Art.-No.: 2095 LUX
Function:
Control output / master connection
Object
h
10
Function
8-bit value
Name
Master, dimming
value
Type
1-byte
DPT
5.001
Flag
C, -, T, R
Description
This object is only available for the operating mode "Constant light regulation".
The group address linked to this object can be used to transmit the dimming
value to the actuator via the bus.
In Master/Slave mode this object is used to control the actuator of the master
lighting group.
Function:
Slave connection / expansion of the luminaire groups
Object
h
11
Function
8-bit value
Name
Slave 1, dimming
value
Type
1-byte
DPT
5.001
Flag
C, -, T, R
Description
This object is only available in the operating mode "Constant light regulation"
in master/slave mode, if the number of slaves is set to 1 or more in the ETS.
The group address linked to this object can be used to transmit or query the
dimming value of the first slave luminaire group via the bus.
Function:
Slave connection / expansion of the luminaire groups
Object
h
12
Function
8-bit value
Name
Slave 2, dimming
value
Type
1-byte
DPT
5.001
Flag
C, -, T, R
Description
This object is only available in the operating mode "Constant light regulation"
in master/slave mode, if the number of slaves is set to 2 or more in the ETS.
The group address linked to this object can be used to transmit or query the
dimming value of the second slave luminaire group via the bus.
Function:
Slave connection / expansion of the luminaire groups
Object
h
13
Function
8-bit value
Name
Slave 3, dimming
value
Type
1-byte
DPT
5.001
Flag
C, -, T, R
Description
This object is only available in the operating mode "Constant light regulation"
in master/slave mode, if the number of slaves is set to 3 or more in the ETS.
The group address linked to this object can be used to transmit or query the
dimming value of the third slave luminaire group via the bus.
Function:
Slave connection / expansion of the luminaire groups
Object
h
14
Function
8-bit value
Name
Slave 4, dimming
value
Type
1-byte
DPT
5.001
Flag
C, -, T, R
Description
This object is only available in the operating mode "Constant light regulation"
in master/slave mode, if the number of slaves is set to 4 in the ETS. The group
address linked to this object can be used to transmit or query the dimming
value of the fourth slave luminaire group via the bus.
Page 16 of 27