Care and  

Maintenance

The  Series RFII-MRI Concealed 

Pendent Sprinklers must be maintained 

and serviced in accordance with this 

section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this action.
Absence of the Cover Plate/Retainer 

Assembly can delay sprinkler opera-

tion in a fire situation.
When properly installed, there is a 

nominal 3/32 in. (2,4 mm) air gap 

between the lip of the Cover Plate and 

the ceiling, as shown in Figure 2.
This air gap is necessary for proper 

operation of the sprinkler. If the ceiling 

requires repainting after sprinkler 

installation, ensure that the new paint 

does not seal off any of the air gap.
Do not pull the Cover Plate relative to  

the Enclosure. Separation may result.
Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Exercise care to avoid damage to sprin-

klers before, during, and after instal-

lation. Replace sprinklers damaged 

by dropping, striking, wrench twist-

ing, wrench slipping, or the like. Also, 

replace any sprinkler that has a cracked 

bulb or that has lost liquid from its bulb. 

(See the Installation section.)
If you must remove a sprinkler, do not 

reinstall it or a replacement without 

reinstalling the Cover Plate/Retainer 

Assembly. If a Cover Plate/Retainer 

Assembly becomes dislodged during 

service, replace it immediately.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION (NFPA) - for example, 

NFPA 25 - in addition to the standards 

of any other authorities having jurisdic-

tion. Contact the installing contractor 

or sprinkler manufacturer regarding any 

questions.
Automatic sprinkler systems should be 

inspected, tested, and maintained by a 

qualified Inspection Service in accor-

dance with local requirements and/or 

national code.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering  

Procedure

Contact your local distributor for 

availability. When placing an order, 

indicate the full product name.

Sprinkler/Support Cup Assembly

Specify: Series RFII-MRI (specify SIN),  

K=5.6, Pendent Sprinkler, (specify) 

temperature rating, P/N (specify):

 

155°F (68°C)

  

200°F (93°C)

TY3530  . . . . . . . . 51-800-1-155 51-800-1-200
TY3550  . . . . . . . . 51-801-1-155 51-801-1-200

Separately Ordered 

Cover Plate/Retainer Assembly:

Specify: (temperature rating from 

below) Non-Magnetic Series RFII-MRI 

Concealed Cover Plate with (specify)

finish, P/N (specify):

 

139°F (59°C)

165°F (74°C)

b

Grey White 

 (RAL9002)  . . . . 56-794-0-135 56-794-0-165
Brass . . . . . . . . . . 56-794-1-135 56-794-1-165
Signal White 

 (RAL9003)  . . . . 56-794-4-135 56-794-4-165
Jet Black 

 (RAL9005)  . . . . 56-794-6-135 59-794-6-165
Custom  . . . . . . . . 56-794-X-135 56-794-X-165

a.  For use with 155°F (68°C) sprinklers.
b.  For use with 200°F (93°C) sprinklers.

Sprinkler Wrench

Specify: RFII Sprinkler Wrench,  

P/N 56-000-1-075

Air and Dust Seal

Specify: Air and Dust Seal,  

P/N 56-908-1-001

SUPPORT

CUP

SPRINKLER

AIR

AND DUST

SEAL

COVER

PLATE

LIP OF

RETAINER

FACE OF

CEILING

ORIENT

SEAL

BEVEL AS

SHOWN

COVER

PLATE

RETAINER

ASSEMBLY

CLEARANCE

HOLE

FIGURE 5 

OPTIONAL AIR AND DUST SEAL 

FOR SERIES RFII-MRI (TY3550)

FIGURE 4 

DISPOSABLE PROTECTIVE CAP

Отзывы: