18
The external air intakes must be made so that they cannot get accidentally covered and if they have an insect
protection mesh they must be cleaned periodically to prevent clogging with dust and dirt, especially in periods with intense
pollen concentrations.
NOTE
As indicated in the national reference standard UNI
10683, the product can not be installed in rooms
with a volume of under 15 m
3
.
NOTE
Bear in mind that the minimum distances from
inflammable materials are:
Minimum air distance from inflammable side wall: 200 mm
Minimum air distance from inflammable rear wall:
100 mm
Frontal air distance from inflammable material: 1000 mm
NOTE
CHAP.07 POSITIONING AND CONNECTIONS FOR THE INSTALLER
07.1
SETTING UP OF EXTERNAL AIR INTAKES AND ELECTRIC CURRENT
The device must only be installed indoors and on surfaces
that can support the load. If the existing construction does not
meet this requirement, it will be necessary to take appropriate
measures (e.g. installing a load distribution plate). The appliance
must be installed in an area where the appliance itself, gas
exhaust pipes and flue can be easily accessed for maintenance.
Fig. 1
and
2
illustrate minimum distances that must be observed,
all measurements are in mm.
The lateral distance from the adjacent wall, according to
installation, is to be maintained on both sides.
F
ig
.1
F
ig
.2
min. 200
min.
100
min.
100
min. 200
max. 1250
min.
100
max. 1250
min.
100