29
JO
NIX
up in
SPEED
JUMPER ON INPUT
VOLT SIGNAL FAN
AIR FLOW RATE
Speed 1
I7
3V (*)
35 m
3
/h
Speed 2
I8
5V (*)
60 m
3
/h
Speed 3
I9
7V (*)
90 m
3
/h
8.2.4 Fan
8.2.3 External alarm input I5
8.2.2 Alarm reset button
8.2.1 on-off SWITCH (power supply selector switch)
(*) The fan voltages at the three speeds are parameters that can be changed using the optional
display (see chapter 9 "DISPLAY EVO optional").
The fan is modulating type with 0-10V signal and the electronic card allows it to operate at
constant speed with unit ON (on) according to the SPEED activated by a jumper on inputs I7-I8-I9
with the following defaults:
It is possible to turn the JO
N
IX
up in
device to OFF by connecting it to an external alarm:
I5 closed = no alarm.
I5 open = alarm.
If this alarm occurs, the device turns off and the red LED with slow flashing is activated (see
paragraph 8.3 "ALARM SIGNALLING").
With button pressed = alarm reset ((I6 open - I10 closed).
WARNING: the reset is performed if the button is pressed for 5 seconds (the contact is closed
for 5 seconds).
0 = device OFF (I6 open - I10 open).
I = device ON (I6 closed - I10 open).
8.2 MANAGED COMPONENTS, OPERATING LOGIC AND FACTORY SETTINGS
NOTES:
• if all the inputs are open, Speed 2 is activated;
• if several inputs are closed, Speed 2 is activated;
• if IONIZER FUNCTION 4 is active, ventilation function
only during the ionization cycle.