P5417009-rev.6
63
●
Setting for Transmitting
Use the following settings for the outdoor unit numbers, refrigerant system numbers and end terminal
resistance for this H-LINK system.
●
Setting of Outdoor Unit Number (No.)
If there are combined outdoor units, set DSW6 as shown below.
NOTE:
Be sure to set DIP switch DSW6-No.4 for using the low ambient kit.
Refer to the “Installation Manual” for LAK or “Service Manual” for the outdoor unit.
DSW and RSW setting before shipment is 0.
Maximum in setting refrigerant system number is 63.
Setting Switch
10 digit
1 2 3 4 5 6
ON
OFF
1 digit
0
7
9
5
8
6
4 3
1 2
Setting Position
Set by inserting
slotted screwdriver
into the groove.
Outdoor Unit
DSW1
RSW1
Indoor Unit
(H-LINK II)
DSW5
RSW2
Example: If Setting Refrigerant System No. 25
●
Setting of Refrigerant System Number
In the same refrigerant system, set the same refrigerant system number for the outdoor unit and the indoor
units as shown below.
Setting outdoor unit refrigerant system number is required only for the main unit.
The sub unit settings are not required.
As for setting indoor unit refrigerant system number, set RSW2 and DSW5 on the indoor unit PCB.
Base Unit
(Before Shipment)
Combination of Base Unit
Unit A
(No.0)
Unit B
(No.1)
Unit C
(No.2)
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
Maximum Number of Connectable
Outdoor Units and Indoor Units
(for H-LINK II)
Outdoor Unit
64
Indoor Unit
160
For installing the outdoor unit
and the indoor unit on the same
communication cable, which cannot be
used for H-LINK II, maximum number
of connectable indoor units is 128.
0
7
9
5
8
6
4 3
1 2
3
2
1
4
ON
5 6
OFF
Turn ON No. 2 pin.
Set Dial No.5.
0
7
9
5
8
6
4 3
1 2
3
2
1
4
ON
5 6
OFF
3
2
1
4
ON
OFF
DSW1:
DSW6:
RSW1:
0
7
9
5
8
6
4 3
1 2
3
2
1
4
ON
5 6
OFF
3
2
1
4
ON
OFF
DSW1:
DSW6:
RSW1:
0
7
9
5
8
6
4 3
1 2
3
2
1
4
ON
5 6
OFF
3
2
1
4
ON
OFF
DSW1:
DSW6:
RSW1:
Main Unit
Sub Unit
Sub Unit
Ref. System No. 25
Setting is not required.
Setting is not required.
Setting of Main Unit (Unit A)
Setting of
Sub Unit (Unit B)
Setting of
Sub Unit (Unit C)
H-LINK II
(Factory-Setting)
to the Indoor Units
Setting Example
Communication Line
(No Polarity)
H-LINK II
Centralized Controller
Outdoor Unit
Indoor
Unit
Wired Controller
Set the refrigerant system No.
not to duplicate no. with the other outdoor units.
Refrigerant System for
This Outdoor Unit
Set to the same refrigerant
system No.