AUXILIARY OUTPUT MANAGEMENT - AUS

 

ACH 

Kind of regulation for auxiliary relay:

 (Ht; CL) 

Ht

 = heating; 

CL

 = cooling. 

SAA 

Set Point for auxiliary relay:

 (-55.0 to 150.0°C; -67 to 302°F) it defines the room temperature 

set point to switch auxiliary relay. 

SHY 

Differential for auxiliary relay:

 (0.1 to 25.5°C; 1 to 45°F) differential for auxiliary output set 

point. 

 

ACH=CL

, AUX Cut in is [

SAA+SHY

]; AUX Cut out is 

SAA

 

ACH=Ht

, AUX Cut in is [

SAA

SHY]

; AUX Cut out is 

SAA

ArP 

Probe selection for auxiliary relay:

 (nP; P1; P2; P3; P4) 

nP

 = no probe, the auxiliary relay is 

switched only by the digital input; 

P1

 = Probe 1 (Thermostat probe); 

P2

 = Probe 2 (evaporator 

probe); 

P3

 = do not use it; 

P4

 = Probe 4. 

Sdd 

Auxiliary  relay  switched  off  during  defrost:

  (n;  Y) 

n

  =  the  auxiliary  relay  operates  during 

defrost. 

Y

 = the auxiliary relay is switched off during defrost. 

btA 

Base Time for timed activation of auxiliary output:

 (SEC; Min) SEC=base time is in second

 

Ato 

AUX output in ON state:

 0 to 255 (base time defined in par. 

btA

AtF 

AUX output in OFF state:

 0 to 255 (base time defined in par. 

btA

ALARMS - ALr

 

ALP 

Temperature alarms probe selection: 

(P1, P2, P3, P4) 

ALC 

Temperature alarms configuration: 

(Ab, rE) 

Ab

 = absolute; 

rE

 = relative. 

ALU

 

Maximum temperature alarm:

 when this temperature is reached, the alarm is enabled after 

the 

Ad

 delay time. 

 

If 

ALC=Ab

 

 ALL to 150.0°C or ALL to 302°F. 

 

If 

ALC=rE

 

 0.0 to 50.0°C or 0 to 90°F. 

ALL

 

Minimum temperature alarm:

 when this temperature is reached, the alarm is enabled after the 

Ad

 delay time. 

 

If 

ALC=Ab

 

 -55.0°C to ALU or -67°F to ALU. 

 

If 

ALC=rE

 

 0.0 to 50.0°C or 0 to 90°F. 

AFH 

Differential for temperature alarm recovery:

 (0.1 to 25.0°C; 1 to 45°F) differential for alarms.

 

ALd

 

Temperature  alarm  delay:

  (0  to  255  min)  delay  time  between  the  detection  of  an  alarm 

condition and the relative alarm signalling. 

Dot

 

Delay  of  temperature  alarm  with  door  open: 

(0.0  to  24h00min,  res.  10  min)  delay  time 

between the detection of a temperature alarm condition and the relative alarm signalling, after 
powering on the instrument. 

dAo

 

Delay of temperature alarm at start up: 

(0.0 to 24h00min, res. 10 min) delay time between 

the detection of a temperature alarm condition and the relative alarm signalling, after powering 
on the instrument. 

CONDENSER TEMPERATURE ALARM - ALr 

AP2 

Probe  selection  for  second  temperature  alarms: 

(nP;  P1;  P2;  P3;  P4) 

nP

=no  probe; 

P1

=thermostat probe; 

P2

=evaporator probe; 

P3

=do not use it; 

P4

=Probe on Hot Key plug 

AU1 

Second high temperature pre-alarm:

 (-55.0 to 150.0°C; -67 to 302°F)

 

AH1 

Differential for second temperature pre-alarm recovery: 

(0.1 to 25.0°C; 1 to 45°F)

 

Ad1 

Second temperature pre-alarm delay: 

(0 to 255 min; 255 = not used) delay time between the 

detection of a condenser pre-alarm condition and the relative alarm signaling.

 

AL2 

Second low temperature alarm:

 (-55.0 to 150.0°C; -67 to 302°F)

 

AU2 

Second high temperature alarm: 

(-55.0 to 150.0°C; -67 to 302°F)

 

AH2 

Differential for second temperature alarm recovery: 

(0.1 to 25.0°C; 1 to 45°F)

 

Ad2 

Second  temperature  alarm  delay: 

(0  to  255  min;  255  =  not  used)  delay  time  between  the 

detection of a condenser alarm condition and the relative alarm signaling.

 

dA2 

Delay for second temperature alarm at start up: 

(0.0 to 24h00min, res. 10 min)

 

bLL 

Compressor  off  because  of  second  low  temperature  alarm: 

(n;  Y)

  n 

=  no,

 

compressor 

keeps on working

; Y 

= yes,

 

compressor is  switched off  till the alarm is present, in any case 

regulation restarts after 

AC

 time at minimum. 

AC2 

Compressor  off  because  of  second  high  temperature  alarm: 

(n;  Y)

  n 

=  no,

 

compressor 

keeps on working

; Y 

= yes,

 

compressor is  switched off  till the alarm is present, in any case 

regulation restarts after 

AC

 time at minimum. 

SAF 

Differential for anti freezing control: 

(-12.0 to 12.0°C; -21.0 to 21.0°F) regulation sopped if 

T<SET+SAF

 

DIGITAL OUTPUT MANAGEMENT - oUt 

tbA 

Alarm muting: 

(n; Y) to disable the (optional) buzzer and the output configured as alarm. 

oAx 

(x=1,2,3,4) 

Output configuration: 

(nu; CP1; dEF; FAn; ALr; LiG; AUS; db; onF; HES; Cnd) 

nu

=not 

used; 

CP1

=compressor; 

dEF

=defrost; 

FAn

=ventilators; 

ALr

=alarm; 

LiG

=light; 

AUS

=Auxiliary  relay; 

onF

=always  on  with  instrument  on; 

db

=neutral  zone; 

HES

=night 

blinds; 

Cnd

=Condenser fan; 

CP2

=second compressor; 

dF2

=second defrost; 

HEt

=heater 

control; 

inV

=do not use it. 

AoP 

Alarm relay polarity: 

(oP; CL) 

oP 

= alarm activated by closing the contact; 

CL 

= alarm 

activated by opening the contact

 

DIGITAL INPUT - inP 

ibt

 

Base time for digital inputs:

 (SEC; Min) 

SEC 

= seconds; 

Min 

= minutes. Delay for activating 

the function linked to the digital inputs. 

i1P

 

Digital  input  1  polarity:

  (oP;  CL) 

oP 

=  activated  by  closing  the  contact; 

CL 

=  activated  by 

opening the contact. 

i1F

 

Digital input 1 configuration:

 (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG; 

CC; EMt)  

 

nu

=not used 

 

dor

 = door switch function 

 

dEF

 = defrost activation  

 

AUS

 = auxiliary output 

 

ES 

= energy saving mode activation 

 

EAL

 = external warning alarm 

 

bAL 

= external lock alarm 

 

PAL 

= external pressure alarm 

 

FAn 

= evaporator fan control 

 

HdF

 = holiday defrost 

 

onF 

= ON/OFF status change 

 

LiG 

= light output control 

 

CC

 = change configuration (between C1 and C2) 

 

EMt

 = do not use it  

did

 

Digital inputs 1 alarm delay:

 (0 to 255) it is the delay between the detection of an  external 

event and the activation of the relative function. 

i2P

 

Digital input 2 polarity (if d.i.2 present):

 (oP; CL) 

oP 

= activated by closing the contact; 

CL 

activated by opening the contact. 

i2F

 

Digital input 2 configuration:

 (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG; 

CC; EMt)  

 

nu

=not used 

 

dor

 = door switch function 

 

dEF

 = defrost activation  

 

AUS

 = auxiliary output 

 

ES 

= energy saving mode activation 

 

EAL

 = external warning alarm 

 

bAL 

= external lock alarm 

 

PAL 

= external pressure alarm 

 

FAn 

= evaporator fan control 

 

HdF

 = holiday defrost 

 

onF 

= ON/OFF status change 

 

LiG 

= light output control 

 

CC

 = change configuration (between C1 and C2) 

 

EMt

 = Motion detector 

d2d 

Digital inputs 2 alarm delay:

 (0 to 255) it is the delay between the detection of an  external 

event and the activation of the relative function. 

nPS 

Number  of  external  pressure  alarms  before  stopping  the  regulation: 

(0  to  15)  after 

reaching 

nPS

 events in the digital input alarm delay (par. 

dxd

) the regulation will be stopped 

and a manual restart (ON/OFF, power OFF and power ON) will be required 

odC

 

Compressor and fan status after door opening:

 (no; FAn; CPr; F-C): 

no

 = normal;  

FAn

 = Fans OFF; 

CPr

 = Compressor OFF; 

F-C

 = Compressor and fans OFF. 

rrd

 

Regulation restart after door open alarm:

 (n; Y) 

n

 = no regulation if door is opened; 

Y

 = when 

did

 is elapsed, regulation restarts even if a door open alarm is present. 

LCi 

Light output controlled by digital input: 

(0 to 255 min) a digital input event will activate the 

light output and the output will stay ON for this interval 

ENERGY SAVING - ES 

HES

 

Differential  for  energy  saving  mode:

  (-30.0  to  30.0°C;  -54  to  54°F)  it  sets  the  increasing 

value of the set point during the Energy Saving cycle. 

LdE 

Energy saving mode controls the lights: 

(n; Y) lights off when energy saving mode is active

 

StE 

Period  to  switch  from  normal  mode  to  energy  saving  mode  (valid  if  ErA=bAS): 

(0.0  to 

24h00min,  res.  10  min)  if  door  stay  closed  for 

StE

  time,  the  energy  saving  mode  will  be 

activated. NOTE: this will require a door switch to work.

 

EtS 

Period  to  switch  from  energy  saving  mode  to  normal  mode  (valid  if  ErA=bAS): 

(0.0  to 

24h00min, res. 10 min) maximum time for energy saving mode. NOTE: this will require a door 
switch to work.

 

dS 

Door open time to switch from EtS to StE (valid if ErA=bAS): 

(0 to 999 sec) the energy 

saving mode will be immediately deactivated as soon as the door stay open more than the 

dS 

time. NOTE: this will require a door switch to work. 

TOTAL COUNTERS - Cnt 

n1H 

Number of relay output 1 activations (thousands of) (read only) 

n1L 

Number of relay output 1 activations (hundreds of) (read only) 

n2H 

Number of relay output 2 activations (thousands of) (read only) 

n2L 

Number of relay output 2 activations (hundreds of) (read only) 

n3H 

Number of relay output 3 activations (hundreds of) (read only) 

n3L 

Number of relay output 3 activations (hundreds of) (read only) 

n4H 

Number of relay output 4 activations (thousands of) (read only) 

n4L 

Number of relay output 4 activations (hundreds of) (read only) 

n5d 

Number of daily activations of digital input 1 (read only) 

n5H 

Number of digital input 1 activations (thousands of) (read only) 

n5L 

Number of digital input 1 activations (hundreds of) (read only) 

n6d 

Number of daily activations of digital input 2 (read only) 

n6H 

Number of digital input 2 activations (thousands of) (read only) 

n6L 

Number of digital input 2 activations (hundreds of) (read only) 

F1H 

Number of working hours for relay output oA1 (thousands of) (read only) 

F1L 

Number of working hours for relay output oA1 (hundreds of) (read only) 

F2H 

Number of working hours for relay output oA2 (thousands of) (read only) 

F2L 

Number of working hours for relay output oA2 (hundreds of) (read only) 

F3H 

Number of working hours for relay output oA3 (thousands of) (read only) 

F3L 

Number of working hours for relay output oA3 (hundreds of) (read only) 

F4H 

Number of working hours for relay output oA4 (thousands of) (read only) 

F4L 

Number of working hours for relay output oA4 (hundreds of) (read only) 

REAL TIME CLOCK MENU - rtC 

Hur

 

Hours: 

0 to 23 hours

 

Min

 

Minutes:

 0 to 59 minutes

 

dAY

 

Day of the week:

 Sun to Sat

 

dYM

 

Day of the month:

 1 to 31 

Mon

 

Month:

 1 to 12 

YAr

 

Year:

 00 to 99 

Hd1

 

First day of the weekend: 

(Sun to Sat; nu) set the first day of the week which follows 

the holiday times.

 

Hd2

 

Second day of the weekend: 

(Sun to Sat; nu) set the second day of the week which 

follows the holiday times.

 

iLE

 

Working day energy saving starting time:

 (0 to 23h50min) during the Energy Saving 

cycle the set point is increased by the  value in HES so that the operation set point is 

SET+HES

.

 

dLE

 

Working day energy saving duration:

 (0 to 24h00min) sets the duration of the Energy 

Saving cycle on workdays.

 

iSE

 

Holyday energy saving starting time:

 0 to 23h50min.

 

dSE

 

Holyday energy saving duration:

 0 to 24h00min.

 

dd1…d

d6

 

Daily defrost enabled:

 (n; Y) to enable the 

Ld1…Ld6

 defrost operations for any day of 

the week. 

Ld1

Ld6

 

Daily defrost starting time:

 (0 to 23h50min) these parameters set the beginning of the 

6 programmable defrost cycles during workdays. Ex: when 

Ld2=12.4

 the second defrost 

starts at 12.40 during workdays.

 

 

N.B.: 

To disable a defrost cycle set it to “nu”

 (not used).  

Ex: if Ld6=nu; the sixth defrost cycle will be disabled. 

Содержание Dixell XR70CHC

Страница 1: ...NERGY SAVING ALGORITHM The energy saving status will be always saved in the internal memory to resume previous operation if a power failure occurs It needs the presence of a door switch to work for example i1F dor 4 2 1 PARAMETER INVOLVED i1F or i2F set as door input to monitor the appliance usage StE interval to change from normal to energy saving mode EtS interval to change from energy saving to...

Страница 2: ...ions related to par UPC and UP2 if available DOWN In programming mode it browses the parameter codes or decreases the displayed value Other functions related to the par dnC and dn2 if available ONOFF Keep it pressed for 3 sec to switch on and off the device KEYS COMBINATION To lock or unlock the keyboard To enter in programming mode To return to room temperature display ICON MODE MEANING On Compre...

Страница 3: ...t any possible offset of the first probe P2P Evaporator probe presence n not present Y the defrost stops by temperature oE Evaporator probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust any possible offset of the third probe P3P Third probe presence n not present Y the defrost stops by temperature o3 Third probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust any possible offset of...

Страница 4: ...do not use it did Digital inputs 1 alarm delay 0 to 255 it is the delay between the detection of an external event and the activation of the relative function i2P Digital input 2 polarity if d i 2 present oP CL oP activated by closing the contact CL activated by opening the contact i2F Digital input 2 configuration nu dor dEF AUS ES EAL bAL PAL FAn HdF onF LiG CC EMt nu not used dor door switch fu...

Страница 5: ...ed to control the light output CHANGE CONFIGURATION ixF CC It is used to change the controller configuration MOTION SENSOR DETECTOR ixF EMt To use the X MOD motion sensor Please note that motion sensor can be connected only to the HOTKEY port so it needs digital input 2 properly configurated 14 INSTALLATION AND MOUNTING Instrument XR70CHC shall be mounted on vertical panel in a 29x71 mm hole and f...

Страница 6: ...ized repairs changes or modifications could result in permanent damage to the equipment and void your warranty and your authority to operate this device under Part 15 of the FCC Rules NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful int...

Отзывы: