background image

 

 

 

 

 

 

 

24- 9890- 161,   Rev.   C

 

 

   

 

Installation Instructions   

 

Issue Date  March 2016 

 

©  2016 Johnson Controls, Inc. 

 

 

Part No. 24-9890-161, Rev. C 

www.johnsoncontrols.com 

 

TEC2103-2 Networked Multi-Stage Thermostat 

Application 

The TEC2103-2 thermostat is an N2 networked 
thermostat that provides control of multi-stage HVAC 
equipment. The TEC2103-2 thermostat provides 
exceptional accuracy through the use of a unique 
Proportional-Integral (PI) time proportioning algorithm. 
The algorithm virtually eliminates temperature offset 
associated with traditional, differential-based on/off 
thermostats. The TEC2103-2 thermostat also uses an 
adaptive control logic algorithm to control the space 
temperature during recovery to minimize overshoot 
while providing maximum comfort. 

The TEC2103-2 thermostat has Metasys® N2 
communication capability. This communication allows 
the user to view and adjust parameters from a remote 
workstation. Additionally, the menu driven backlit 
display, plain text menus, and five keys on the 
TEC2103-2 thermostat make operating the thermostat 
easy and intuitive. 

Note: 

In this document, Building Automation System 

(BAS) is a generic term that refers to the Metasys 
Network (Network Control Module [NCM] or N30 
Series), and Companion (CPN) supervisory systems. 
The specific system names are used when referring to 
system specific applications. 

Installation 

Location Considerations 

Locate the TEC2103-2 thermostat: 

 

on a partitioning interior wall, and approximately 
5 ft. (1.5 m) above the floor in a location of 
average temperature 

 

away from direct sunlight, radiant heat, outside 
walls, behind doors, air discharge grills, stairwells, 
or outside doors 

 

away from steam or water pipes, warm air stacks, 
unheated/uncooled areas, or sources of electrical 
interference 

To install the thermostat: 

1. 

Remove the security screw on the bottom of the 
thermostat cover using a Phillips-head 
screwdriver. Open the thermostat by pulling on 
the bottom side of the thermostat cover 
(Figure 1). 

2. 

Unlock the Printed Circuit Board (PCB) by 
carefully pressing the locking tabs to the right 
(Figure 2). Open the thermostat’s PCB to the left. 

3. 

Pull out approximately 6 in. (152 mm) of wires 
from the wall and insert the cable through the 
hole in the base. 

4. 

Align the base on the wall, and using the base as 
a template, mark the location of the two mounting 
holes on the wall. Confirm the thermostat base is 
installed with the proper side up. 

5. 

Use the supplied anchors and screws for 
mounting on drywall or plaster. Drill two 3/16 in. 
(4.7 mm) holes at the marked locations and tap 
nylon anchors flush to wall surface (Figure 3). 

6. 

Position base on the wall, insert screws through 
mounting base, and fasten into wall anchors. Do 
not overtighten screws. 

7. 

Swing the thermostat PCB back to the right to 
close. Gently press on the PCB to secure each of 
the locking tabs. 

8. 

Pull out the screw terminal blocks using the 
pull-tabs on each connector (Figure 4). 

Note: 

The number of terminals on the terminal 

blocks varies depending on the TEC model. 

 

 

 

 

 

 

Содержание TEC2103-2

Страница 1: ...thermostat on a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills stairwells or outside doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security scr...

Страница 2: ... que dispositif de contrôle de fonctionnement Lorsqu une défaillance ou un dysfonctionnement du thermostat risque de provoquer des blessures ou d endommager l équipement contrôlé ou un autre équipement la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires Veiller dans ce cas à intégrer de façon permanente d autres dispositifs tels que des systèmes de supe...

Страница 3: ... appropriate terminal according to the TEC2103 2 thermostat wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall hole with fireproof material to prevent drafts from affecting ambient temperature readings and install screw terminal blocks back onto the PCB 3 Reattach the thermostat cover to the installed base top side first and install the security screw on the bottom ...

Страница 4: ...or N2 Bus Function Y1 Y2 G RC C RH W1 W2 D1 D2 RS Scom OS N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM Cool 2 Figure 5 TEC2103 2 Thermostat Wiring Schematic Connecting the N2 Bus To connect the N2 Bus 1 Observe the polarity when connecting the N2 Bus wires to the TEC2103 2 thermostat Note An End of Line EOL is not needed on ...

Страница 5: ...BI CSBD 0 Off 1 On G State Fan BD 8 N2 BI CSBD 0 Off 1 On Temp Unitsa c Local Display Only BD 9 N2 BO See Footnote c 0 C 1 F Occupancy Override BD 10 N2 BI CSBD 0 No Override 1 Override DI1b f BI 1 N2 BI CSBI 0 Off 1 On Temp Alarmb BI 2 N2 BI CSBI 0 Normal 1 Alarm DI2b f BI 3 N2 BI CSBI 0 Off 1 On Notes a Commandable b Can be a Change of State COS alarm to the BAS or N2 Dialer Module NDM to initia...

Страница 6: ...stablished in the controller by Minimum Heat SP ADI 7 read only and Maximum Heat SP ADI 8 The value for Cooling SP ADI 4 and Setback Cooling SP ADI 6 must stay within the limits established in the controller by Minimum Cool SP ADI 9 and Maximum Cool SP ADI 10 read only If a setpoint is overridden the TEC if necessary adjusts the other setpoint to maintain the minimum 2 F deadband between the setpo...

Страница 7: ... to manually scroll to the next parameter on the menu When left unattended for 45 seconds the display resumes scrolling NO key when you do not desire a parameter change and to advance to the next menu item MENU key to access the Main User Menu or exit the menu UP DOWN arrow keys to adjust values activate a Temporary Setpoint Configuration Key T600_TEC_Config_Key Figure 7 Configuration Key Location...

Страница 8: ...ving the front cover and pressing the configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Status Display Menu Table 2 Installer Configu...

Страница 9: ... Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with the input Service A Service alarm is displayed Filter A Filter alarm is displayed RemOVR Remote Override OVR contact This disables all override menu functions of the thermostat The override function is now cont...

Страница 10: ... for instructions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection is activated even if the thermostat is set to the Off System Mode If frost protection is active it is displayed as an alarm Frost on with the backlight lit on the Status Display Menu To en...

Страница 11: ...m Heating Stage Cycles per Hour Heat cph section for instructions Setting the Maximum Heating Stage Cycles per Hour Heat cph The heating cycles per hour establishes the maximum number of times the equipment or stages are turned on and off in one hour The selection ranges from three to eight cycles per hour Note A higher number of heating cycles per hour results in more accurate temperature control...

Страница 12: ...ting the N2 Address N2 addr To adjust the N2 address adjustable from 1 to 253 while in the Installer Configuration Menu 1 Answer NO to all prompts until the setting the N2 address prompt appears in the display Press YES to set the address 2 Use the UP DOWN arrow keys to display the desired address Press YES to store the address The display now shows the temporary occupancy time prompt See the Esta...

Страница 13: ...w keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the heating lockout prompt See the Setting the Heating Lockout H lock section for instructions Setting the Heating Lockout H lock This feature disables heating operation based on auxiliary or outdoor air temperature requires temperature sensor to be connected to the Auxiliary Outdoor Air Sensor terminal OS for t...

Страница 14: ...the first prompt 2 Press YES to enable the temporary override The TEC2103 2 thermostat returns to the Status Display Menu When scrolling through the Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu 1 Answer NO to all prompts until the Resume Schedule ...

Страница 15: ...he temporary setpoint for the current mode of operation Note Whether the thermostat is heating or cooling the respective setpoint will be temporarily adjusted Note To toggle between the temporary heating and cooling setpoints press the NO key while changing the temporary setpoints Note If a setpoint is overridden over the N2 network it appears the setpoint value can be changed through the TEC2103 ...

Страница 16: ...upied and unoccupied periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods Smart Fan Mode smart Energizes the fan all the time for occupied periods and only on a call for heating and cooling in unoccupied periods This is the default setting To set the fan mode while in the Main User Menu...

Страница 17: ...pply power to the TEC2103 2 thermostat N2 cable runs are broken Locate and correct the wiring Device type is incorrect TEC2103 2 thermostat address must be VND device type Entire N2 Bus is offline EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Computer PC or 120 VAC source Plug MM CVT101 into PC or plug it into a 120 VAC so...

Страница 18: ...6 x 29 mm Shipping Weight 0 75 lb 0 34 kg UL and cUL Listing File E27734 with CCN s XAPX US UL 873 and XAPX7 Canada CSA C22 2 No 24 FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference when this eq...

Страница 19: ... GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2016 Johnson Contr...

Отзывы: