Configuring the Digital Inputs (DI1 and DI2) 

Press the configuration menu access key. The first 
prompt is to program Digital Inputs DI1 and DI2. 

The digital inputs display an alarm condition when the 
input is closed. An alarm message is included on the 
scrolling Status Display Menu and when the message 
is displayed, the backlight momentarily lights up. 

Each digital input can be programmed in one of five 
conditions. 

• 

None

 – No function is associated with the input. 

• 

Service

 – A Service alarm is displayed. 

• 

Filter

 – A Filter alarm is displayed. 

• 

RemNSB

 – Remote night setback timer clock 

input. The scheduling is set per the digital input 
when this option is selected. 

− 

Open Contact = Occupied setpoints 

− 

Closed Contacts = Unoccupied setpoints 

• 

RemOVR

 – Remote override contact. This 

disables all override menu functions of the 
thermostat. The override function is controlled 
manually by a remote, momentarily closed 
contact. When configured in this mode, the input 
operates in a toggle mode. With this function 
enabled, it is now possible to toggle between 
unoccupied and occupied setpoints for the amount 
of time set by the temporary occupancy time 
parameter. 

When override is enabled through the digital inputs, an 

Override

 message appears in the Status Display 

Menu. 

To configure the digital inputs while in the Installer 
Configuration Menu: 
1.  The first prompt is to configure the digital inputs. 

Press YES to configure Digital Input 1 or NO to 
advance to Digital Input 2. 

2.  Use the UP/DOWN arrow keys to locate the 

desired function for the Digital Input 1. Press YES 
to select the desired function. 

3.  Press YES to configure Digital Input 2 or NO to 

advance to the keypad lockout setup prompt. 

4.  Use the UP/DOWN arrow keys to locate the 

desired function for the Digital Input 2. Press YES 
to select the desired function. 

The display now shows the keypad lockout setup 
prompt. See the 

Enabling Keypad Lockout (Lockout) 

section for instructions. 

Enabling Keypad Lockout (Lockout) 

The T600HCN-1 has three levels of keypad lockout. 
The levels and degree of lockout are shown in Table 2. 

To set the keypad lockout level while in the Installer 
Configuration Menu: 
1.  Answer NO to all prompts until the keypad lockout 

setup prompt appears in the display. Press YES to 
enter the keypad lockout menu. 

2.  Use the UP/DOWN arrow keys to locate the 

desired lockout level. Press YES to select the 
level. 

The display now shows the power delay setup prompt. 
See the 

Setting the Power-up Delay (Pwr del)

 section 

for instructions. 

Table 2: Keypad Lockout Levels 

 

Level 0 

Level 1 

Level 2 

*Resume to 

Scheduling 

Yes access 

Yes access 

No access 

Temperature 

Setpoints 

Yes access 

No access 

No access 

System 

Mode Setting 

Yes access 

Yes access 

No access 

Fan Mode 

Setting 

Yes access 

Yes access 

No access 

*Permanent 

Hold 

Yes access 

Yes access 

No access 

*  Displayed only if digital input DI1 or DI2 is configured 

for remote NSB. 

 

Setting the Power-up Delay (Pwr del) 

On initial power up of the T600HCN-1 (or each time 
power is removed and reapplied), there is a delay 
before any operation is authorized (fan, cooling, and 
heating). The delay time is adjustable between 
10 and 120 seconds. You can also use this parameter 
to sequence the startup of multiple units in one 
location. 

Note: 

When adjusting the time with the UP/DOWN 

arrow keys, holding the keys down changes the time 
by 10-second intervals. 

6    

T600HCN-1 Non-Programmable Thermostat Installation Instructions 

Содержание T600HCN-1

Страница 1: ...the thermostat cover see Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs to the right see Figure 2 Open the thermostat s PCB to the left 3 Pull out approximatel...

Страница 2: ...e the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire back into wall plug the wall hole with...

Страница 3: ...24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stage Configurable digital input Configurable digital input Remote room sensor Sensor common Outdoor air s...

Страница 4: ...uring normal thermostat operation The menu continually scrolls through the following parameters see Figure 6 Room Temperature System Mode Schedule Status Occupied Unoccupied see Note Outdoor Temperatu...

Страница 5: ...Maximum Cooling Cycles per Hour Cool cph Sets the Minimum Heating Cooling Deadband Default 2 0 F 1 1 C See Setting the Heating Cooling Deadband Deadband Determines how the Fan Activates in Response to...

Страница 6: ...nfigure Digital Input 2 or NO to advance to the keypad lockout setup prompt 4 Use the UP DOWN arrow keys to locate the desired function for the Digital Input 2 Press YES to select the desired function...

Страница 7: ...ows the minimum cooling setpoint prompt See the Setting the Minimum Cooling Setpoint Cool min section for instructions Setting the Minimum Cooling Setpoint Cool min The minimum cooling setpoint establ...

Страница 8: ...hes the minimum difference between the heating and cooling setpoints The range is adjustable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in th...

Страница 9: ...the display Press YES to enter the outdoor sensor calibration menu 2 Use the UP DOWN arrow keys to adjust the correction that should be applied to the sensor reading Press YES to store the offset The...

Страница 10: ...de schedule prompt only appears when the thermostat is in the unoccupied state This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the...

Страница 11: ...et prompt appears in the display it may be the first prompt Press YES to enter temperature setting menu Press YES to change occupied cooling setpoint Press NO to advance to occupied heating setpoint m...

Страница 12: ...rn to the Status Display Menu or NO to return to the fan mode selection menu Setting Permanent Hold Note Displayed only if Digital Input DI1 or DI2 is configured for remote NSB This menu is used to se...

Страница 13: ...d to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interferenc...

Отзывы: