GCM Battery Replacement
iSTAR Ultra Installation and Configuration Guide
8–7
GCM Battery Replacement
The GCM coin cell battery should be tested annually and replaced as necessary.
The battery is a CR2032 Lithium 230 mA/h coin cell.
The battery retains power for the Real Time Clock for at least 3 weeks. After three weeks
of accumulated power outage, the battery should be replaced.
The battery should last 5 years if there’s no power outages.
To Remove and Replace the Battery
1. With a small screwdriver, gently pry the battery up at point
A
.
2. At the same time, use your thumb to push the black tab back
B
.
3. Gently slide the battery to the left and out.
4. To replace, slide the battery in from the left, under the black tab and under the metal
spring
C
.
Figure 8-2:
GCM Lithium Battery Replacement
Caution - Do not bend or break the metal spring
C
. The spring is important to the operation of
the battery.
A
B
C