65
[FIG.85] S.S.R pulse output
In case min value is -5 %, it becomes 3.2 ㎃ d.c output and it becomes 20.8 ㎃ d.c output in
case max value is 105 %. The value of control output within its range will be converted into
rectilinear figure and output will be done.
Based on SSR pulse output, control output will be ON in a specific time and remaining time
will be OFF.
T.Out type
T.SSR out period
T.Out direct
T.Out range
Select and use S.S.R or S.C.R (4 - 20 ㎃ d.c). Select according to the
equipment (Initial value : S.S.R)
You can set up when you select S.S.R output. Output cycle means On/Off
working time in the proportional band.
(Initial Value : 1 seconds)
Select cooling control (direct movement) or heating control
(inverse movement) (Initial Value : Inverse movement)
You can control output and selection range : -5 %(3.2 ㎃ d.c) · · ·
105 %(20.8 ㎃ d.c) (Initial Value : 100 %)
● Control Output Setting 1 is the same as Control Output Setting 2
min value of
output range=-5 %
max range of
output range=105 %
[FIG.86] S.C.R output