18
P5417009-rev.6
NOTICE:
Keep the upper side open to prevent mutual interference between the inlet and outlet air of each outdoor
unit.
The figure indicates sufficient clearance around the outdoor units for operation and maintenance at typical
installation conditions as follows.
[Operation Mode: Cooling Operation, Outside Temp.: 95
o
F (35
o
C)]
In the following situations when compared to the installation condition, an appropriate clearance
dimension is required by calculating air flow current when
* the outdoor unit ambient temperature is higher
* a short circuit is likely to occur
For the multiple installation of units, one group will consist of a maximum of six outdoor units.
Maintain a distance of 3.3 ft (1m) between each unit group.
3) Walls on
Four
Sides
Single Installation
Installation in the Same Direction
Rear to Rear Installation
Multiple / Serial Installation
One Group (Max. Six Outdoor Units)
Min. 3.3 ft
▼
▼
▼
▼
▼
▼
Top View
Front Side
No limit for
side wall height.
No limit for
side wall height.
Min.
19-11/16 (500) + h2/2
Min. 7-7/8
(200)
Min. 7-7/8
(200)
Front Side
Min. 35-7/16 (900)
Min.
11-13/16 (300) + h1/2
Open
Min. 31-1/2
(800)
Open
Min. 31-1/2
(800)
Min. 7-7/8
(200)
Min. 7-7/8
(200)
▼
Open
Top View
Front Side
No limit for
side wall height.
No limit for
side wall height.
Min.
11-13/16 (300) + h1/2
Min.
19-11/16 (500) + h2/2
Min. 7-7/8
(200)
Min. 7-7/8
(200)
Min. 31-1/2
(800)
Unit: inch (mm)
▼
▼
▼
▼
▼
▼
Top View
Front Side
No limit for
side wall height.
No limit for
side wall height.
Front Side
Min. 63 (1600)
(Side Space)
Min.
19-11/16 (500) + h2/2
Open
Min. 31-1/2
(800)
Open
Min. 31-1/2
(800)
Min. 7-7/8
(200)
Min. 7-7/8
(200)
Unit: inch (mm)
Min.
19-11/16 (500) + h2/2
Min. 7-7/8
(200)
Min. 7-7/8
(200)
: Partly open a wall if the unit is surrounded by walls on four sides.