7 Configuration level
27
7.8
C118 Display switch-off after timeout
7.9
C119 Warning alarm function
The warning alarm is indicated via LED KV and is output simultaneously at the binary output. The switching action can be
configured as an absolute value or as an interval to the limit value (relative).
k
Factory setting
Display switch off
Comment
0
inactive
Display is permanently switched on.
1
active
Display switches off after a timeout and re-appears,
as soon as a key is pressed.
Warning alarm function
Comment
0
inactive
Warning alarm and LED KV switched off.
1
absolute value
Warning alarm limit fixed.
2
Interval from the limit value
The warning alarm limit varies with the value of the limit set for switching
off the relay.