7 Configuration level
22
k
Factory setting
037
W3Re-W25Re D
Thermocouple
-1999 to +9999°C
-5 to +2500°C
039
Cu-CuNi T
Thermocouple EN 60584
-1999 to +9999°C
-205 to +405°C
040
Fe-CuNi J
Thermocouple EN 60584
-1999 to +9999°C
-205 to +1205°C
041
Cu-CuNi U
Thermocouple DIN 43710
-1999 to +9999°C
-205 to +605°C
042
Fe-CuNi L
Thermocouple DIN 43710
-1999 to +9999°C
-205 to +905°C
043
NiCr-Ni K
Thermocouple EN 60584
-1999 to +9999°C
-205 to +1377°C
044
Pt10Rh-Pt S
Thermocouple EN 60584
-1999 to +9999°C
-5 to +1773°C
045
Pt13Rh-Pt R
Thermocouple EN 60584
-1999 to +9999°C
-5 to +1773°C
046
Pt30Rh-Pt6Rh B
Thermocouple EN 60584
-1999 to +9999°C
295 to 1825°C
048
NiCrSi-NiSi N
Thermocouple EN 60584
-1999 to +9999°C
-105 to +1305°C
052
0 to 20 mA
-1999 to +9999°C
0 to 21mA
053
4 to 20 mA
-1999 to +9999°C
3.6 to 21mA
063
0 to 10 V
-1999 to +9999°C
0 to 10.5 V
071
2 to 10 V
-1999 to +9999°C
1.8 to 10.5V
v
Chapter 10.4 “Restricting the setting
range for the AL limit (minimum/maximum
value master)”
Analog input
Comment
Setting range for AL:
(can be restricted via
setup)
Limits for
overrange/
underrange
Содержание safetyM TB/TW
Страница 19: ...5 Commissioning the instrument 17 2011 12 31...
Страница 42: ...9 DIN approved probes 2011 12 31 40...
Страница 50: ...13 What if 2011 12 31 48...
Страница 51: ......