TFP182

Page 3 of 4

A: 3-1/4 inches (82,6 mm)

C: 2-3/8 to 2-5/8 inches (60,3 to 66,7 mm)

B: 3/16 inches (4,8 mm)

D: 1-3/4 to 2-1/4 inches (44,5 to 57,2 mm)

by under- or over-tightening the Sprin-

kler/Support Cup Assembly. Re-adjust 

the position of the sprinkler fitting to 

suit.

Step 1.

 Install the sprinkler only in the 

pendent position with the center-line 

of the sprinkler perpendicular to the 

mounting surface.

Step 2.

 Remove the Protective Cap.

Step 3.

 With pipe thread sealant 

applied to the pipe threads, hand-

tighten the sprinkler into the sprinkler 

fitting.

Step 4.

 Wrench-tighten the sprinkler  

using only the RFII Sprinkler Wrench, 

see Figure 3. Apply the RFII Sprinkler 

Wrench to the Sprinkler as shown in 

Figure 3.

Step 5.

 Replace the Protective Cap by 

pushing it upwards until it bottoms out 

against the Support Cup, see Figure 

4. The Protective Cap helps prevent 

damage to the Deflector and Arms 

during ceiling installation and/or finish. 

You can also use the Protective Cap to 

locate the center of the clearance hole 

by gently pushing the ceiling material 

up against the center point of the Pro-

tective Cap.

NOTICE

As long as the Protective Cap remains 

in place, the system is considered  “Out 

of Service”.

Step 6.

 After the ceiling has been 

completed with the 2-1/2 in. (63,5 mm) 

diameter clearance hole and in prep-

aration for installing the Cover Plate/

Retainer Assembly, remove and discard 

the Protective Cap. Verify that the 

Deflector moves up and down freely.
If the Sprinkler is damaged and the 

Deflector does not move up and down 

freely, replace the entire Sprinkler.  

Do not attempt to modify or repair a 

damaged sprinkler.

Step 7.

 When installing an Air and Dust 

Seal, see Figure 5; otherwise, proceed 

to Step 8. To attach the Air and Dust 

Seal, verify the angle of the outside 

edge of the seal is oriented accord-

ing to Figure 5. Start the edge of the 

Retainer in the grooved slot of the Air 

and Dust Seal and continue around the 

retainer until the entire Air and Dust 

Seal is engaged.

Step 8.

 Screw on the Cover Plate/

Retainer Assembly until the Retainer, 

shown in Figure 2, or the Air and Dust 

Seal, shown in Figure 5, contacts the 

ceiling. Do not continue to screw on the 

Cover Plate/Retainer Assembly so that 

it lifts a ceiling panel out of its normal 

position. If you cannot engage the 

Cover Plate/Retainer Assembly with 

the Support Cup or you cannot engage 

the Cover Plate/Retainer Assembly suf-

ficiently to contact the ceiling, you must 

reposition the Sprinkler Fitting.

COVER PLATE

PROFILE DEPTH

DIMENSION B

1/2" (12,7 mm)

THREADED

ADJUSTMENT

D

FACE OF

SPRINKLER

FITTING

MANUFACTURER

PRESET GAP

3/32" (2,4 mm)

FACE

OF CEILING,

RETAINING RING

MOUNTING

SURFACE

SPRINKLER

SUPPORT CUP

ASSEMBLY

CLEARANCE HOLE

DIAMETER

DIMENSION C

DEFLECTOR

IN DROPPED

POSITION

3/16" to 11/16"

(4,8 to 17,5 mm)

REFERENCE

COVER PLATE

RETAINER

ASSEMBLY

COVER PLATE

DIAMETER

DIMENSION A

FRAME

ARM

SUPPORT

CUP

7/8" (23 mm)

SQUARE

ACCEPTS

1/2" SOCKET

DRIVE

ALIGN

ARROWS WITH

FRAME ARMS

FIGURE 2 

SERIES RFII-MRI CONCEALED SPRINKLER 

INSTALLATION DIMENSIONS

FIGURE 3 

SERIES RFII-MRI SPRINKLER WRENCH