7. Electrical Wiring
● The indoor unit fan may continue to operate for up to five minutes following the heating cycle to
dissipate residual heat from the indoor unit.
● Check to ensure that the indoor fan and the outdoor fan have stopped before electrical wiring work
or a periodical check is performed.
● Insulate electrical wiring, drain piping, and electrical components from threats posed by burrowing
animals and temperature extremes. Failure to do so, can over time, deteriorate system performance.
● Electrical cables should not come into contact with refrigerant piping, plate edges, and electrical
components inside the unit.
● GFCI may be recommended depending on the application; if not, electric shock or a fire can result.
● Secure the cables. External forces on the terminals can lead to fire.
● Tighten screws according to the following torque.
M3.5: 0.5 to 0.7 ft·lbs (0.7 to 0.9 N·m)
M5: 1.5 to 1.8 ft·lbs (2.0 to 2.5 N·m)
M6: 3.0 to 3.7 ft·lbs (4.0 to 5.0 N·m)
M8: 6.6 to 8.1 ft·lbs (9.0 to 11.0 N·m)
M10: 13.3 to 17.0 ft·lbs (18.0 to 23.0 N·m)
● Set DSW7 on the PCB1 according to each power supply shown in the figure below.
● Use the specified cables for wiring between the outdoor unit and indoor units. Selecting incorrect
cables will cause an electric shock or a fire. Communication cable shall be a minimum of
AWG18
(0.82mm
2
), 2-Conductor, Stranded Copper. Shielded cable must be considered for applications and
routing in areas of high EMI and other sources of potentially excessive electrical noise to reduce
the potential for communication errors. When shielded cable is applied, secure properly and
terminate cable shield as required per Johnson Controls guidelines. Plenum and riser ratings for
communication cables must be considered per application and local code requirements.
● Tightly secure the electrical wirings to the terminal block according to the specified torque.
If tightening the terminals is not completed, heat generation, an electric shock or a fire will occur at
the terminal connections.
Power Supply Setting
208V, 230V Unit: 230V Setting Before Shipment
460V Unit: 460V Setting Before Shipment
208V Unit:
230V, 460V Unit:
208V
230V
460V
DSW7
2
1
ON
3 4
2
1
ON
3 4
2
1
ON
3 4
No setting is required.
Setting is required.