background image

TFP182

Page 2 of 4

Technical  

Data

Sprinkler Approvals

TY3530 (3 mm bulb)

•  UL Listed, C-UL listed as quick 

response

•  FM approved as standard response

TY3550 (5 mm bulb)

•  UL listed, C-UL listed, and FM approved 

as standard response

Note:

 FM does not approve concealed 

sprinklers for quick response.

Note:

 Approvals apply only to the service 

conditions indicated in the Design Criteria 

section.

Air and Dust Seal Approvals

UL and C-UL Listed 

Standard Response (TY3550) application 

only

Maximum Working Pressure

Maximum 175 psi (12,1 bar)

Temperature Rating

155°F (68°C) Sprinkler with 

139°F (59°C) Plate
200°F (93°C) Sprinkler with 

165°F (74°C) Plate

Discharge Coefficient 

K= 5.6 GPM/psi

½

 (80,6 LPM/bar

½

)

Adjustment 

1/2 in. (12,7 mm)

Finishes

See the Ordering Procedure section.

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Support Cup . . . . . . . . . . . . . . . . . . . . . . . .Brass

Guide Pins . . . . . . . . . . . . . . . . . .  Stainless Steel

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Compression Screw . . . . . . . . . . . . . . . . . .Brass 

Bulb

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass

Cap  . . . . . . . . . . . . . . . . . . . . . Bronze or Copper

Sealing Assembly  . .Beryllium Nickel w/TEFLON

Cover Plate . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Retainer . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Ejection Spring . . . . . . . . . . . . . .  Stainless Steel

Design  

Criteria

The Series RFII-MRI Concealed 

Pendent Sprinklers are intended for 

fire protection systems designed in 

accordance with the standard installa-

tion rules recognized by the applicable 

Listing or Approval agency; for example, 

UL Listing is based on NFPA 13.
The RFII-MRI Sprinklers are only listed 

with the Series RFII-MRI Concealed 

Cover Plates having a factory applied 

finish.

NOTICE

Do not use the 

RFII-MRI Sprinklers

 in 

applications where the air pressure 

above the ceiling is greater than that 

below. Down drafts through the Sprin-

kler/Support Cup Assembly can delay 

sprinkler operation in a fire situation.

Operation

When exposed to heat from a fire, the 

Cover Plate, normally soldered to the 

Retainer at three points, falls away to 

expose the Sprinkler/Support Cup 

Assembly.
The Deflector — supported by the 

Guide Pins — then drops down to its 

operational position.
The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, activating the sprinkler and 

allowing water to flow.

Installation

The Series RFII-MRI Concealed 

Pendent Sprinklers must be installed 

in accordance with this section.

General Instructions

Do not install any bulb-type sprin-

kler if the bulb is cracked or there is 

a loss of liquid from the bulb. With the 

sprinkler held horizontally, a small air 

bubble should be present. The diam-

eter of the air bubble is approximately 

1/16 in. (1,6 mm) for the 155°F (68°C) 

and 3/32 in. (2,4 mm) for the 200°F 

(93°C) temperature ratings.
A leak-tight 1/2 in. NPT sprinkler joint 

should be obtained by applying a 

minimum to maximum torque of 7 to 

14 lb-ft (9,5 to 19,0 N·m). Higher levels 

of torque can distort the sprinkler Inlet 

with consequent leakage or impairment 

of the sprinkler.
Do not attempt to compensate for 

insufficient adjustment in the Sprinkler 

SPRINKLER/SUPPORT CUP

ASSEMBLY

COVER PLATE/RETAINER

ASSEMBLY

GUIDE

PINS (2)

DEFLECTOR

(DROPPED

POSITION)

COMPRESSION

SCREW

DEFLECTOR

SUPPORT

CUP WITH

ROLL FORMED

THREADS

FRAME

1/2" NPT

CAP

BULB

SEALING

ASSEMBLY

RETAINER

WITH THREAD

DIMPLES

EJECTION

SPRING

SOLDER

TABS (3)

COVER

PLATE

THREAD INTO

SUPPORT

CUP UNTIL

MOUNTING

SURFACE IS

FLUSH WITH

CEILING

FIGURE 1 

SERIES RFII-MRI CONCEALED SPRINKLER  

ASSEMBLY