing a QFX5120 Switch for Shipping 155 Packing QFX5120 Switch Components for Shipping 157 Safety and Compliance Information 7 General Safety Guidelines and Warnings 161 Definitions of Safety Warning Levels 162 Qualified Personnel Warning 164 Warning Statement for Norway and Sweden 165 Fire Safety Req...

Страница 8: ...eneral Electrical Safety Guidelines and Warnings 190 Action to Take After an Electrical Accident 191 Prevention of Electrostatic Discharge Damage 191 AC Power Electrical Safety Guidelines 193 AC Power Disconnection Warning 194 DC Power Electrical Safety Guidelines 195 DC Power Disconnection Warning 196 DC Power Grounding Requirements and Warning 198 DC Power Wiring Sequence Warning 200 DC Power Wi...

Страница 9: ...European Community 211 Israel 211 Japan 211 Korea 212 Tawain 212 United States 212 Nonregulatory Environmental Standards 213 ix ...

Страница 10: ...product documentation page on the Juniper Networks website at https www juniper net documentation If the information in the latest release notes differs from the information in the documentation follow the product Release Notes Juniper Networks Books publishes books by Juniper Networks engineers and subject matter experts These books go beyond the technical documentation to explore the nuances of ...

Страница 11: ...1 From the HTML or PDF version of the manual copy a configuration example into a text file save the file with a name and copy the file to a directory on your routing platform For example copy the following configuration to a file and name the file ex script conf Copy the ex script conf file to the var tmp directory on your routing platform system scripts commit file ex script xsl interfaces fxp0 d...

Страница 12: ...g platform commit file ex script snippet xsl 2 Move to the hierarchy level that is relevant for this snippet by issuing the following configuration mode command edit user host edit system scripts edit system scripts 3 Merge the contents of the file into your routing platform configuration by issuing the load merge relative configuration mode command edit system scripts user host load merge relativ...

Страница 13: ...e text and syntax conventions used in this guide Table 2 Text and Syntax Conventions Examples Description Convention To enter configuration mode type the configure command user host configure Represents text that you type Bold text like this user host show chassis alarms No alarms currently active Represents output that appears on the terminal screen Fixed width text like this A policy term is a n...

Страница 14: ...ub default metric metric Encloses optional keywords or variables angle brackets broadcast multicast string1 string2 string3 Indicates a choice between the mutually exclusive keywords or variables on either side of the symbol The set of choices is often enclosed in parentheses for clarity pipe symbol rsvp Required for dynamic MPLS only Indicates a comment specified on the same line as the configura...

Страница 15: ...stem Click TechLibrary Feedback on the lower right of any page on the Juniper Networks TechLibrary site and do one of the following Click the thumbs up icon if the information on the page was helpful to you Click the thumbs down icon if the information on the page was not helpful to you or if you have suggestions for improvement and use the pop up form to provide feedback E mail Send your comments...

Страница 16: ...niper net Find product documentation https www juniper net documentation Find solutions and answer questions using our Knowledge Base https kb juniper net Download the latest versions of software and review release notes https www juniper net customers csc software Search technical bulletins for relevant hardware and software notifications https kb juniper net InfoCenter Join and participate in th...

Страница 17: ...1 CHAPTER Overview QFX5120 System Overview 21 QFX5120 Chassis 32 QFX5120 Cooling System 41 QFX5120 Power System 49 ...

Страница 18: ......

Страница 19: ...ervers the QFX5120 is designed for extremely agile data centers that demand support for overlay and underlay network architectures The QFX5120 includes native 25 Gigabit Ethernet fiber only and 100 Gigabit Ethernet fixed configuration options with rich L2 L3 Ethernet VPN EVPN and MPLS features In addition to a high throughput Packet Forwarding Engine PFE the performance of the QFX5120 control plan...

Страница 20: ...s core aggregation capabilities aimed at enterprises with campus networks that want a compact and highly scalable solution Industry leading 25 Gbps and 100 Gbps wire speeds The QFX5120 Switch offers industry leading high density 25 Gbps and 100 Gbps wire speeds that support 48 ports at 100 Gbps or 48 ports at 25 Gbps and 8 100 Gbps uplink ports Common data center protocols The QFX5120 also uses da...

Страница 21: ...h 48 SFP28 ports and eight 100 Gbps quad small form factor pluggable QSFP28 ports Each SFP28 port can operate as a native 25 Gigabit Ethernet port 10 Gigabit Ethernet port and can act as a 1 Gbps port based on the transceivers inserted Each of the eight uplink ports can operate as either 100 G or 40 G based on the optics used You can use breakout cables to configure the ports as per your requireme...

Страница 22: ...r QFX5120 32C you cannot configure four independent 10 Gigabit ports or four independent 25 Gigabit ports using breakout cables on port 31 However you can configure two independent 50 G ports on this port Both the QFX5120 32C and QFX5120 48Y offer A 2 2 GHz quad core Intel CPU with 16 GB memory and 64 GB SSD storage Feature rich automation capabilities with support for Python and Zero Touch Provis...

Страница 23: ... g051102 1 2 1 2 1 Fan modules AC power supply in slot 0 AC power supply in slot 1 Figure 7 on page 25 shows the rear panel of a QFX5120 48Y switch with AC Power Supplies Figure 8 Components on the Rear Panel of a QFX5120 48Y Switch with AC Power Supplies g051002 1 3 4 5 6 2 12 11 10 8 9 7 7 7 1 Power Supply LEDs Chassis Status LEDs 8 2 Fan Module LEDs Console Port 9 3 RJ 45 Management Port C0 RJ ...

Страница 24: ... 1 Power Supply LEDs Chassis Status LEDs 8 2 Fan Module LEDs Console Port 9 3 RJ 45 Management Port C0 RJ 45 Management Port C1 10 4 Reset Button ESD Point 11 5 USB Port Fan module 12 6 CLEI Label Power Supplies Table 3 on page 26 lists the QFX5120 switch models and their components Table 3 Components in QFX5120 Switches Power Supply Shipped by Default Fan Modules Shipped by Default Built in Ports...

Страница 25: ...C AFO2 Two 650 W DC power supplies 1 1 redundancy Five fan modules each with an AIR IN AFI label 48x25G SFP28 ports and 8x100G QSFP28 ports QFX5120 48Y DC AFI2 System Software Juniper Networks QFX Series Ethernet Switches run Junos OS operating system Junos OS which provides Layer 2 and Layer 3 switching routing and security services QFX5120 Power System QFX5120 48Y switches support two AC or DC p...

Страница 26: ... and DC power supplies depending on the switch model All models of the QFX5120 ship with two power supplies and five fans installed by default Table 4 on page 28 lists the components shipped with QFX5120 switch models Table 4 QFX5120 Switch Models and Shipped Components Airflow Power Supply Ports Product Numbers Front to back air intake to cool the chassis is through the vents on the front panel o...

Страница 27: ...e front panel of the chassis AC 48 SFP28 8 QSFP28 QFX5120 48Y AFI2 Front to back air intake to cool the chassis is through the vents on the front panel of the chassis and hot air exhausts through the vents on the rear panel of the chassis DC 48 SFP28 8 QSFP28 QFX5120 48Y DC AFO2 Back to front air intake to cool the chassis is through the vents on the rear panel of the chassis and hot air exhausts ...

Страница 28: ...y Flags 0x00 Version REV D CLEI Code ID QFX5120 48Y FRU Model Number QFX5120 48Y AFO2 The model number of your switch is one of the following QFX5120 32C AFO QFX5120 32C AFI QFX5120 48Y AFO2 QFX5120 48Y AFI2 QFX5120 48Y DC AFO2 QFX5120 48Y DC AFI2 In the sample output the switch model is QFX5120 48Y AFO2 Meaning In QFX5120 switch model numbers The 48Y in the model number indicates that the number ...

Страница 29: ... physical specifications of the QFX5120 32C switch Table 5 Physical Specifications of the QFX5120 32C Switch Chassis Value Description 1 7 in 43 25 mm Chassis height 17 26 in 438 4 mm Chassis width 20 27 in 515 0 mm excluding fan and power supply handles Chassis depth 21 12 lbs 9 12 kg with two power supplies and fans installed Weight Table 6 on page 31 shows the physical specifications of the QFX...

Страница 30: ...tion If you want to purchase any of these components you must order them separately NOTE If you have a Juniper J Care service contract register any addition change or upgrade of hardware components at https www juniper net customers support tools updateinstallbase Failure to do so can result in significant delays if you need replacement parts This note does not apply if you replace existing compon...

Страница 31: ...dels that have front to back airflow the air intake to cool the chassis is through the vents on the front panel of the switch and hot air exhausts through the vents on the rear panel Figure 11 on page 33 shows the front to back airflow through a QFX5120 32C switch chassis Figure 11 Front to Back Airflow Through QFX5120 32C Switch Chassis g051123 Ports FRUs Figure 12 on page 34 shows the front to b...

Страница 32: ...e fan modules have AIR OUT AFO labels QFX5120 Models with Back to Front Airflow In the QFX5120 switch models that have back to front airflow the air intake to cool the chassis is through the vents on the rear panel and hot air exhausts through the vents on the front panel of the switch Figure 13 on page 35 shows the back to front airflow through QFX5120 32C switch chassis 34 ...

Страница 33: ... Switch Chassis g022524 Ports FRUs You must install only power supplies that have AIR IN AFI labels in switches in which the fan modules have AIR IN AFI labels The labels on the power supplies and fan modules must match the labels on the switch chassis Mixing components with AIR IN AFI and AIR OUT AFO labels in the same chassis hampers the performance of the cooling system of the switch and leads ...

Страница 34: ...Status A QFX5120 switch has a status LED for each fan module next to the fan module slot on the rear panel of the chassis The status LED indicates the status of the fan module Table 7 on page 36 describes the status LED on the fan module of a QFX5120 switch Table 7 Fan Module Status LED Description State Color LED The fan module is functioning normally On steadily Green Status An error has been de...

Страница 35: ...16 on page 37 shows the location of management port on QFX5120 48Y Figure 16 LEDs on the QFX5120 48Y Management Port g051028 2 1 2 1 Link Activity LED Status LED Table 8 on page 37 shows the link activity LED on the management port on QFX5120 switches Table 8 Link Activity LED on the Management Port on QFX5120 Switches State and Description Color LED Blinking The port and the link are active and t...

Страница 36: ...Ds that show the link activity and status of the port Each QSFP28 on a QFX5120 32C switch has four LEDs The first LED is for non channelized ports and the other three are for channelized ports The built in QSFP28 port on a QFX5120 48Y switch has four LEDs that shows both the link activity and status of the port in a QFX5120 48Y switch Figure 17 on page 38 shows the LEDs on the QSFP28 network ports...

Страница 37: ...Port LEDs Figure 20 on page 39 shows the LEDs on the QSFP28 network ports on QFX5120 48Y Figure 20 LEDs on the SFP28 Network Ports QFX5120 48Y g022531 1 2 2 1 Status LED Link Activity LED Each QSFP28 port on a QFX5120 32C switch has four LEDs which display the link activity and status of the port The first LED denotes non channelized ports and the other three denote channelized ports Each QSFP28 p...

Страница 38: ...ng A 25 10 Gigabit link is established in channelized mode but there is no link activity A 25 10 Gigabit link is established in channelized mode and there is link activity On steadily Green 2 4 Blinking All four LEDs blink to indicate the beacon function was enabled on the port NOTE Note that the beacon function is not available for the QFX5120 32C switch Blinking Amber All Table 10 on page 40 des...

Страница 39: ...an modules and the fans that are part of the power supplies The QFX5120 32C has six fan modules and the QFX5120 48Y has five fan modules You can order a QFX5120 that works in one of two airflow directions The airflow direction depends on the fan modules and power supplies that are installed in the switch QFX5120 switches provide back to front airflow air enters through the back of the switch indic...

Страница 40: ... In or Airflow Out The fan modules are also color coded according to the airflow direction Figure 21 on page 42 shows the QFX5120 32C fan module Figure 21 QFX5120 32C AFI Fan Module g051119 Figure 22 on page 42 shows the QFX5120 48Y fan module Figure 22 QFX5120 48Y AFI2 Fan Module g022520 For QFX5120 32C the six fan modules are numbered 0 through 5 counting from left to right For QFX5120 48Y the f...

Страница 41: ... to front air enters through the back of the switch indicated by label AIR IN and azure blue color Front to back air exhausts through the back of the switch indicated by label AIR OUT and gold color QFX5120 Models and Airflow Direction Table 12 on page 43 shows the airflow direction in QFX5120 switch models Table 12 Airflow Direction in QFX5120 Switch Models Power Supplies Direction of Airflow in ...

Страница 42: ...have fan modules with the AIR OUT label you must install only power supplies that have the AIR OUT label Front to back air intake to cool the chassis is through the vents on the front panel of the chassis and hot air exhausts through the vents on the rear panel of the chassis Juniper Gold The switch ships with five fan modules and two AC power supplies each with a label AIR OUT QFX5120 48Y AFO2 Fo...

Страница 43: ... must install only power supplies that have the AIR IN label Back to front air intake to cool the chassis is through the vents on the rear panel of the chassis and hot air exhausts through the vents on the front panel of the chassis Juniper Azure Blue The switch ships with five fan modules and two DC power supplies each with a label AIR IN QFX5120 48Y DC AFI2 CAUTION Do not mix AC and DC power sup...

Страница 44: ...0 32C Switch Chassis g051123 Ports FRUs Figure 12 on page 34 shows the front to back airflow through the QFX5120 48Y switch chassis Figure 24 Front to Back Airflow Through QFX5120 48Y Switch Chassis g022525 Ports FRUs You must install only power supplies that have AIR OUT labels in switches in which the fan modules have AIR OUT labels 46 ...

Страница 45: ... on the rear panel and hot air exhausts through the vents on the front panel of the switch Figure 13 on page 35 shows the back to front airflow through QFX5120 32C switch chassis Figure 25 Back to Front Airflow Through QFX5120 32C Switch Chassis g051124 Ports FRUs Figure 14 on page 35 shows the back to front airflow through the QFX5120 48Y switch chassis 47 ...

Страница 46: ... chassis Mixing components with AIR IN and AIR OUT labels in the same chassis hampers the performance of the cooling system of the switch and leads to overheating of the chassis CAUTION The system raises an alarm if a fan module fails or if the ambient temperature inside the chassis rises above the acceptable range If the temperature inside the chassis rises above the threshold temperature the sys...

Страница 47: ...s possible Either the fan has failed or it is seated incorrectly To maintain proper airflow through the chassis leave the fan module installed in the chassis until you are ready to replace it Blinking Amber Under normal operating conditions the fan modules operate at a moderate speed Temperature sensors in the chassis monitor the temperature within the chassis The system raises an alarm if a fan m...

Страница 48: ...es for the QFX5120 switch are fully redundant load sharing and hot removable and hot insertable FRUs The QFX5120 switch models are shipped with two power supplies pre installed in the rear panel of the chassis NOTE Currently QFX5120 32C switch supports only AC power supplies AC Power Supply Specifications for QFX5120 Switches QFX5120 switches support two 650 W AC power supplies Figure 27 on page 5...

Страница 49: ...ither have labels on the handles that indicate the direction of airflow or they have color coded handles with a fan icon AIR IN AFI label or a blue colored handle indicates back to front airflow while AIR OUT AFO label or a gold colored handle indicates front to back airflow See Figure 29 on page 51 Figure 29 Power Supply Handle Detail 1 AIR IN AFI label Be sure to use the correct power supply for...

Страница 50: ...t replace all the fans and power supplies at one time to use the new direction Table 14 on page 52 lists the AC and DC power supplies used in QFX5120 switches and the direction of airflow in them Table 14 Airflow Direction in Power Supplies for QFX5120 Switches Color of Power Supply Handle Direction of Airflow Product Number Juniper Gold Front to back JPSU 650W AC AO Juniper Azure Blue Back to fro...

Страница 51: ... 50 60 Hz AC input line frequency 7 8A at 100 120 VAC 3 8A at 200 240 VAC AC input current rating 260W Typical Power Consumption 450W Maximum power AC Power Cord Specifications for QFX5120 Switches A detachable AC power cord is supplied with the AC power supplies The coupler is type C13 as described by International Electrotechnical Commission IEC standard 60320 The plug at the male end of the pow...

Страница 52: ...0 Hz Australia CBL EX PWR C13 BR NBR 14136 Type BR 3 250 VAC 10 A 50 Hz Brazil CBL EX PWR C13 CH GB 1002 1996 Type PRC 3 250 VAC 10 A 50 Hz China CBL EX PWR C13 EU CEE 7 VII Type VIIG 250 VAC 10 A 50 Hz Europe except Italy Switzerland and United Kingdom CBL EX PWR C13 IN IS 1293 Type IND 3 250 VAC 10 A 50 Hz India CBL EX PWR C13 IL SI 32 1971 Type IL 3G 250 VAC 10 A 50 Hz Israel CBL EX PWR C13 IT ...

Страница 53: ...dom Figure 30 on page 55 illustrates the plug on the power cord for some of the countries or regions listed in Table 17 on page 54 Figure 30 AC Plug Types AC Power Supply LEDs in QFX5120 Switches Figure 31 on page 55 shows the location of the LED on an AC power supply for QFX5120 32C switches Figure 31 AC Power Supply LED on AC Power Supply for QFX5120 32C Switches g051109 1 1 Bicolored LED Table ...

Страница 54: ...gh the chassis leave the power supply installed in the chassis until you are ready to replace it On steadily Red The internal fan in the power supply has failed Replace the power supply as soon as possible To maintain proper airflow through the chassis leave the power supply installed in the chassis until you are ready to replace it Blinking Figure 32 on page 56 shows the location of the LEDs on a...

Страница 55: ... supply Replace the power supply as soon as possible To maintain proper airflow through the chassis leave the power supply installed in the chassis until you are ready to replace it On steadily Amber Fault NOTE If the AC OK LED and the DC OK LED are not lit green either the AC power cord is not installed properly or the power input voltage is not within normal operating range If the AC OK LED is l...

Страница 56: ...T AFO in the same chassis Fan modules with different airflow labels AIR IN AFI and AIR OUT AFO in the same chassis Power supplies and fan modules with different airflow labels AIR IN AFI and AIR OUT AFO in the same chassis This topic includes Characteristics of a DC Power Supply QFX5120 switches support 650 W DC power supply see Figure 33 on page 58 Figure 33 DC Power Supply for an QFX5120 Switch ...

Страница 57: ...nput current rating 38 through 60 VDC NOTE The minimum input power required to power on the switch is 43 5 0 5 VDC After the switch is powered on the operating range is 38 through 60 VDC Operating range To prevent electrical injury while installing or removing DC power supplies carefully follow instructions in Connecting DC Power to a QFX5120 Switch on page 101 and Maintaining the QFX5120 Power Sy...

Страница 58: ...air exhausts through the vents on the front panel of the chassis AIR IN AFI JPSU 650 DC AFI QFX5120 DC Power Specifications The typical and maximum power consumption values are calculated using dummy transceivers on all ports Traffic is run at 25 C ambient Table 22 DC Power Specifications for QFX5120 48Y Specifications Item Rated operating voltage 48 VDC to 60 VDC Operating voltage range 40 8 VDC ...

Страница 59: ...ct the terminals to different sources Table 23 on page 61 describes the LEDs on the DC power supplies Table 23 DC Power Supply LEDs on a QFX5120 48Y Switch Description State Color Name The power supply is disconnected from power or power is not coming into the power supply Off Unlit In Power is coming into the power supply On steadily Green The power supply is disconnected from power or the power ...

Страница 60: ...iption State Color Name An error has been detected in the power supply Replace the power supply as soon as possible To maintain proper airflow through the chassis leave the power supply installed in the chassis until you are ready to replace it On steadily Amber Fault 62 ...

Страница 61: ...eparation and Specifications Site Preparation Checklist for QFX5120 Switches 65 QFX5120 Site Guidelines and Requirements 66 QFX5120 Network Cable and Transceiver Planning 73 QFX5120 Management Cable Specifications and Pinouts 81 ...

Страница 62: ......

Страница 63: ...e for QFX5120 Switches on page 71 Measure the distance between external power sources and the switch installation site Locate sites to connect system grounding AC Power Supply Specifications for QFX5120 Switches on page 52 QFX5120 DC Power Specifications on page 60 Calculate the power consumption and requirements Hardware Configuration QFX5120 Switches Hardware Overview on page 21 Choose the numbe...

Страница 64: ... and management QFX5120 Site Guidelines and Requirements IN THIS SECTION Environmental Requirements and Specifications for QFX5120 Switches 66 General Site Guidelines 68 Site Electrical Wiring Guidelines 68 Rack Requirements for QFX5120 Switches 69 Cabinet Requirements for QFX5120 Switches 70 Clearance Requirements for Airflow and Hardware Maintenance for QFX5120 Switches 71 Environmental Requirem...

Страница 65: ...requirements per NEBS GR 63 CORE Issue 3 Normal operation ensured in temperature range of 32 F through 104 F 0 C through 40 C Non operating storage temperature in shipping container 40 F through 158 F 40 C through 70 C Normal operation ensured in relative humidity range of 5 through 90 noncondensing No performance degradation to 6000 feet 1829 meters QFX5120 48Y Normal operation ensured in tempera...

Страница 66: ...cause components to fail completely or intermittently over time Install the device in a secure area so that only authorized personnel can access the device Site Electrical Wiring Guidelines Table 26 on page 68 describes the factors you must consider while planning the electrical wiring at your site WARNING You must provide a properly grounded and shielded environment and use electrical surge suppr...

Страница 67: ...and receivers in the device Electrical hazards as a result of power surges conducted over the lines into the equipment Electromagnetic compatibility Rack Requirements for QFX5120 Switches QFX5120 switches are designed to be installed on four post racks Rack requirements consist of Rack type Mounting bracket hole spacing Rack size and strength Table 27 on page 69 provides the rack requirements and ...

Страница 68: ...ch needs to be mounted flush with the rack and still adjustable for racks with different depths The front and rear rack rails must be spaced between 23 62 in 600 mm and 31 5 in 800 mm front to back The rack must be strong enough to support the weight of the switch Ensure that the spacing of rails and adjacent racks allows for proper clearance around the switch and rack Rack size and strength Secur...

Страница 69: ...h removing the hot air exhaust The QFX5120 fans exhaust hot air either through the vents on the port panel or through the fans and power supplies Install the switch in the cabinet in a way that maximizes the open space on the FRU side of the chassis This maximizes the clearance for critical airflow Route and dress all cables to minimize the blockage of airflow to and from the chassis Ensure that t...

Страница 70: ...onnel to remove and install hardware components Figure 35 QFX5120 48Y Switch Clearance Requirements for Airflow and Hardware Maintenance If you re installing a QFX5120 32C Switch note that the dimensions for the grounding lug are different see Figure 36 on page 73 The dimensions are as follows Grounding wire 14 AWG Lug 4 3 mm Circular Lug Screw 8mm screw used for tightening the Lug 72 ...

Страница 71: ...tach Copper Cables for QFX5120 Switches 74 QSFP28 Direct Attach Copper Cables for QFX5120 Switches 76 Cable Specifications for QSFP and QSFP28 Transceivers on QFX5120 Switches 77 Calculating the Fiber Optic Cable Power Budget for QFX Series Switches 78 Calculating the Fiber Optic Cable Power Margin for QFX Series Switches 79 Pluggable Transceivers Supported on QFX5120 Switches QFX5120 switches sup...

Страница 72: ...P28 transceivers installed in QFX5120 switches support digital optical monitoring DOM You can view the diagnostic details for these transceivers by issuing the operational mode CLI command show interfaces diagnostics SFP28 Direct Attach Copper Cables for QFX5120 Switches IN THIS SECTION Cable Specifications 75 Standards Supported by These Cables 75 Small form factor pluggable transceiver SFP28 dir...

Страница 73: ...ve DAC cables See Figure 37 on page 75 Figure 37 SFP28 Direct Attach Copper Cables for QFX5120 Switches The cables are hot removable and hot insertable You can remove and replace them without powering off the switch or disrupting switch functions A cable comprises a low voltage cable assembly that connects directly into two 25 Gigabit Ethernet ports one at each end of the cable The cables use high...

Страница 74: ...third party optic or cable the Juniper Networks Technical Assistance Center JTAC can help you diagnose the source of the problem Your JTAC engineer might recommend that you check the third party optic or cable and potentially replace it with an equivalent Juniper Networks optic or cable that is qualified for the device Cable Specifications QSFP28 passive DAC cables are hot removable and hot insert...

Страница 75: ...ency approvals use only a properly constructed shielded cable TIP Ensure that you order cables with the correct polarity Vendors refer to these crossover cables as key up to key up latch up to latch up Type B or Method B If you are using patch panels between two QSFP ports ensure that the proper polarity is maintained through the cable plant Table 29 on page 77 describes the signals on each fiber ...

Страница 76: ...in Pin 12 1 11 2 10 3 9 4 8 5 7 6 6 7 5 8 4 9 3 10 2 11 1 12 Calculating the Fiber Optic Cable Power Budget for QFX Series Switches Calculate the fiber optic data link s power budget when planning fiber optic cable layout and distances to ensure that fiber optic connections have sufficient power for correct operation The power budget is the maximum amount of power the link can transmit When you ca...

Страница 77: ...to ensure that fiber optic connections have sufficient signal power to overcome system losses and still satisfy the minimum input requirements of the receiver for the required performance level The power margin P M is the amount of power available after attenuation or link loss LL has been subtracted from the power budget P B When you calculate the power margin you use a worst case analysis to pro...

Страница 78: ... less than 500 MHz km Modal and chromatic dispersion 0 dBm Single mode None This example assumes five connectors Loss for five connectors 5 x 0 5 dBm 2 5 dBm 0 5 dBm Connector This example assumes two splices Loss for two splices 2 0 5 dBm 1 dBm 0 5 dBm Splice This example assumes the link is 2 km long Fiber attenuation for 2 km 2 km 1 dBm km 2 dBm Multimode 1 dBm km Fiber attenuation This example...

Страница 79: ...o DB 9 Serial Port Adapter Pinout Information 83 QSFP QSFP28 SFP SFP and SFP28 Port Connector Pinout Information 83 Console Port Connector Pinout Information The console port on a Juniper Networks device is an RS 232 serial interface that uses an RJ 45 connector to connect to a console management device The default baud rate for the console port is 9600 baud Table 32 on page 82 provides the pinout...

Страница 80: ...ector Pinout Information Table 33 on page 82 provides the pinout information for the RJ 45 connector for the management port on Juniper Networks devices Table 33 RJ 45 Management Port Connector Pinout Information Description Signal Pin Transmit receive data pair 1 TRP1 1 Transmit receive data pair 1 TRP1 2 Transmit receive data pair 2 TRP2 3 Transmit receive data pair 3 TRP3 4 Transmit receive dat...

Страница 81: ...45 to DB 9 female adapter along with a USB to DB 9 male adapter Table 34 on page 83 provides the pinout information for the RJ 45 to DB 9 serial port adapter Table 34 RJ 45 to DB 9 Serial Port Adapter Pinout Information Signal DB 9 Pin Signal RJ 45 Pin CTS 8 RTS 1 DSR 6 DTR 2 RXD 2 TXD 3 GND 5 GND 4 TXD 3 RXD 6 DTR 4 DSR 7 RTS 7 CTS 8 QSFP QSFP28 SFP SFP and SFP28 Port Connector Pinout Information...

Страница 82: ...l indication RX_LOS 8 Module receiver ground VeeR 9 Module receiver ground VeeR 10 Module receiver ground VeeR 11 Receiver inverted data output RD 12 Receiver noninverted data output RD 13 Module receiver ground VeeR 14 Module receiver 3 3 V supply VccR 15 Module transmitter 3 3 V supply VccT 16 Module transmitter ground VeeT 17 Transmitter noninverted data input TD 18 Transmitter inverted data in...

Страница 83: ... of signal indication RX_LOS 8 Rate select 1 optionally controls SFP transmitter RS1 9 Module receiver ground VeeR 10 Module receiver ground VeeR 11 Receiver inverted data output RD 12 Receiver noninverted data output RD 13 Module receiver ground VeeR 14 Module receiver 3 3 V supply VccR 15 Module transmitter 3 3 V supply VccT 16 Module transmitter ground VeeT 17 Transmitter noninverted data input...

Страница 84: ...FP28 Network Port Connector Pinout Information Signal Pin GND 1 TX2n 2 TX2p 3 GND 4 TX4n 5 TX4p 6 GND 7 ModSelL 8 LPMode_Reset 9 VccRx 10 SCL 11 SDA 12 GND 13 RX3p 14 RX3n 15 GND 16 RX1p 17 RX1n 18 GND 19 GND 20 RX2n 21 86 ...

Страница 85: ...and QSFP28 Network Port Connector Pinout Information continued Signal Pin RX2p 22 GND 23 RX4n 24 RX4p 25 GND 26 ModPrsL 27 IntL 28 VccTx 29 Vcc1 30 Reserved 31 GND 32 TX3p 33 TX3n 34 GND 35 TX1p 36 TX1n 37 GND 38 87 ...

Страница 86: ...on and Configuration Unpacking and Mounting the QFX5120 Switch 91 Connecting the QFX5120 to Power 98 Connecting the QFX5120 to the Network 106 Connecting the QFX5120 to External Devices 110 Configuring Junos OS on the QFX5120 112 ...

Страница 87: ......

Страница 88: ...s are maximally protected inside the shipping carton Do not unpack the switches until you are ready to begin installation To unpack the switch 1 Move the shipping carton to a staging area as close to the installation site as possible but where you have enough room to remove the system components 2 Position the carton so that the arrows marked on the carton are pointing up 3 Open the top flaps on t...

Страница 89: ...tions in countries without toll free numbers see https www juniper net support requesting support html Table 38 on page 92 lists the parts and their quantities as in the standard packing list for a QFX5120 switch Table 38 Inventory of Components Provided with an QFX5120 Switch Quantity Component 1 Switch 5 preinstalled 6 preinstalled QFX5120 48Y QFX5120 32C Fan modules 2 AC or DC preinstalled QFX5...

Страница 90: ...s that do not have registered serial numbers or accurate installation base data Register your product s at https tools juniper net svcreg SRegSerialNum jsp Update your installation base at https www juniper net customers csc management updateinstallbase jsp Mounting a QFX5120 Switch on Four Posts of a Rack or Cabinet The four post rack mounting kit ships with the short front mounting brackets atta...

Страница 91: ...u begin mounting a QFX5120 switch ensure that you have the following parts and tools available Phillips screwdriver number 2 not provided Screws to secure the chassis and the rear mounting brackets to the rack not provided 6 flat head 4 40 Phillips mounting screws provided with the four post rack mounting kit 12 flat head 4x6 mm Phillips mounting screws provided with the four post rack mounting ki...

Страница 92: ...hilips number 2 screwdriver For QFX5120 32C ensure that the remaining four holes in the side mounting rails are aligned with the four holes in the side panel 4 Insert 4x6 mm Phillips flat head mounting screws into the remaining four holes in the side mounting rails and tighten the screws by using the Phillips number 2 screwdriver See Figure 39 on page 95 Figure 40 on page 95 andFigure 41 on page 9...

Страница 93: ... both the front mounting brackets with a hole in each rack rail making sure that the chassis is level 6 Have a second person secure the front of the switch to the rack by using the appropriate screws for your rack Tighten the screws See Figure 42 on page 96 and Figure 43 on page 96 Figure 42 Mounting a QFX5120 48Y Switch on Front Posts of a Rack g022534 Figure 43 Mounting a QFX5120 32C Switch on F...

Страница 94: ...necting Rear Mounting Brackets to a QFX5120 48Y Switch g022535 Figure 45 Connecting Rear Mounting Brackets to a QFX5120 32C Switch g0xxxxx g051135 9 Ensure that the switch chassis is level by verifying that all the screws on the front of the rack are aligned with the screws at the back of the rack NOTE We recommend that you install cover panels in all unused power supply slots 97 ...

Страница 95: ...Earth Ground to a QFX5120 Switch To connect earth ground to a switch 1 Connect one end of the grounding cable to a proper earth ground such as the rack in which the switch is mounted 2 Place the grounding lug attached to the grounding cable over the protective earthing terminal See Figure 46 on page 98 and Figure 47 on page 99 Figure 46 Connecting a Grounding Cable to a QFX5120 48Y Switch 98 ...

Страница 96: ...y is a hot removable and hot insertable field replaceable unit FRU when the second power supply is installed and running You can install replacement power supplies in the two slots next to the fan modules without powering off the switch or disrupting switch functions Ensure that you have a power cord appropriate for your geographical location available to connect AC power to the switch Before you ...

Страница 97: ...wer outlet by using the AC power cord appropriate for your geographical location To connect AC power to a QFX5120 1 Attach the grounding strap to your bare wrist and to a site ESD point 2 Ensure that the power supplies are fully inserted in the chassis and the latches are secure If only one power supply is installed ensure that a blank cover panel is installed over the second power supply slot 3 L...

Страница 98: ...move power from the power supply and replace the power supply Do not remove the power supply until you have a replacement power supply ready the power supplies or a blank cover panel must be installed in the switch to ensure proper airflow CAUTION Replace a failed power supply with a blank panel or new power supply within one minute of removal to prevent chassis overheating Connecting DC Power to ...

Страница 99: ...rrectly attached lug can damage the switch for example by causing a short circuit To meet safety and electromagnetic interference EMI requirements and to ensure proper operation you must connect the chassis to earth ground before you connect it to power For installations that require a separate grounding conductor to the chassis use the protective earthing terminal on the switch chassis to connect...

Страница 100: ...ower source cable leads is 0 V and that the cable leads do not become active while you are connecting DC power NOTE The V terminals are referred to as RTN and V terminals are referred to as 48 V in DC Power Wiring Sequence Warning on page 200 and DC Power Electrical Safety Guidelines on page 195 4 Ensure that the power supplies are fully inserted in the chassis 5 Remove the terminal block cover Th...

Страница 101: ...ON The connection between each power source and power supply must include a circuit breaker Do not connect two sources to a single power supply because doing so can potentially cause circulating current in feed wires whenever there is any difference in the voltage of the two sources a Secure the ring lug of the positive DC power source cable to the V terminal on the DC power supply b Secure the ri...

Страница 102: ...minals 48V 7 3 Output LED Terminal block 8 4 Input LED Ejector lever CAUTION The V terminals are shunted internally together as are the V terminals The same polarity terminal can be wired together from the same source to provide an additional current path in a higher power chassis Do not connect the terminals to different sources See Figure 51 on page 106 105 ...

Страница 103: ...he device 10 Verify that the IN and OUT LEDs on the power supply are lit green and are on steadily Connecting the QFX5120 to the Network IN THIS SECTION Installing a Transceiver 106 Connecting a Fiber Optic Cable 109 Installing a Transceiver The transceivers for Juniper Networks devices are hot removable and hot insertable field replaceable units FRUs You can remove and replace them without poweri...

Страница 104: ...re you begin to install a transceiver in a device ensure that you have taken the necessary precautions for safe handling of lasers see Laser and LED Safety Guidelines and Warnings on page 178 Ensure that you have a rubber safety cap available to cover the transceiver Figure 52 on page 108 shows how to install a QSFP transceiver The procedure is the same for all types of transceivers except the QSF...

Страница 105: ...the empty port The connectors must face the chassis CAUTION Before you slide the transceiver into the port ensure that the transceiver is aligned correctly Misalignment might cause the pins to bend making the transceiver unusable 6 Slide the transceiver in gently until it is fully seated If you are installing a CFP transceiver tighten the captive screws on the transceiver by using your fingers 7 R...

Страница 106: ...bber safety cap remove the cap Save the cap 2 Remove the rubber safety cap from the optical transceiver Save the cap 3 Insert the cable connector into the optical transceiver see Figure 53 on page 109 Figure 53 Connecting a Fiber Optic Cable to an Optical Transceiver Installed in a Device 4 Secure the cables so that they do not support their own weight Place excess cable out of the way in a neatly...

Страница 107: ... an Ethernet cable with an RJ 45 connector Use the management port to connect the device to the management device Ensure that you have an Ethernet cable that has an RJ 45 connector at either end Figure 54 on page 110 shows the RJ 45 connector of the Ethernet cable supplied with the device Figure 54 RJ 45 Connector on an Ethernet Cable To connect a device to a network for out of band management see...

Страница 108: ...ct an Ethernet cable with an RJ 45 connector Use the console port to connect the device to the console server or management console The console port accepts a cable that has an RJ 45 connector Ensure that you have an Ethernet cable that has an RJ 45 connector at either end One such cable and an RJ 45 to DB 9 serial port adapter are supplied with the device Figure 56 on page 111 shows the RJ 45 con...

Страница 109: ...page 112 1 Connect one end of the Ethernet cable to the console port labeled CON CONSOLE or CON1 on the device 2 Connect the other end of the Ethernet cable to the console server see Figure 57 on page 112 or management console see Figure 58 on page 112 Figure 57 Connecting a Device to a Management Console Through a Console Server g020547 CON To Console port Console server PC Figure 58 Connecting a...

Страница 110: ... topic shows the factory default configuration file of a QFX5120 switch system syslog user any emergency file messages any notice authorization info file interactive commands interactive commands any commit factory settings Connecting and Configuring a QFX5120 Switch The QFX5120 switch is shipped with the Junos OS preinstalled and ready to be configured when the switch is powered on You must perfo...

Страница 111: ...raffic For complete information about enabling the switch to forward traffic including examples see the Junos OS configuration guides To configure the software 1 Verify that the switch is powered on 2 Log in as the root user There is no password 3 Start the CLI root cli root 4 Enter configuration mode cli configure edit root 5 Set the root authentication password by entering either a clear text pa...

Страница 112: ... in double quotation marks edit root set system host name host name 7 Create a user account edit root set system login user user name authentication plain text password New password password Retype new password password 8 Set the user account class to super user edit root set system login user user name class super user 9 Configure the switch s domain name edit root set system domain name domain n...

Страница 113: ...o remote subnets with access to the management port Access to the management port is limited to the local subnet edit root set routing options static route remote subnet next hop destination IP retain no readvertise 14 Configure the telnet service at the edit system services hierarchy level edit root set system services telnet 15 Optional Display the configuration to verify that it is correct edit...

Страница 114: ...witch edit root commit 17 Optional Configure additional properties by adding the necessary configuration statements Then commit the changes to activate them on the switch edit root switch commit 18 When you have finished configuring the switch exit configuration mode edit root switch exit root switch 117 ...

Страница 115: ...4 CHAPTER Maintaining Components Maintaining the QFX5120 Cooling System 121 Maintaining the QFX5120 Power System 124 Maintaining Transceivers 129 Maintaining Fiber Optic Cables 138 ...

Страница 116: ......

Страница 117: ...t A replacement fan module NOTE The fan module slots are at the left side of the rear panel Figure 59 on page 122 shows how to remove a fan module 1 Place the antistatic bag or the antistatic mat on a flat stable surface 2 Loosen the captive screws on the front faceplate of the fan module by using your fingers If you are unable to loosen the captive screws by using your fingers use the screwdriver...

Страница 118: ... 1 redundant fans and QFX5120 32C comes with 5 1 redundant fans Each fan module is a hot removable and hot insertable field replaceable unit FRU installed in the rear panel of the switch You can remove and replace it without powering off the switch or disrupting switch functions CAUTION Do not mix Fan modules with different airflow labels AIR IN AFI and AIR OUT AFO in the same chassis Power suppli...

Страница 119: ...eed replacement parts This note does not apply if you replace existing components with the same type of component 1 Ensure that you have the correct fan module The label AIR IN AFI or AIR OUT AFO on the fan module must match the label AIR IN AFI or AIR OUT AFO on the installed power supply 2 Attach the ESD grounding strap to your bare wrist and connect the strap to the ESD point on the chassis 3 R...

Страница 120: ...g AC Power to a QFX5120 Switch 126 Removing Power Supply from a QFX5120 Switch All QFX5120 switches are shipped from the factory with two power supplies Each power supply is a hot removable and hot insertable field replaceable unit FRU when the second power supply is installed and running You can install replacement power supplies in the two slots next to the fan modules without powering off the s...

Страница 121: ...lled in your QFX5120 you need to power off the switch before removing the power supply 3 Disconnect power to the switch AC power supply If the AC power source outlet has a power switch set it to the off O position If the AC power source outlet does not have a power switch gently pull out the male end of the power cord connected to the power source outlet DC power supply Switch the circuit breaker ...

Страница 122: ...re 62 Removing a Power Supply from a QFX5120 48Y Switch g022512 Figure 63 Removing a Power Supply from a QFX5120 32C Switch g051111 Connecting AC Power to a QFX5120 Switch The QFX5120 is shipped with two 650 W power supplies pre installed Each power supply is a hot removable and hot insertable field replaceable unit FRU when the second power supply is installed and running You can install replacem...

Страница 123: ...h ground The switch gains additional grounding when you plug the power supply in the switch into a grounded AC power outlet by using the AC power cord appropriate for your geographical location To connect AC power to a QFX5120 1 Attach the grounding strap to your bare wrist and to a site ESD point 2 Ensure that the power supplies are fully inserted in the chassis and the latches are secure If only...

Страница 124: ...er source outlet 8 Verify that the AC and DC LEDs on each power supply are lit green If the amber fault LED is lit remove power from the power supply and replace the power supply Do not remove the power supply until you have a replacement power supply ready the power supplies or a blank cover panel must be installed in the switch to ensure proper airflow CAUTION Replace a failed power supply with ...

Страница 125: ...a device ensure that you have taken the necessary precautions for the safe handling of lasers see Laser and LED Safety Guidelines and Warnings on page 178 Ensure that you have the following parts and tools available An antistatic bag or an antistatic mat Rubber safety caps to cover the transceiver and fiber optic cable connector A dust cover to cover the port or a replacement transceiver Figure 66...

Страница 126: ... when inserting or removing a cable The rubber safety cap keeps the port clean and prevents accidental exposure to laser light CAUTION Do not bend fiber optic cables beyond their minimum bend radius An arc smaller than a few inches in diameter can damage the cables and cause problems that are difficult to diagnose 4 Remove the cable connected to the transceiver see Disconnecting a Fiber Optic Cabl...

Страница 127: ...revent electrostatic discharge ESD damage to the transceiver do not touch the connector pins at the end of the transceiver Figure 66 Removing an SFP SFP XFP or a QSFP Transceiver 1 Ejector lever To remove a CFP transceiver a Loosen the screws on the transceiver by using your fingers b Grasp the screws on the transceiver and gently slide the transceiver approximately 0 5 in 1 3 cm straight out of t...

Страница 128: ...fore you begin to remove a transceiver from a device ensure that you have taken the necessary precautions for safe handling of lasers see Laser and LED Safety Guidelines and Warnings on page 178 Ensure that you have the following parts and tools available An antistatic bag or an antistatic mat Rubber safety caps to cover the transceiver and fiber optic cable connector A dust cover to cover the por...

Страница 129: ...wn weight as it hangs to the floor Place excess cable out of the way in a neatly coiled loop in the cable management system Placing fasteners on the loop helps to maintain its shape CAUTION Do not bend the fiber optic cable beyond its minimum bend radius An arc smaller than a few inches in diameter can damage the cable and cause problems that are difficult to diagnose Figure 67 Removing a QSFP28 T...

Страница 130: ...ngineer might recommend that you check the third party optic or cable and potentially replace it with an equivalent Juniper Networks optic or cable that is qualified for the device Before you begin to install a transceiver in a device ensure that you have taken the necessary precautions for safe handling of lasers see Laser and LED Safety Guidelines and Warnings on page 178 Ensure that you have a ...

Страница 131: ...rt before installing a new transceiver 5 Using both hands carefully place the transceiver in the empty port The connectors must face the chassis CAUTION Before you slide the transceiver into the port ensure that the transceiver is aligned correctly Misalignment might cause the pins to bend making the transceiver unusable 6 Slide the transceiver in gently until it is fully seated If you are install...

Страница 132: ...hased from Juniper Networks with your Juniper Networks device CAUTION If you face a problem running a Juniper Networks device that uses a third party optic or cable the Juniper Networks Technical Assistance Center JTAC can help you diagnose the source of the problem Your JTAC engineer might recommend that you check the third party optic or cable and potentially replace it with an equivalent Junipe...

Страница 133: ...ansceiver and the end of the cable and insert the cable into the transceiver WARNING Do not look directly into a fiber optic transceiver or into the ends of fiber optic cables Fiber optic transceivers and fiber optic cable connected to a transceiver emit laser light that can damage your eyes CAUTION Do not leave a fiber optic transceiver uncovered except when inserting or removing cable The safety...

Страница 134: ... the cable and cause problems that are difficult to diagnose Maintaining Fiber Optic Cables IN THIS SECTION Connecting a Fiber Optic Cable 138 Disconnecting a Fiber Optic Cable 139 Maintaining Fiber Optic Cables 140 Connecting a Fiber Optic Cable Before you begin to connect a fiber optic cable to an optical transceiver installed in a device ensure that you have taken the necessary precautions for ...

Страница 135: ...nnecting a Fiber Optic Cable to an Optical Transceiver Installed in a Device 4 Secure the cables so that they do not support their own weight Place excess cable out of the way in a neatly coiled loop Placing fasteners on a loop helps cables maintain their shape CAUTION Do not bend fiber optic cables beyond their minimum bend radius An arc smaller than a few inches in diameter can damage the cables...

Страница 136: ...vice set interface name disable WARNING Do not look directly into a fiber optic transceiver or into the ends of fiber optic cables Fiber optic transceivers and fiber optic cables connected to transceivers emit laser light that can damage your eyes 2 Carefully unplug the fiber optic cable connector from the transceiver 3 Cover the transceiver with a rubber safety cap WARNING Do not leave a fiber op...

Страница 137: ...s which are expensive to repair Attach a short fiber extension to the optical equipment Any wear and tear due to frequent plugging and unplugging is then absorbed by the short fiber extension which is easier and less expensive to replace than the instruments Keep fiber optic cable connections clean Microdeposits of oil and dust in the canal of the transceiver or cable connector can cause loss of l...

Страница 138: ...5 CHAPTER Troubleshooting Hardware Troubleshooting QFX5120 Components 145 ...

Страница 139: ......

Страница 140: ...yellow alarm conditions for chassis components Alarm Failure event that triggers an alarm Alarm condition Seriousness of the alarm The level of severity can be either major red or minor yellow Major red Indicates a critical situation on the device that has resulted from one of the following conditions A red alarm condition requires immediate action One or more hardware components have failed One o...

Страница 141: ...gure to alert you when an interface is down To configure an interface link down condition to trigger a red or yellow alarm or to configure the link down condition to be ignored use the alarm statement at the edit chassis hierarchy level You can specify the ethernet fibre channel or management ethernet interface type NOTE Fibre Channel alarms are only valid on QFX3500 devices NOTE When red alarms o...

Страница 142: ...vice on another Juniper Networks switch or router or any PC or laptop that supports Linux The steps you take to create the emergency boot device vary depending on the device To create an emergency boot device 1 Use FTP to copy the installation media image into the var tmp directory on the device 2 Insert a USB device into the USB port 3 From the Junos OS command line interface CLI start the shell ...

Страница 143: ... install media host usb ex 4e flex x86 64 18 3R1 10 secure img 11006 1 records in 11006 1 records out 180332544 bytes transferred in 71 764266 secs 2512846 bytes sec 6 Log out of the shell root device exit exit user device 148 ...

Страница 144: ...6 CHAPTER Contacting Customer Support and Returning the Chassis or Components Returning a QFX5120 Chassis or Components 151 ...

Страница 145: ......

Страница 146: ...e the serial number of the chassis if you need to return the switch If you need to return one or more components determine the serial number for each component 2 Obtain an RMA number from JTAC as described in Contacting Customer Support to Obtain Return Material Authorization on page 154 NOTE Do not return any component to Juniper Networks unless you have first obtained an RMA number Juniper Netwo...

Страница 147: ...u do not have access to the CLI or if the serial number for the component does not appear in the command output you can locate the serial number ID label on the physical switch or component NOTE If you want to find the serial number on the physical switch component you will need to remove the component from the switch chassis for which you must have the required parts and tools available Listing t...

Страница 148: ...these FRUs you must remove the FRU from the switch chassis to see the FRU s serial number ID label Power Supply The serial number ID label is on the top of the power supply To see the location of the serial number ID label on the AC and DC power supplies see Figure 73 on page 153 and Figure 73 on page 153 Figure 72 Location of the Serial Number ID Labels on QFX5120 48Y AC Power Supply g022539 1 Fi...

Страница 149: ...nent you want to return open a service request with Juniper Networks Technical Assistance Center JTAC on the Web or by telephone Before you request an RMA number from JTAC be prepared to provide the following information Your existing service request number if you have one Serial number of the component Your name organization name telephone number fax number and shipping address Details of the fai...

Страница 150: ... you have Followed all the steps listed in Contacting Customer Support to Obtain Return Material Authorization on page 154 Retrieved the original shipping carton and packing materials Contact your JTAC representative if you do not have these materials to learn about approved packing materials See Contacting Customer Support to Obtain Return Material Authorization on page 154 Ensure you understand ...

Страница 151: ...h See Removing a Transceiver on page 129 Ensure that you have the following parts and tools available to pack the switch Phillips screwdriver number 2 not provided The original switch packing material cardboard box accessory box and its contents and foam padding ESD grounding strap Antistatic bag CAUTION Do not pack the switch in anything except its original container or the switch might be damage...

Страница 152: ...unding strap CAUTION Do not stack switch components Return individual components in separate boxes if they do not fit together on one level in the shipping box To pack the switch components Place individual components in antistatic bags Use the original packing materials if they are available If the original packing materials are not available ensure the component is adequately packed to prevent d...

Страница 153: ...ts 165 Installation Instructions Warning 167 Chassis and Component Lifting Guidelines 167 Restricted Access Warning 169 Ramp Warning 171 Rack Mounting and Cabinet Mounting Warnings 171 Grounded Equipment Warning 176 Radiation from Open Port Apertures Warning 177 Laser and LED Safety Guidelines and Warnings 178 Maintenance and Operational Safety Guidelines and Warnings 181 General Electrical Safety...

Страница 154: ...Power Electrical Safety Guidelines 195 DC Power Disconnection Warning 196 DC Power Grounding Requirements and Warning 198 DC Power Wiring Sequence Warning 200 DC Power Wiring Terminations Warning 203 Multiple Power Supplies Disconnection Warning 206 TN Power Warning 207 Agency Approvals for QFX5120 Switches 207 Compliance Statements for EMC Requirements for the QFX Series 209 ...

Страница 155: ...l or manipulate wiring during electrical storms Never install electrical jacks in wet locations unless the jacks are specifically designed for wet environments Operate the device only when it is properly grounded Ensure that the separate protective earthing terminal provided on this device is permanently connected to earth Replace fuses only with fuses of the same type and rating Do not open or re...

Страница 156: ...ls of safety warnings there are two Warning formats NOTE You might find this information helpful in a particular situation or you might overlook this important information if it was not highlighted in a Note CAUTION You need to observe the specified guidelines to prevent minor injury or discomfort to you or severe damage to the device WARNING This symbol alerts you to the risk of personal injury f...

Страница 157: ...e befinden sich in einer Situation die zu einer Körperverletzung führen könnte Bevor Sie mit der Arbeit an irgendeinem Gerät beginnen seien Sie sich der mit elektrischen Stromkreisen verbundenen Gefahren und der Standardpraktiken zur Vermeidung von Unfällen bewußt Avvertenza Questo simbolo di avvertenza indica un pericolo La situazione potrebbe causare infortuni alle persone Prima di lavorare su q...

Страница 158: ...ention Tout installation ou remplacement de l appareil doit être réalisé par du personnel qualifié et compétent Warnung Gerät nur von geschultem qualifiziertem Personal installieren oder auswechseln lassen Avvertenza Solo personale addestrato e qualificato deve essere autorizzato ad installare o sostituire questo apparecchio Advarsel Kun kvalifisert personell med riktig opplæring bør montere eller...

Страница 159: ...on equipment be available in the event of a fire in the vicinity of the equipment and that all local fire safety and electrical codes and ordinances be observed when you install and operate your equipment Fire Suppression In the event of an electrical hazard or an electrical fire you should first turn power off to the equipment at the source Then use a Type C fire extinguisher which uses noncorros...

Страница 160: ...ny equipment in a room in which a chemical fire extinguisher has been discharged is subject to premature failure and unreliable operation The equipment is considered to be irreparably damaged NOTE To keep warranties effective do not use a dry chemical fire extinguisher to control a fire at or near a Juniper Networks device If a dry chemical fire extinguisher is used the unit is no longer eligible ...

Страница 161: ...s til strømkilden Aviso Leia as instruções de instalação antes de ligar o sistema à sua fonte de energia Atención Ver las instrucciones de instalación antes de conectar el sistema a la red de alimentación Varning Läs installationsanvisningarna innan du kopplar systemet till dess strömförsörjningsenhet Chassis and Component Lifting Guidelines Before moving the device to a site ensure that the site ...

Страница 162: ...o or more people 70 5 lb 32 kg to 121 2 lb 55 kg Three or more people Above 121 2 lbs 55 kg Material handling systems such as levers slings lifts and so on must be used When this is not practical specially trained persons or systems must be used riggers or movers 168 ...

Страница 163: ...Restricted Access Warning 169 ...

Страница 164: ... sécurité est sous le contrôle de l autorité responsable de l emplacement Warnung Diese Einheit ist zur Installation in Bereichen mit beschränktem Zutritt vorgesehen Ein Bereich mit beschränktem Zutritt ist ein Bereich zu dem nur Wartungspersonal mit einem Spezialwerkzeugs Schloß und Schlüssel oder anderer Sicherheitsvorkehrungen Zugang hat und der von dem für die Anlage zuständigen Gremium kontro...

Страница 165: ...prijplaat niet onder een hoek van meer dan 10 graden Varoitus Älä käytä sellaista kaltevaa pintaa jonka kaltevuus ylittää 10 astetta Attention Ne pas utiliser une rampe dont l inclinaison est supérieure à 10 degrés Warnung Keine Rampen mit einer Neigung von mehr als 10 Grad verwenden Avvertenza Non usare una rampa con pendenza superiore a 10 gradi Advarsel Bruk aldri en rampe som heller mer enn 10...

Страница 166: ...kerd Dit toestel dient onderaan in het rek gemonteerd te worden als het toestel het enige in het rek is Wanneer u dit toestel in een gedeeltelijk gevuld rek monteert dient u het rek van onderen naar boven te laden met het zwaarste onderdeel onderaan in het rek Als het rek voorzien is van stabiliseringshulpmiddelen dient u de stabilisatoren te monteren voordat u het toestel in het rek monteert of h...

Страница 167: ...sollte sie unten im Gestell angebracht werden Bei Anbringung dieser Einheit in einem zum Teil gefüllten Gestell ist das Gestell von unten nach oben zu laden wobei das schwerste Bauteil unten im Gestell anzubringen ist Wird das Gestell mit Stabilisierungszubehör geliefert sind zuerst die Stabilisatoren zu installieren bevor Sie die Einheit im Gestell anbringen oder sie warten Avvertenza Per evitare...

Страница 168: ... deverá ser instalado numa prateleira fixa à estrutura do edificio Esta unidade deverá ser montada na parte inferior da estante caso seja esta a única unidade a ser montada Ao montar esta unidade numa estante parcialmente ocupada coloque os itens mais pesados na parte inferior da estante arrumando os de baixo para cima Se a estante possuir um dispositivo de estabilização instale o antes de montar ...

Страница 169: ...r Networks switch måste installeras i en ställning som är förankrad i byggnadens struktur Om denna enhet är den enda enheten på ställningen skall den installeras längst ned på ställningen Om denna enhet installeras på en delvis fylld ställning skall ställningen fyllas nedifrån och upp med de tyngsta enheterna längst ned på ställningen Om ställningen är försedd med stabiliseringsdon skall dessa mon...

Страница 170: ...Dieses Gerät muß geerdet werden Stellen Sie sicher daß das Host Gerät während des normalen Betriebs an Erde gelegt ist Avvertenza Questa apparecchiatura deve essere collegata a massa Accertarsi che il dispositivo host sia collegato alla massa di terra durante il normale utilizzo Advarsel Dette utstyret skal jordes Forviss deg om vertsterminalen er jordet ved normalt bruk Aviso Este equipamento dev...

Страница 171: ... Vermeiden Sie es sich den Strahlungen auszusetzen und starren Sie nicht in die Öffnungen Avvertenza Quando i cavi in fibra non sono inseriti radiazioni invisibili possono essere emesse attraverso l apertura della porta Evitate di esporvi alle radiazioni e non guardate direttamente nelle aperture Advarsel Unngå utsettelse for stråling og stirr ikke inn i åpninger som er åpne fordi usynlig stråling...

Страница 172: ...following guidelines and warnings General Laser Safety Guidelines When working around ports that support optical transceivers observe the following safety guidelines to prevent eye injury Do not look into unterminated ports or at fibers that connect to unknown sources Do not examine unterminated optical ports with optical instruments Avoid direct exposure to the beam WARNING Unterminated optical c...

Страница 173: ...laser produkt Varoitus Luokan 1 lasertuote Attention Produit laser de classe I Warnung Laserprodukt der Klasse 1 Avvertenza Prodotto laser di Classe 1 Advarsel Laserprodukt av klasse 1 Aviso Produto laser de classe 1 Atención Producto láser Clase I Varning Laserprodukt av klass 1 179 ...

Страница 174: ...us Luokan 1 valodiodituote Attention Alarme de produit LED Class I Warnung Class 1 LED Produktwarnung Avvertenza Avvertenza prodotto LED di Classe 1 Advarsel LED produkt i klasse 1 Aviso Produto de classe 1 com LED Atención Aviso sobre producto LED de Clase 1 Varning Lysdiodprodukt av klass 1 180 ...

Страница 175: ...kt mit optischen Geräten prüfen Avvertenza Non fissare il raggio con gli occhi né usare strumenti ottici per osservarlo direttamente Advarsel Stirr eller se ikke direkte p strlen med optiske instrumenter Aviso Não olhe fixamente para o raio nem olhe para ele directamente com instrumentos ópticos Atención No mirar fijamente el haz ni observarlo directamente con instrumentos ópticos Varning Rikta in...

Страница 176: ...Operating Temperature Warning 187 Product Disposal Warning 189 While performing the maintenance activities for devices observe the following guidelines and warnings 182 ...

Страница 177: ...leichen oder vom Hersteller empfohlenen Batterietyp Entsorgen Sie die benutzten Batterien nach den Anweisungen des Herstellers Advarsel Det kan være fare for eksplosjon hvis batteriet skiftes på feil måte Skift kun med samme eller tilsvarende type som er anbefalt av produsenten Kasser brukte batterier i henhold til produsentens instruksjoner Avvertenza Pericolo di esplosione se la batteria non è i...

Страница 178: ...Jewelry Removal Warning 184 ...

Страница 179: ...n Schmuck einschließlich Ringe Ketten und Uhren abnehmen Metallgegenstände erhitzen sich wenn sie an das Netz und die Erde angeschlossen werden und können schwere Verbrennungen verursachen oder an die Anschlußklemmen angeschweißt werden Avvertenza Prima di intervenire su apparecchiature collegate alle linee di alimentazione togliersi qualsiasi monile inclusi anelli collane braccialetti ed orologi ...

Страница 180: ...rissa äläkä yhdistä tai irrota kaapeleita ukkosilmalla Attention Ne pas travailler sur le système ni brancher ou débrancher les câbles pendant un orage Warnung Arbeiten Sie nicht am System und schließen Sie keine Kabel an bzw trennen Sie keine ab wenn es gewittert Avvertenza Non lavorare sul sistema o collegare oppure scollegare i cavi durante un temporale con fulmini Advarsel Utfør aldri arbeid p...

Страница 181: ...Operating Temperature Warning 187 ...

Страница 182: ...iner Gegend betrieben werden in der die Umgebungstemperatur das empfohlene Maximum von 40 C überschreitet Um Lüftungsverschluß zu verhindern achten Sie darauf daß mindestens 15 2 cm lichter Raum um die Lüftungsöffnungen herum frei bleibt Avvertenza Per evitare il surriscaldamento dei switch non adoperateli in un locale che ecceda la temperatura ambientale massima di 40 C Per evitare che la circola...

Страница 183: ...sia lakeja ja säännöksiä noudattaen Attention La mise au rebut définitive de ce produit doit être effectuée conformément à toutes les lois et réglementations en vigueur Warnung Dieses Produkt muß den geltenden Gesetzen und Vorschriften entsprechend entsorgt werden Avvertenza L eliminazione finale di questo prodotto deve essere eseguita osservando le normative italiane vigenti in materia Advarsel E...

Страница 184: ... other end of the strap around your bare wrist Failure to use an ESD grounding strap could result in damage to the device Install the device in compliance with the following local national and international electrical codes United States National Fire Protection Association NFPA 70 United States National Electrical Code Other countries International Electromechanical Commission IEC 60364 Part 1 th...

Страница 185: ...the following actions in this order 1 Use caution Be aware of potentially hazardous conditions that could cause further injury 2 Disconnect power from the device 3 If possible send another person to get medical aid Otherwise assess the condition of the victim then call for help Prevention of Electrostatic Discharge Damage Device components that are shipped in antistatic bags are sensitive to damag...

Страница 186: ...ng strap is available touch the exposed bare metal of the device to ground yourself before handling the component Avoid contact between the component that is subject to ESD damage and your clothing ESD voltages emitted from clothing can damage components When removing or installing a component that is subject to ESD damage always place it component side up on an antistatic surface in an antistatic...

Страница 187: ...only a grounding type power outlet Do not circumvent this safety feature Equipment grounding must comply with local and national electrical codes You must provide an external certified circuit breaker 2 pole circuit breaker or 4 pole circuit breaker based on your device rated minimum 20 A in the building installation The power cord serves as the main disconnecting device for the AC powered device ...

Страница 188: ...der in der Nähe von Netzgeräten arbeiten ziehen Sie bei Wechselstromeinheiten das Netzkabel ab bzw Avvertenza Prima di lavorare su un telaio o intorno ad alimentatori scollegare il cavo di alimentazione sulle unità CA Advarsel Før det utføres arbeid på kabinettet eller det arbeides i nærheten av strømforsyningsenheter skal strømledningen trekkes ut på vekselstrømsenheter Aviso Antes de trabalhar n...

Страница 189: ...70 NOTE Primary overcurrent protection is provided by the building circuit breaker This breaker must protect against excess currents short circuits and earth grounding faults in accordance with NEC ANSI NFPA 70 Ensure that the polarity of the DC input wiring is correct Under certain conditions connections with reversed polarity might trip the primary circuit breaker or damage the equipment For per...

Страница 190: ...DC Power Disconnection Warning 196 ...

Страница 191: ... le panneau de service du circuit en courant continu placer le disjoncteur en position fermée OFF et à l aide d un ruban adhésif bloquer la poignée du disjoncteur en position OFF Warnung Vor Ausführung der folgenden Vorgänge ist sicherzustellen daß die Gleichstromschaltung keinen Strom erhält Um sicherzustellen daß sämtlicher Strom abgestellt ist machen Sie auf der Schalttafel den Unterbrecher für...

Страница 192: ...tor automático en posición de Apagado OFF Varning Innan du utför någon av följande procedurer måste du kontrollera att strömförsörjningen till likströmskretsen är bruten Kontrollera att all strömförsörjning är BRUTEN genom att slå AV det överspänningsskydd som skyddar likströmskretsen och tejpa fast överspänningsskyddets omkopplare i FRÅN läget DC Power Grounding Requirements and Warning An insula...

Страница 193: ...ier et déconnectée en dernier Warnung Der Erdanschluß muß bei der Installation der Einheit immer zuerst hergestellt und zuletzt abgetrennt werden Avvertenza In fase di installazione dell unità eseguire sempre per primo il collegamento a massa e disconnetterlo per ultimo Advarsel Når enheten installeres må jordledningen alltid tilkobles først og frakobles sist Aviso Ao instalar a unidade a ligação ...

Страница 194: ...DC Power Wiring Sequence Warning 200 ...

Страница 195: ...lié d abord et débranché pour la dernière fois Warnung Die Stromzufuhr ist nur mit geeigneten Ringösen an das DC Netzteil anzuschliessen Die richtige Anschlusssequenz ist Erdanschluss zu Erdanschluss RTN zu RTN und dann 48V zu 48V Die richtige Sequenz zum Abtrennen der Stromversorgung ist 48V zu 48V RTN zu RTN und dann Erdanschluss zu Erdanschluss Es ist zu beachten dass der Erdanschluss immer zue...

Страница 196: ...TN a RTN então 48 V a 48 V Ao desconectar a potência a seqüência apropriada da fiação é 48 V a 48 V RTN a RTN moeu então para moer Anote que o fio à terra deve sempre ser conectado primeiramente e desconectado por último Anote que o fio à terra deve sempre ser conectado primeiramente e desconectado por último Varning Korrekt kopplingssekvens ar jord till jord RTN till RTN 48 V till 48 V Korrekt ko...

Страница 197: ...DC Power Wiring Terminations Warning 203 ...

Страница 198: ...conducteur Warnung Wenn Litzenverdrahtung erforderlich ist sind zugelassene Verdrahtungsabschlüsse z B für einen geschlossenen Regelkreis oder gabelförmig mit nach oben gerichteten Kabelschuhen zu verwenden Diese Abschlüsse sollten die angemessene Größe für die Drähte haben und sowohl die Isolierung als auch den Leiter festklemmen Avvertenza Quando occorre usare trecce usare connettori omologati c...

Страница 199: ...etar tanto el aislante como el conductor Varning När flertrådiga ledningar krävs måste godkända ledningskontakter användas t ex kabelsko av sluten eller öppen typ med uppåtvänd tapp Storleken på dessa kontakter måste vara avpassad till ledningarna och måste kunna hålla både isoleringen och ledaren fastklämda 205 ...

Страница 200: ...inen Stromanschluß um Strom gänzlich von der Einheit fernzuhalten müssen alle Stromzufuhren abgetrennt sein Avvertenza Questa unità ha più di una connessione per alimentatore elettrico tutte le connessioni devono essere completamente rimosse per togliere l elettricità dall unità Advarsel Denne enheten har mer enn én strømtilkobling Alle tilkoblinger må kobles helt fra for å eliminere strøm fra enh...

Страница 201: ...sitivo foi criado para operar com sistemas de corrente TN Atención El equipo está diseñado para trabajar con sistemas de alimentación tipo TN Varning Enheten är konstruerad för användning tillsammans med elkraftssystem av TN typ Agency Approvals for QFX5120 Switches QFX5120 switches comply with the following standards Safety CAN CSA C22 2 No 60950 1 Safety of Information Technology Equipment UL 60...

Страница 202: ...characteristics Limits and methods of measurement EN 55035 2017 CISPR 35 2016 Electromagnetic compatibility of multimedia equipment Immunity requirements IEC EN 61000 Immunity Test AS NZS CISPR 32 2015 Australia New Zealand Radiated and Conducted Emissions FCC 47 CFR Part 15 USA Radiated and Conducted Emissions IC ICES 003 Canada Radiated and Conducted Emissions VCCI CISPR 32 2016 Japanese Radiate...

Страница 203: ... equipment Electro Magnetic Compatibility EMC requirements EN 300 386 V2 1 1 2016 07 Telecommunication network equipment Electro Magnetic Compatibility EMC requirements Harmonized Standard covering the essential requirements of the Directive 2014 30 EU EN 55032 2015 CISPR 32 2015 Electromagnetic compatibility of multimedia equipment Emission requirements EN 55024 2010 CISPR 24 2010 Information tec...

Страница 204: ... should ensure that it is permissible to connect the equipment to the facilities of the local telecommunications company The equipment must also be installed using an acceptable method of connection In some cases the inside wiring associated with a single line individual service may be extended by means of a certified connector assembly The customer should be aware that compliance with the above c...

Страница 205: ...from Hebrew Warning This product is Class A In residential environments the product may cause radio interference and in such a situation the user may be required to take adequate measures Japan The preceding translates as follows This is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures VCCI A 211 ...

Страница 206: ...easures United States The QFX Series device has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed a...

Страница 207: ... Compliance GR 1089 CORE Issue 6 EMC and Electrical Safety Generic Criteria for Network Telecommunications Equipment The equipment is suitable for installation in locations where the National Electrical Code NEC applies The battery return connection is to be treated as an Isolated DC return DC I as defined in GR 1089 CORE GR 63 CORE NEBS Physical Protection The equipment is suitable for installati...

Отзывы: