background image

 

1592033070 XR70CHC EN r1.0 2019.01.30 

                           XR70CHC 

1/6 

 

DIGITAL CONTROLLER WITH  

BLUETOOTH CONNECTIVITY 

XR70CHC 

82 rel. 1.0.1 

 
1

 

GENERAL WARNINGS ................................................................................................................................... 1

 

2

 

GENERAL DESCRIPTION .............................................................................................................................. 1

 

3

 

REGULATION .................................................................................................................................................. 1

 

4

 

ENERGY SAVING ALGORITHM .................................................................................................................... 1

 

5

 

PULL DOWN FUNCTION ................................................................................................................................ 1

 

6

 

EVAPORATOR FANS ..................................................................................................................................... 1

 

7

 

CONDENSER FAN .......................................................................................................................................... 1

 

8

 

DEFROST ........................................................................................................................................................ 2

 

9

 

DIGITAL OUTPUT CONFIGURATION ........................................................................................................... 2

 

10

 

FRONT PANEL COMMANDS ......................................................................................................................... 2

 

11

 

PARAMETER MENU ....................................................................................................................................... 2

 

12

 

PARAMETERS ................................................................................................................................................ 3

 

13

 

DIGITAL INPUTS ............................................................................................................................................. 5

 

14

 

INSTALLATION AND MOUNTING .................................................................................................................. 5

 

15

 

OPTIONAL FEATURES .................................................................................................................................. 5

 

16

 

ELECTRICAL CONNECTIONS ....................................................................................................................... 5

 

17

 

USE THE HOT-KEY ........................................................................................................................................ 5

 

18

 

INTERNAL MEMORY ...................................................................................................................................... 5

 

19

 

ALARM SIGNALLING ...................................................................................................................................... 6

 

20

 

TECHNICAL DATA .......................................................................................................................................... 6

 

21

 

WIRINGS .......................................................................................................................................................... 6

 

22

 

BLUETOOTH COMMUNICATION .................................................................................................................. 6

 

 

1

 

GENERAL WARNINGS 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 
used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring 
the same and unchanged functionality. 

1.2

 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 
temperature changes with high atmospheric humidity to prevent formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.

r.l

.” (see 

address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 
other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel 
with inductive loads could be useful. 

2

 

GENERAL DESCRIPTION 

The 

XR70CHC

32x74x60mm format

, is a microprocessor-based controller suitable  for  applications 

on  medium  or  low  temperature  ventilated  refrigeration  units.  It  has  4  relay  outputs  to  control 
compressor, fans, light and defrost or auxiliary output. The device is also provided with up to 4 NTC, 
PTC or PT1000 probe inputs: the first one for temperature control, the second one to be located onto 
the  evaporator  to  control  the  defrost  termination  temperature  and  to  manage  the  fan  and  the  third, 
optional and located on the HOT-KEY port, used to control the condenser temperature. There is also a 
configurable digital input. By using the 

HOT-KEY

 it is possible to  program the instrument in  a quick 

and easy way. 
The controller has Bluetooth 4.2 connectivity.  

3

 

REGULATION 

The  regulation  is  performed  according  to 
the  temperature  measured  by  the 
thermostat  probe  with  a  positive 
differential  from  the  set  point:  if  the 
temperature  increases  and  reaches  set 
point  plus  differential,  the  compressor  will 
start.  The  compressor  will  stop  when  the 
temperature  reaches  the  set  point  value 
again. 

 

In  case  of  fault  because  of  the  thermostat  probe,  the  start  and  stop  of  the  compressor  are  timed 
through parameters 

CoF

 and 

Con

4

 

ENERGY SAVING ALGORITHM

 

4.1

 

DESCRIPTION 

The device permits to set different temperature to be used during normal and reduced power use. The 
standard SET-POINT (

SET

) is used to maintain the temperature at a certain value when the energy 

saving status (ES) is not active. On the other side, when the ES status is active a different SET-POINT 
(

SET_ES

),  higher  than  the  standard  one,  will  be  used.  The  parameter 

HES

  will  have  to  be  set  to 

change the regulation temperature according to the following formula: 

SET_ES = SET + HES 

There are also two different differential values for 

SET

 and 

SET_ES

, which are used for compressor 

cut-in  and  cut-out:  when  ES  status  is  active  the 

HYE

  parameter  will  be  used  instead  of  the 

HY

 

parameter. 

4.2

 

BASIC ENERGY SAVING ALGORITHM 

The energy saving status will be always saved in the internal memory to resume previous operation if 
a power failure occurs. It needs the presence of a door switch to work (for example: 

i1F=dor

). 

4.2.1

 

PARAMETER INVOLVED 

 

i1F or i2F:

 set as door input to monitor the appliance usage

 

 

StE:

 interval to change from normal to energy saving mode

 

 

EtS:

 interval to change from energy saving to normal mode

 

 

HES:

 differential for SETPOINT when energy saving mode active

 

 

HYE:

 differential for regulation when energy saving mode is active

 

 

dS:

 interval for door opening detection

 

 

LdE:

 light output controlled (OFF when energy saving mode is active)

 

 

FROM 

TO 

CHANGED BY 

Normal 

mode

 

Energy 
Saving

 

- Pushing the 

DOWN

 button for 3 sec (if enabled). 

- Door continuously closed for the 

StE

 time.

 

Energy 
Saving

 

Normal 

mode 

- Pushing the 

DOWN

 button for 3 sec (if enabled).  

- Controller in ES mode for the 

EtS

 time. 

- If the controller is in ES mode, it returns in Standard mode 
(normal set-point) after opening the door more than 

dS

 time.

 

  

NOTE: 

the  cycling  mode  (ES  -  Normal  mode  -  ES  -  etc.)  works  if 

i1F=dor

  and 

EtS

  and 

StE

  are 

different from zero. If 

EtS=0 

or

 StE=0, 

the controller will not change the operating mode,

 

and it will be 

possible to change from the normal mode to the energy saving mode by using ES button or by setting 

i1F=ES

. See the below diagrams where the status changing is described: 

5

 

PULL DOWN FUNCTION 

The Pull Down is automatically activated: 

 

After any defrost 

 

After power-on if 

T>SET+CCS

 

 

When the regulation probe temperature 

is:  

 

T>SET+HY+oHt

 value in normal mode 

 

T>SET+HES+HYE+oHE

 value in energy saving mode  

In this case, a different set-point value (

SET+CCS

) will be enabled. As soon as the room temperature reaches 

the 

SET+CCS

 value, the compressor will be stopped and the normal regulation will restart. 

NOTE:

 Pull Down 

function is disabled when 

CCS=0

 or 

CCt=0

The 

CCt

 parameter sets the maximum activation time for any pull down. When 

CCt

 expires, the Pull Down will 

be immediately stopped and the standard SET-POINT will be restored. 

6

 

EVAPORATOR FANS 

6.1

 

GENERAL DESCRIPTION 

The evaporator fan is can be managed by dedicated control. To enable it, an evaporator probe must 
be selected by using par. 

FAP

. Here follows the description of all the related parameters: 

 

FAP

: to select the evaporator fan probe 

 

FSt

: to select the evaporator fan deactivation setpoint 

 

HYF

: differential for evaporator fan activation 

 

FnC

 parameter it can be selected the evaporator fan working mode: 

o

 

FnC=C-n:

 evaporator fan will switch ON and OFF with the compressor and

 

will 

not run during defrost; when compressor is OFF, evaporator fan will start a duty-
cycle mode (see 

FoF

Fon

FF1

 and 

Fo1

 parameters). 

o

 

FnC=o-n:

 evaporator fan will run even if the compressor is off, and  will not run 

during defrost; 

o

 

FnC=C-Y: 

evaporator fan will switch ON and OFF with the compressor and will 

run  during  defrost;  when  compressor  is  OFF,  evaporator  fan  will  enter  a  duty-
cycle working mode (see 

FoF

Fon

FF1

 and 

Fo1

 parameters). 

o

 

FnC=o-Y: 

evaporator fan will run continuously, also during defrost. 

 

Fnd:

 activation delay after any defrost 

6.2

 

EVAPORATOR FAN AND DIGITAL INPUT 

When  the  digital  input  is  configured  as  door  switch  (

i1F=dor

),  evaporator  fan  and  compressor  status  will 

depend on the par. 

odC

 

odC=no

: normal regulation 

 

odC=FAn

: evaporator fan OFF 

 

odC=CPr

: compressor OFF 

 

odC=F-C

: compressor and evaporator fan OFF 

 
When 

rrd=Y

 the regulation will always restart after a door open alarm. 

7

 

CONDENSER FAN 

7.1

 

GENERAL DESCRIPTION 

The condenser fan is can be managed by dedicated control. To enable it, a condenser probe must be 
selected by using par. 

FAC

. Here follows the description of all the related parameters: 

 

FAC

: to select the condenser fan probe 

 

St2

: to select the condenser fan deactivation setpoint 

 

HY2

: differential for condenser fan activation 

 

FCC

 parameter it can be selected the condenser fan working mode: 

o

 

FCC=C-n:

 condenser fan will switch ON and OFF with the compressor and

 

will 

not run during defrost 

o

 

FCC =o-n:

 condenser fan will run even if the compressor is off, and will not run 

during defrost 

o

 

FCC =C-Y: 

condenser fan will switch ON and OFF with the compressor and will 

run during defrost 

o

 

FCC =o-Y: 

condenser fan will run continuously, also during defrost. 

Содержание Dixell XR70CHC

Страница 1: ...NERGY SAVING ALGORITHM The energy saving status will be always saved in the internal memory to resume previous operation if a power failure occurs It needs the presence of a door switch to work for example i1F dor 4 2 1 PARAMETER INVOLVED i1F or i2F set as door input to monitor the appliance usage StE interval to change from normal to energy saving mode EtS interval to change from energy saving to...

Страница 2: ...ions related to par UPC and UP2 if available DOWN In programming mode it browses the parameter codes or decreases the displayed value Other functions related to the par dnC and dn2 if available ONOFF Keep it pressed for 3 sec to switch on and off the device KEYS COMBINATION To lock or unlock the keyboard To enter in programming mode To return to room temperature display ICON MODE MEANING On Compre...

Страница 3: ...t any possible offset of the first probe P2P Evaporator probe presence n not present Y the defrost stops by temperature oE Evaporator probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust any possible offset of the third probe P3P Third probe presence n not present Y the defrost stops by temperature o3 Third probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust any possible offset of...

Страница 4: ...do not use it did Digital inputs 1 alarm delay 0 to 255 it is the delay between the detection of an external event and the activation of the relative function i2P Digital input 2 polarity if d i 2 present oP CL oP activated by closing the contact CL activated by opening the contact i2F Digital input 2 configuration nu dor dEF AUS ES EAL bAL PAL FAn HdF onF LiG CC EMt nu not used dor door switch fu...

Страница 5: ...ed to control the light output CHANGE CONFIGURATION ixF CC It is used to change the controller configuration MOTION SENSOR DETECTOR ixF EMt To use the X MOD motion sensor Please note that motion sensor can be connected only to the HOTKEY port so it needs digital input 2 properly configurated 14 INSTALLATION AND MOUNTING Instrument XR70CHC shall be mounted on vertical panel in a 29x71 mm hole and f...

Страница 6: ...ized repairs changes or modifications could result in permanent damage to the equipment and void your warranty and your authority to operate this device under Part 15 of the FCC Rules NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful int...

Отзывы: