8 Technical data
31
DC voltage, DC current
NiCrSi-NiSi N
EN 60584
-100 to +1300°C
0.4%
Pt10Rh-Pt S
EN 60584
0 to +1768°C
0.4%
Pt13Rh-Pt R
EN 60584
0 to +1768°C
0.4%
Pt13Rh-Pt6Rh B EN 60584
300 to 1820°C
0.4%
W3Re-W25Re D
0 to +2495°C
0.4%
Cold junction
Pt 100, internal
Cold junction accuracy
± 1K
Sampling
210 ms
Input filter
2nd order digital filter; filter constant adjustable from 0 to 100secs
Features
also programmable in °F
1. Accuracy refers to the maximum extent of the measuring range.
Measuring range
Accuracy
0 to 20mA, voltage drop < 2 V
4 to 20mA, voltage drop < 2 V
0.2%
0 to 10V, input resistance > 100 k
Ω
2 to 10V, input resistance > 100 k
Ω
0.1%
Scaling
freely programmable within the limits
Sampling time
210 ms
Input filter
2nd order digital filter; filter constant adjustable from 0 to 100secs