66
P5417009-rev.6
Model
Tightening Torque [ft·lbs (N·m)]
Hexagonal
Wrench Size
inch (mm)
Stop Valve
Flare Nut
Cap
Access Port
High/Low
Pressure
Gas Valve
Low
Pressure
Gas Valve
Liquid
Valve
Liquid
Valve
Gas
Valve
Liquid
Valve
Gas
Valve
Liquid
Valve
Gas
Valve
Liquid
Valve
72
13.3 - 16.2
(18.0 - 22.0)
13.3 - 16.2
(18.0 - 22.0)
5.2 - 6.6
(7.0 - 9.0)
24.3 - 31.0
(33.0 - 42.0)
36.1 - 42.8
(49.0 - 58.0)
24.3 - 31.0
(33.0 - 42.0) 6.6 - 10.3
(9.0 - 14.0)
10.3 - 13.3
(14.0 - 18.0)
3/8
(10)
3/16
(4)
96 - 144
18.4 - 22.9
(25.0 - 31.0)
36.9 - 45.7
(50.0 - 62.0)
168, 192
6.6 - 8.1
(9.0 - 11.0)
50.2 - 62.0
(68.0 - 84.0)
36.9 - 45.7
(50.0 - 62.0)
3/16
(5)
8. Additional Refrigerant Charge
8.1 Airtight Test
(1) Check to ensure that the stop valves for high/low pressure gas, low pressure gas and liquid pipes are
closed completely before airtight test.
(2) The refrigerant used for this outdoor unit is R410A. Use the manifold gauge and the charging hose for
exclusive use of R410A.
Tightening Check of Stop Valves
After connecting the pipe, remove the caps of stop valves for high/low pressure gas, low pressure gas
and liquid. Tighten the open-close stop valve in the closing direction according to the following tightening
torque.
Operation of Stop Valves Caution
(a) Remove the stop valve caps before performing the airtight test after connecting the refrigerant
piping. Tighten the stop valve in clockwise direction.
(b) Perform the work after warming the stop valve with a hair dryer etc. when controlling the stop valve
in a cold area. (The stop valve O-ring will harden at low temperature, causing the O-ring material to
contract by volume, and refrigerant leakage can occur.)
(c) Do not apply excessive force after fully opening the stop valve (Tightening Torque: < 3.7 ft·lbs
(5.0 N·m)). (A back seat (hard stop), is not provided, allowing complete removal of the valve stem.)
(d) Tighten caps securely according to the following torque specifications after each stop valve is
opened.
Stop Valves for Gas Pipe
(High/Low Pressure)
Stop Valve for Gas Pipe
(Low Pressure)
Stop Valve for
Liquid Pipe
Position both
wrenches here.
Flare Nut
Hexagonal
Wrench
Stop Valve
Refrigerant
Pressure
Counterclockwise...Open
Clockwise...............Close
Only the charging
hose for R410A
can be connected.
Closed before Shipment
Access Port
Cap
O-ring
(Rubber)
To open or
close the
stop valve
Do NOT put two
wrenches here.
Содержание YVAHR072B32S