P2-08THM Analog Input

The P2-08THM Thermocouple Input Module 

provides eight differential channels for receiving  

thermocouple and voltage input signals for use

with the Productivity2000 System.

General Specifications   . . . . . . . . . . . . . . . . . . . . . . 1

T/C Input Specifications   . . . . . . . . . . . . . . . . . . . . . 2

Voltage Input Specifications   . . . . . . . . . . . . . . . . . . 2

Configuration/Diagnostics  . . . . . . . . . . . . . . . . . . . . 2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3

Module Installation Procedure . . . . . . . . . . . . . . . . . 4

QR Code  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Hot Swap Information  . . . . . . . . . . . . . . . . . . . . . . . 4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Module Configuration   . . . . . . . . . . . . . . . . . . . . . . . 5

Typical Application Example  . . . . . . . . . . . . . . . . . . 6

OLED Panel Display Menus  . . . . . . . . . . . . . . . . . . 7

Warning  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Removable Terminal Block Specifications. . . . . . . .  8

General Specifications

Operating Temperature

0º to 60ºC (32º to 140ºF)

Storage Temperature

-20º to 70ºC (-4º to 158ºF)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation

1800VAC applied for 1 second

Heat Dissipation

500mW

Enclosure Type

Open Equipment

Agency Approvals

UL508 File E139594, Canada & USA 

CE (EN61131-2*)

Module Keying to Backplane Electronic
Module Location

Any I/O slot in a Productivity2000 System

Field Wiring

Removable terminal block (included). 

The P2-08THM module is not compatible with the 

ZIPLink wiring system.

EU Directive

See the “EU Directive” topic in the Productivity2000 

Help File. Information can also be obtained at: 

www.productivity2000.com

Connector Type (included)

18-position removable terminal block

Weight

90g (3.2 oz)

*Meets EMC and Safety requirements. See the D.O.C. for details.

Terminal Block Included. Not Compatible with ZIPLink.

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement. (See www.productivity2000.com for details).

Summary of Contents for PRODUCTIVITY 2000

Page 1: ...ºC 4º to 158ºF Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800VAC applied for 1 second Heat Dissipation 500mW Enclosure Type Open Equipment Agency Approvals UL508 File E139594 Canada USA CE EN61131 2 Module Keying to Backplane Electronic Module Location Any I O slot in a Pro...

Page 2: ...es Maximum Inaccuracy 3 C maximum excluding thermocouple error including temperature drift Warm up Time 30 minutes for 1 repeatability 2 minutes to reach voltage specifications Sample Duration Time 270ms All Channel Update Rate 2 16 s Open Circuit Detection Time Within 2s Conversion Method Sigma Delta External DC Power Required None Voltage Input Specifications Linear mV Device Input Ranges 0 39 0...

Page 3: ... TC5 TC6 TC6 TC7 TC7 CH2 T C INPUT CH3 T C INPUT CH4 T C INPUT CH5 T C INPUT CH6 T C INPUT CH7 T C INPUT CH8 T C INPUT 1 2 3 4 5 6 7 8 9 10 11 12 18 13 14 15 16 17 Wiring Diagram Schematic NOTES 1 Connect shield to thermocouple signal ground only Do not connect to both ends 2 Install jumper wire on each unused input TC to TC 3 With grounded thermocouples take precautions to prevent having a voltag...

Page 4: ...ationDirect com for details on how to plan your installation for use of this powerful feature 1 Align with slot 2 rotate to seated position WARNING Do not apply field power until the following steps are completed See hot swapping procedure for exceptions WIRESTRIP LENGTH WIRESTRIP LENGTH Step One Align module catch with base slot and rotate module into connector Locked Unlocked Step Two Pull top l...

Page 5: ...tic Module Verification or No Verification and Enable Hot Swap Specify Temperature Scale and Burnout Detection and use the drop down menu to select module range and resolution If desired assign a User Tagname to each input point channel selected and to each Status Bit Item Wiring Options 1 Screw Terminal Block Included P2 RTB Quantity 1 2Spring Clamp Terminal Block P2 RTB 1 Quantity 1 Module Confi...

Page 6: ...rt 770 844 4200 www productivity2000 com Typical Application Example Process Variable feedback Heat Controller Heater PID Output er Oven Temperature User s Desired Setpoint Thermocouple to P2 08THM P2 08THM Module ...

Page 7: ...ted into the cycling Status Info screen Momentarily Press SEL button to toggle through secondary displays Note Volts Celsius or Fahrenheit values are specified with the P2 08THM Module Options configuration dialog box in Productivity Suite software Note SPARE denotes deselected channel 1 J 0 0 0 F 2 E 0 0 0 F 3 0 0 0 m V 4 0 0 0 0 V 5 0 0 0 m V 6 0 0 0 m V 7 0 0 0 m V 8 S P A R E 1J 000 F 2E 000 F...

Page 8: ...ons concerning the installation or operation of this equipment or if you need additional information please call Technical Support at 770 844 4200 This publication is based on information that was available at the time it was printed At AutomationDirect com we constantly strive to improve our products and services so we reserve the right to make changes to the products and or publications at any t...

Reviews: