5.0 Installation Requirements
This insert can be installed in most solid fuel burning
fireplaces of either masonry construction or a
prefabricated factory built fireplace.
Prior to any installation, the existing chimney
flue must be thoroughly cleaned and given a NFPA
211, Level II inspection by a qualified chimney sweep
or fireplace service person.
Do not install this appliance into a chimney that
is damaged or contains combustible construction
materials. Any repairs must be made prior to
installing the insert. The chimney and fireplace
must be in good working order. Chimney clean-
outs must be accessible and fit properly. If you
are unsure of the condition of your fireplace and
chimney, contact a professional fireplace technician
or your local authorized Jøtul dealer for professional
assistance.
Figure 5.1. Firebox dimensions.
Leveling Note:
This appliance is equipped with
four leveling bolts; the front
two are adjusted from inside
the firebox, and the rear bolts
are adjusted by tipping the
firebox and unscrewing them
from the base.
Also note that use of the
leveling bolts will affect
required minimum clearance
to combustible top trim and
mantle construction. See the
figures and tables on pages 8
and 9.
DO NOT REMOVE BRICKS OR MORTAR FROM
THE FIREPLACE OR CHIMNEY STRUCTURE. However,
masonry or steel may be removed from the
smoke shelf and adjacent damper frame area
to accommodate installation of a chimney liner,
provided that their removal will not weaken the
structure of the fireplace or chimney, and will not
reduce protection for combustible materials.
If the existing fireplace has been modified to
accommodate installation, use anchors or masonry
nails to attach the metal Fireplace Conversion
Notice Plate to the back wall of the masonry
fireplace firebox where it will be readily seen should
the insert be removed.
THIS APPLIANCE MUST NOT BE CONNECTED TO A
CHIMNEY OR FLUE SERVING ANY OTHER APPLIANCE
OF ANY KIND. All venting components must be
installed in accordance with the terms of their
listing and manufacturer’s instructions. Refer to
the pipe manufacturer’s instructions for proper pipe
clearances.