Art.-No.: 2095 LUX
elapses.
Minimum brightness
change for new
transmission of the
measured value
15 lux
30 lux
45 lux
60 lux
This parameter is used to set the
minimum brightness change for
automatically transmitting a new
brightness measured value.
This parameter is only visible if the
parameter "Transmit brightness
measured value" is parameterised to
"When the brightness value is changed"
or "When the brightness value is
changed & cyclically".
Cycle time for
brightness measured
value
15 seconds
30 seconds
60 seconds
5 minutes
10 minutes
15 minutes
30 minutes
60 minutes
This parameter is used to set the cycle
time for the automatic transmission of
the brightness measured value.
This parameter is only visible if the
parameter "Transmit brightness
measured value" is parameterised to
"Cyclically" or "When the brightness
value is changed & cyclically".
Transmit all switching
command and dimming
value
No
15 minutes
30 minutes
60 minutes
This parameter can be used if
necessary to activate cyclical
transmission of the last controller
switching command or dimming value.
Cyclical transmission is only performed
when automatic mode is switched on.
Response to bus
voltage return
Like before the bus
voltage failure
Automatic mode off
In case of bus voltage failure the current
status of the objects "Presence" and
"Automatic mode" and the last switching
command or dimming value sent by the
controller are saved in the non-volatile
memory. In case of bus voltage return
the brightness controller adopts the
status of the saved objects and then
enters the operating status determined
by the two status values and this
parameter. If the automatic mode should
be switched off when the bus voltage
returns, this can be defined via the
setting "Automatic mode off".
h
Constant light regulation (Only visible with "Operating mode = constant light regulation"!)
Setpoint as
Parameters
Communication object
This parameter is used to set whether
the setpoint for constant light regulation
should be set as a parameter to a fixed
value that can only be changed using
the ETS, or whether it should be
possible to change the brightness
setpoint at any time via the bus using a
communication object. The value
received via the communication object
overwrites the factory-set parameter
Page 21 of 27
Software "Brightness controller A01001"
Parameters