Содержание TH500A

Страница 1: ......

Страница 2: ...Sensor type setting 59 6 2 Control output setting 63 6 3 Retransmission output setting 66 6 4 Inner signal and alarm setting 67 6 5 P I D setting 71 6 6 Digital input D I configuration setting 74 6 7...

Страница 3: ...on of the product Information in this manual may changed without prior notification If you have any question or find error in this manual please contact us Copying or reprinting this manual without no...

Страница 4: ...If it is incorrect model type or find any abnormal parts scratches on the outside please contact to our nearest sales office Standard Type Fixing bracket Resistance 250 2 Manual 1 1 1 TH500 I O Board...

Страница 5: ...al Type 2 TH500 24N I O Board 1 I O Board 2 40p cable 20p cable Additional Type Manual Fixing bracket Resistance 250 2 Resistance 250 2 Fixing bracket 40p cable 20p cable Manual Resistance 250 2 Fixin...

Страница 6: ...armful gas ammonia etc combustible or explosive gas does not occur Do not give impact to products It can cause of damage or malfunction When you wire it please cut out all of electric power Please do...

Страница 7: ...using environment is DegreeII 1 3 Quality guarantee Unless it is included company s conditions for warrantee we are not responsible for any warranties or guarantees We are not responsible for any dama...

Страница 8: ...prevent electric shock please check turn off power Before turn on power please connect over the third class grounding During retransmission it may cause electric shock so please do not touch terminal...

Страница 9: ...output 12 points Temp Humidity control output SSR SCR D I 8 points D O 12 points Relay Output SMPS 24V d c 18 W Input Output Board 2 Open Collector 8 points external terminal board Input Output Board...

Страница 10: ...11 186 min 147 min 186 min 147 mi n 2 3 Dimension and panel cutout 2 3 1 Type TH500 1 Standard Unit Unit TH500 2 Additional th300_500_ _th300_500_ qxp 19 6 26 1 33 11...

Страница 11: ...arate body Connector 40 Pin Power Supply for sensor 24 V d c 18 W max D I 8 Points Connector 20 Pin Unit Unit Input Output board 1 Output board 2 External terminal board th300_500_ _th300_500_ qxp 19...

Страница 12: ...13 2 3 3 Standard type TH300 Output board 3 Connector 20 Pin Unit Unit th300_500_ _th300_500_ qxp 19 6 26 1 33 13...

Страница 13: ...14 2 4 Connection Diagram 2 4 1 Model TH500 1 2 4 2 Model TH500 2 th300_500_ _th300_500_ qxp 19 6 26 1 33 14...

Страница 14: ...midity retransmission out Power supply voltage Communication terminal Humidity input sensor Temperature input sensor Connector 40 Pin Power Supply for sensor 24 V d c 18 W max Connector 20 Pin Connect...

Страница 15: ...esistance difference among three wires Please connect Input Output signal wire separately from power line In case of current input please attach resistance 250 0 1 at the end of input terminals and us...

Страница 16: ...17 Transistor output With TH300 D O 1 4 Relay output 1c Contact Only with TH500 Relay output 1a Contact Digital output D O th300_500_ _th300_500_ qxp 19 6 26 1 33 17...

Страница 17: ...2 4 5 Digital Input D I When using open collector please use as follows Voltage of both ends should be below 2 V and leakage current should be below 100 2 5 Communtcation connection 2 5 1 RS232C Conn...

Страница 18: ...stance 2 5 2 RS422 RS485 arrangement maximum 32 machines Please contact Terminating Resistance 100 200 1 4 W to the both of ends for retransmission lines 2 Wire connection Terminating resistance Termi...

Страница 19: ...screen will be displayed after the Logo display FIG 1 screen and check FIG 2 screen are displayed sequentially Users can edit the logo display screen and system check screen 3 1 Initial screen FIG 1...

Страница 20: ...of numbers or the text input box Fig 4 to Fig 7 will appear epending on situations Then you have only to press the set value This box is inactive under current conditions or situations However if you...

Страница 21: ...er part of initial screen Number input screen Fig 4 is going to be displayed Set up by displaying the input screen of number Korean English and symbol with using the 3 2 2 Number Korean English sign I...

Страница 22: ...shown on the Fig 5 All the keys except the keys consist of duplicate keys There is also an additional function key The principle of using function keys is the same in every mode If you want to enter...

Страница 23: ...o indicate Operation Result _ The _ on the bottom indicates a flickering cursor Ex If you want to indicate Operation Result _ The _ on the bottom indicates a flickering cursor Ex If you want to indica...

Страница 24: ...for one second Result 1 2 X 3 9 _ The _ on the bottom indicates a flickering cursor 25 3 2 5 English Input Mode Fig 7 The screen for sign input 3 2 6 Sign Input Mode The screen for English input is sh...

Страница 25: ...V Current temperature PV Control output BAR for current humidity MV Current humidity PV Temperature PID Zone No input box Humidity PID Zone No input box Current date time Temperature PV Up Down indica...

Страница 26: ...n 2 shift button Running Stop indication Control output BAR for current temperature MV Current temperature PV Control output BAR for current humidity MV Current humidity PV Operation pattern name Curr...

Страница 27: ...value TSV Currenthumiditycontroloutputamount MV Temperature humidity up down interval indication Temperature humidity maintain indication Temperature humidity standby Wait indication Total operation...

Страница 28: ...f X axis X axis time Div Low part screen of Y axis Current temperature PV indication Current temperature MV SV indicator shift button Current temperature MV or SV indication Current humidity PV indica...

Страница 29: ...essing the button will select the fix control Set each of setting lists in the operation setting screen 2 by pressing the button While performing the fix control changing the set value SV will automat...

Страница 30: ...en 1 will be displayed Press button and Auto Tuning will be shown on A T button indication in the Sensor Input Setup 4 Temperature Auto Tuning button Turn on and off during running Humidity Auto Tunin...

Страница 31: ...to 70 again for 40 min and maintain the 70 for 1 hour Program control is especially using widely in the test equipment for environment like as thermostat and electric furnace 3 5 Running of Program co...

Страница 32: ...Set Screen Fig 19 Pattern Set Screen Fig 20 Running stopped screen 1 for program control Fig 21 Running screen 1 for program control Press the button in the program set screen Fig 18 and move to the...

Страница 33: ...ce mode the resulted PID value will be saved into the appropriate PID ZONE If this unit is set to manual PID ZONE reference mode the results PID value will be saved into your designated PID ZONE 34 PI...

Страница 34: ...n for program control graph display Fig 25 Graph set screen Graph s display screen is a screen to display the setting value and measured value of temperature and humidity In the graph setting screen X...

Страница 35: ...ation of errors through sensor disconnection and external D I is displayed with button on and off in the running screen 2 for program control Fig 26 If you press the button the error occurrence screen...

Страница 36: ...orking display 4 1 Operating screen 4 Displays Fig 30 Fixed control the 1st working screen Fig 31 Program control the 2nd working screen Fig 32 Fixed control the 2nd working screen Fig 33 Program cont...

Страница 37: ...ntrol the 1st stop screen Fig 36 Function setting menu screen 4 3 System Setting screen As pushing button in Working display condition Function setting menu screen is shown Pushing the character of Fu...

Страница 38: ...m setting menu screen There is no need for System setting made separately by driver Because the Basic setting condition of this system s model is set up by the operator you should be careful especiall...

Страница 39: ...ol the 1st working stop screen is displayed TH500 TH300 Running Screen will be displayed Function setting menu botton Function setting menu botton Information Information Running Operation Setting scr...

Страница 40: ...l and Fixed control in selecting Working method 5 1 Operation setting 5 1 1 Function setup 1 Fig 41 Function setup 1 screen RUN MODE T SV RATE H SV RATE Fix RUN TIME ZN TRACKING PROGRAM FIX RUN Select...

Страница 41: ...d to check various input and operation It is used to limit the touch panel input during system control operating Selecting Lock it is impossible to input except and buttons As it is the function to tu...

Страница 42: ...each pattern in this screen Program control will process according to the content sequence of segment designed 5 2 1 Pattern setting Fig 46 Program pattern setup screen Fig 47 Segment selection screen...

Страница 43: ...g T S button on the Program Pattern Setting screen Fig 49 or Time Signal number on the Program Pattern Setting 2 screen Fig 50 Time Signal Setting screen Fig 51 will be displayed 5 2 2 Time Signal Set...

Страница 44: ...segment is operating Set the Time Signal in ON after setting time is delayed from the beginning of segment Set the Time Signal in ON during setting time from segment in ON Setting Range Each segment...

Страница 45: ...4 ON under 25 soak status SEG 6 ON under 75 soak status SEG 1 and SEG 5 ON under Up section SEG 3 ON under Down section SEG 1 to SEG 3 ON SEG 4 to SEG 6 ON SEG 1 to SEG 6 ON under program control runn...

Страница 46: ...sing 4 hours it will become OFF ON Delay 00 h 00 m ON Time 04 h 00 m Time signal becomes ON in each of segment 2 4 and 6 and after elapsing ON time it will become OFF Time Signal will be OFF once the...

Страница 47: ...l repetition number Set the partial repeating end segment number Setting 0 will run the next partial repetition number Set the number of current partial repetition Setting 0 will run the next partial...

Страница 48: ...een Waiting operation can be set by each segment of proper pattern In case that Waiting operation of process value PV comes or fails to come within Waiting range of Set value SV wait process of segmen...

Страница 49: ...peration range in order to cancel the standby operation Range 1 100 Pattern 0 300 TH500 0 600 TH300 0 100 0 99 hour 59 minute Waiting time Waiting Range Standby operation becomes cancelled because PV...

Страница 50: ...59 Pattern alarm setup screen 5 2 5 Pattern Alarm Setting Start the standby operation because PV did not fall within the set standby range Cancel the standby operation even though PV did not fall wit...

Страница 51: ...tting FIG 60 screen then set alarm code will be cancelled Code 1 2 3 4 5 6 7 8 9 10 Code 11 12 13 14 15 16 17 18 19 20 Alarm Type Upper limit absolute Tangent Hold Lower limit absolute Tangent Hold Up...

Страница 52: ...sing button again In this display it will be shown to Fig 61 S PV Working start setting display 5 2 6 Pattern start mode setting Fig 62 S SV Operation start setting display Fig 61 S PV Operaiton start...

Страница 53: ...nt copy and segment initializing In the left side you should enter the source pattern or segment number used for pattern management In the right side you should enter the target pattern number of segm...

Страница 54: ...setting screen Fig 69 Fixed control the 1st working stop screen 5 3 Date Time Reservation Setting Keep in mind that it is impossible to recover the original contents of the target after copying the p...

Страница 55: ...creen Fig 71 Graph view screen Table 3 Time per X axis DIV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 00M 20S 01M 00S 02M 00S 03M 00S 04M 00S 05M 00S 06M 00S 07M 00S 08M 00S 09M 00S 10M 00S 20M 00S 00H 30M 00H...

Страница 56: ...ng controlling only Fix Program Save during fixed mode controlling only save during program mode controlling only Delete Initialize Saved Contents in internal memory Do not use USB MEMORY STICK Record...

Страница 57: ...ng Graph Viewer program presented 58 Fig 72 USB Uploader Utility If you turn off all contents will be deleted because the value of saved measurement control is saved in Volatile Memory SDRAM When you...

Страница 58: ...he Temperature sensor setting screen Fig 76 The contents of Humidity sensor setting screen Fig 77 is the same as temperature sensor setting But if you select sensor type as Temperature only display Fi...

Страница 59: ...ect the sensor type as d c voltage for humidity sensor related setting because output for humidity sensor is 4 20 mA But in case of current output sensor please connect the resistance less than 250 1...

Страница 60: ...and measured temperature 70 10 compensation of measured temperature is necessary This time please touch 80 and enter 70 in the number plate After touching compensation is finished Fig 79 Temperature B...

Страница 61: ...ge control output will be OFF Displays Dry bulb temperature Displays Wet bulb temperature Gauze have to be removed Displays relative humidity RH Press and it shows the temperature difference between d...

Страница 62: ...ton 6 2 1 Control output setting 1 Temperature output type Output period of SSR Output direction Reverse Forward Output range could be set up on the Control Output Setting 1 Fig 83 T SV range H SV ran...

Страница 63: ...Output period of SSR Output direction Reverse Forward Output range could be set up on the Conntrol Output Setting 2 Fig 84 TH500 TH300 Fig 83 Control output setting 1 TH500 TH300 Fig 84 Control outpu...

Страница 64: ...Select and use S S R or S C R 4 20 d c Select according to the equipment Initial value S S R You can set up when you select S S R output Output cycle means On Off working time in the proportional band...

Страница 65: ...wn up If output value is different compared to the standard output 50 0 please touch button after setting standard output as 50 0 In this case output signal which is corresponded to 50 0 will be gener...

Страница 66: ...ard output through retransmission output Initialize bias values Contents Button 6 4 1 Inner Signal setup Time Signal is related with segment and Time but Inner Signal is used for signal output of temp...

Страница 67: ...Time Fig 92 Example of Inner Signal setting NSV temp Time Fig 93 Example of Inner Signal setting TSV Setting item I S Number I S SOURCE I S TYPE I S RANGE I S DIRECT I S DELAY Function Directly input...

Страница 68: ...ON OFF signal setting screen Fig 96 will be shown up This screen is a zone setting screen based on temperature and humidity setting values Each output depend on setting condition could be set up and t...

Страница 69: ...elected code please push on the left side 5 And then set alarm value and Hysteresis 70 Same as Fig 97 range is divided by four zones A B C D by means of L SV M SV H SV Its setting condition is L SV M...

Страница 70: ...ith the total 16 PID ZONEs As shown in the chart below the four temperature zones and four humidity zones are combined with each other so you can control the temperature and humidity with the optimize...

Страница 71: ...n P I D setting screen Fig 103 by pushing Zone button wanted in the Fig 102 However it is not possible to set HYS Hysteresis setting screen cause it is not activated as a grey color In order to set it...

Страница 72: ...ortional band is narrow the time to reach to setting value is fast because of high quanity of control ouput But if it is too narrow hunting is appeared Set up integral time Offset is appeared with usi...

Страница 73: ...at the same time it ignores STEP input and it handles HOLD input only Regardless of control action Running or Stop external D I is always displayed and handled internally according to its input status...

Страница 74: ...ated When selecting Waiting Delay time system will be finished after passing waiting delay time 75 TH500 TH300 Fig 111 D I Setting 3 Fig 110 D I Setting 2 6 6 2 D I Setting 2 It is possible for user t...

Страница 75: ...als assigned and connected are displayed through the actual terminal The D O assignment is allowed to be redundant except special cases so it is necessary to assign and enter the RELAY and O C careful...

Страница 76: ...nt by means of temperature and humidity setting values Each output according to setting condition could be set and used in the D O Configuration Setting 3 screen It will be ON after passing setting ti...

Страница 77: ...open collector output FIG 117 D O Configuration Setting 6 Explanation In case of D I input its output becomes ON for a setting time IF RUN STOP STEP and HOLD function input is set its D I will be not...

Страница 78: ...setting 20 Relay or O C Output Relay or O C Output Relay or O C Output Fig 119 Output by temperature UP HOLD DOWN setting D O Configuration setting 7 FIG 118 is used when turning ON the output within...

Страница 79: ...onnection by connecting 4 lines you can use 2 lines by connecting RX with TX doing RX with TX Function Select the communication protocol PCLINK operates by following the format which is assigned by Ha...

Страница 80: ...of Korean on one line Name Language Password User information 6 9 1 ETC Setup 1 Function When selecting T PV HOLD It holds a minute temperature hunting When selecting H PV HOLD It holds a minute humid...

Страница 81: ...e 0 100 set up scaling setting as 0 100 When touching in the Fig 124 Fig 125 Fig 79 Fig 80 will be displayed Low Pass Filter selects suitable time when processed value is chattering due to inflowing o...

Страница 82: ...efore correction Setting item Humi C RNG Dry Temp Wet Temp Rel Humidity D W Adjust Adjust Mode ADJ INIT 7 1 3 Range Setting In order to prevent mistake of user input setting Input temp range when rest...

Страница 83: ...on or heating control Reverse operation Initial value Reverse operation Output could be controlled and its range is 5 00 3 2 105 00 20 8 Initial value 0 00 100 00 S S R or S C R 4 20 could be used as...

Страница 84: ...d c Setting item T Source T Range Out Adjust S Burnout output FIG 131 Inner Signal Set FIG 132 D O Output setup1 When controlling refrigerator and dehumidifier separately by external switch it can be...

Страница 85: ...ature Range 100 30 Subject humidity Range 0 70 Subject Temperature Range 100 50 1 minute 10 seconds 5 seconds Connect 1st refrigerator to 5th Relay Connect dehumidifier to 6th Relay Connect 2nd refrig...

Страница 86: ...rification screen 87 7 4 3 Operate and STOP of Fix Control FIG 135 Fix control 1st operation stop FIG 136 Fix control 1st operation Press temp humidity setting and set up desired setting value After s...

Страница 87: ...t will be better to perform Auto Tuning in order to get good control performance To start Auto Tuning press Auto Tuning button at the bottom of picture Fig 136 When T AT button flickering it shows tha...

Страница 88: ...xplanation of Program Pattern Setting Screen FIG 139 Program pattern setting Explanation Input pattern no directly or select it by using button Press Segment Page Shifting button and it moves to 4 seg...

Страница 89: ...rt segment setting unit within pattern of program control operation stop FIG 141 screen and press the button then program control operation will be started In order to stop the program control operati...

Страница 90: ...A 250 V a c 5 A N C 30 V d c 1 A 250 V a c 2 A 8 points 2 COM 4 points 1 COM 24 V d c 300 max Open Collector 8 points 1a 8 points 2 COM S C R is not available TH500A TH500A Model Model TH300 TH300 8...

Страница 91: ...n 10 m approx within 1 2 km approx 1 M bps 9600 19200 38400 57600 115200 bps 7 8 bits NONE EVEN ODD 1 2 bit s Bulk Mode PCLINK PCLINK CRC MODBUS RTU 0 999 ms Power supply voltage Frequency Power consu...

Страница 92: ...rn 100 segments 6 000 max segments 2 000 max segments 16 Groups Temp 4 zones x Humidity 4 zones Auto Tuning according to SV Setting Value Temp 0 00 600 00 Humidity 0 00 200 00 0 00 ON OFF control 0 0...

Страница 93: ...English Chinese Traditional 8 6 Touch LCD Model TH500A TH300 Usable surrounding temperature Usable surrounding humidity Storage Temperature Vibration Shock Dimension Weight 0 50 20 90 R H No condensa...

Страница 94: ...9 1 Specification 24 V d c 500 Asynchronous Serial Communication RS232C max 38400 bps max 5 m Operate the front switch Memory stick USB MERORY STICK FAT16 32 32 Mb Nonvolatile USB POWER ACT DUMP CLEAR...

Страница 95: ...96 9 3 Dimension and Panel Cutout 9 4 Connection Diagram POWER 24 V d c RX TX EM310 TH500 S G RX TX S G 1 5 6 2 3 th300_500_ _th300_500_ qxp 19 6 26 1 36 96...

Страница 96: ...MA0801E230327 HEAD OFFICE 28 Gilpa ro 71beon gil Nam gu Incheon Korea TEL 82 32 876 4697 FAX 82 32 876 4696 http www hynux com E mail overseas hynux com th300_500_ _th300_500_ qxp 19 6 26 1 32 1...