background image

 

Setting the Maximum Heating Cycles per Hour 
(Heat cph) 

The heating cycles per hour establishes the maximum 
number of times the equipment is turned on and off in 
one hour. The selection ranges from three to eight 
cycles per hour. 

Note: 

A higher number of heating cycles per hour 

results in more accurate temperature control, but could 
accelerate the wear of mechanical components in the 
equipment. 

To set the maximum number of heating cycles per 
hour while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the heating cycles 

per hour prompt appears in the display. Press 
YES to enter the heating cycles per hour menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum number of heating cycles per hour. 
Press YES to store the value. 

The display now shows the cooling cycles per hour 
setup prompt. See the 

Setting the Maximum Cooling 

Cycles per Hour (Cool cph)

 section for instructions. 

Setting the Maximum Cooling Cycles per Hour 
(Cool cph) 

The cooling cycles per hour establishes the maximum 
number of times the equipment is turned on and off in 
one hour. The selection ranges from three to four 
cycles per hour. 

Note: 

A higher number of cooling cycles per hour 

results in more accurate temperature control, but could 
accelerate the wear of mechanical components in the 
equipment. 

To set the maximum number of cooling cycles per 
hour while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the cooling cycles 

per hour prompt appears in the display. Press 
YES to enter the cooling cycles per hour menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum number of cooling cycles per hour. 
Press YES to store the value. 

The display now shows the minimum heating/cooling 
deadband prompt. See the 

Setting the Heating/Cooling 

Deadband

 

(Deadband)

 section for instructions. 

Setting the Heating/Cooling Deadband (Deadband) 

The heating/cooling deadband setting establishes the 
minimum difference between the heating and cooling 
setpoints. The range is adjustable from 2 to 4 F

°

 

(1 to 2 C

°

). 

 

 

To change the minimum deadband between the 
heating and cooling setpoints while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the deadband 

setpoint prompt appears in the display. Press YES 
to enter the deadband setpoint menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

minimum deadband between the heating and 
cooling setpoints. Press YES to store the value. 

The display now shows the fan control prompt. See 
the 

Setting the Fan Control (Fan cont) 

section for 

instructions. 

Setting the Fan Control (Fan cont) 

This parameter controls how the fan activates in 
response to a call for heating. 

When the fan is in Auto Mode (as selected on the Main 
User Menu): 

• 

Selecting 

on

 enables the thermostat to control the 

fan on a call for heating or cooling. 

• 

When selecting 

off

, the fan energizes by the 

thermostat on a call for cooling only. On a call for 
heating, the fan is controlled by the equipment fan 
limit control. 

To set the fan control while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the fan control 

prompt appears in the display. Press YES to enter 
the fan control menu. 

2.  Using the UP/DOWN arrow keys, select 

on

 or 

off

Press YES to store the selection. 

The display now shows the fan delay prompt. See the 

Setting the Setting the Fan Delay (Fan del)

 section for 

instructions. 

Setting the Fan Delay (Fan del) 

The fan delay extends the fan operation by 
60 seconds after the call for heating or cooling has 
ended. This feature is only active when the fan is in 
the 

Auto

 mode. 

To enable the fan delay while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the fan delay 

prompt appears in the display. Press YES to enter 
the fan delay menu. 

2.  Using the UP/DOWN arrow keys, select 

on

 or 

off

Press YES to store the selection. 

The display now shows the occupancy override 
prompt. See the 

Establishing the Temporary 

Occupancy Time (ToccTime)

 section for instructions. 

8    

T600HCN-1 Non-Programmable Thermostat Installation Instructions 

Содержание T600HCN-1

Страница 1: ...the thermostat cover see Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs to the right see Figure 2 Open the thermostat s PCB to the left 3 Pull out approximatel...

Страница 2: ...e the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire back into wall plug the wall hole with...

Страница 3: ...24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stage Configurable digital input Configurable digital input Remote room sensor Sensor common Outdoor air s...

Страница 4: ...uring normal thermostat operation The menu continually scrolls through the following parameters see Figure 6 Room Temperature System Mode Schedule Status Occupied Unoccupied see Note Outdoor Temperatu...

Страница 5: ...Maximum Cooling Cycles per Hour Cool cph Sets the Minimum Heating Cooling Deadband Default 2 0 F 1 1 C See Setting the Heating Cooling Deadband Deadband Determines how the Fan Activates in Response to...

Страница 6: ...nfigure Digital Input 2 or NO to advance to the keypad lockout setup prompt 4 Use the UP DOWN arrow keys to locate the desired function for the Digital Input 2 Press YES to select the desired function...

Страница 7: ...ows the minimum cooling setpoint prompt See the Setting the Minimum Cooling Setpoint Cool min section for instructions Setting the Minimum Cooling Setpoint Cool min The minimum cooling setpoint establ...

Страница 8: ...hes the minimum difference between the heating and cooling setpoints The range is adjustable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in th...

Страница 9: ...the display Press YES to enter the outdoor sensor calibration menu 2 Use the UP DOWN arrow keys to adjust the correction that should be applied to the sensor reading Press YES to store the offset The...

Страница 10: ...de schedule prompt only appears when the thermostat is in the unoccupied state This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the...

Страница 11: ...et prompt appears in the display it may be the first prompt Press YES to enter temperature setting menu Press YES to change occupied cooling setpoint Press NO to advance to occupied heating setpoint m...

Страница 12: ...rn to the Status Display Menu or NO to return to the fan mode selection menu Setting Permanent Hold Note Displayed only if Digital Input DI1 or DI2 is configured for remote NSB This menu is used to se...

Страница 13: ...d to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interferenc...

Отзывы: