Entering Temperature Setpoints 

When the T600HCN-1 is in the occupied state, the first 
prompt appearing in the Main User Menu is to set the 
temperature setpoints. This prompt is where the 
heating and cooling setpoints for the occupied and 
unoccupied (see * in Table 3) states are entered. It is 
also where any temporary setpoints are entered. 

To enter the heating and cooling setpoints for the 
occupied and unoccupied (see * in Table 3) modes 
(permanent or temporary), follow the steps in Table 4. 
When changing the temperatures, pressing the keys 
once changes the temperature 0.5 F/C

°

 and holding 

down the keys changes the temperature by 5 F/C

°

 

increments. 

Setpoint Type 

Permanent Setpoints

 are permanently stored in the 

schedule. This is the default setpoint type. 

Temporary Setpoints

 are changed, but are in effect 

only for the time specified in the 

Establishing the

 

Temporary Occupancy Time (ToccTime)

 parameter 

(see the 

Configuring the T600HCN-1

 section). 

Note: 

There is no indication that a temporary 

setpoint is enabled or active. 

After the specified time, the temporary setpoint reverts 
to the permanent setpoint. 

The temporary setpoint can be cancelled at any time 
by using the Permanent Setpoint option in this menu. 
When permanent modifications of the setpoints are 
required, this parameter needs to be set to permanent. 

Table 4: Entering Temperature Setpoints 

 

Press MENU from the Status Display 
Menu to enter the Main User Menu. 

 

Answer NO to all prompts until the 
temperature set prompt appears in 
the display (it may be the first 
prompt). Press YES to enter 
temperature setting menu. 

 

Press YES to change occupied 
cooling setpoint. Press NO to 
advance to occupied heating setpoint 
menu. 

 

Use the UP/DOWN arrow keys to set 
temperature. Press YES to store 
value and advance to next menu. 

 

Press YES to change the occupied 
heating setpoint. Press NO to 
advance to unoccupied cooling 
setpoint menu. 

 

Use the UP/DOWN arrow keys to set 
temperature. Press YES to store 
value and advance to next menu. 

 

*

Press YES to change the 
unoccupied cooling setpoint. Press 
NO to advance to the unoccupied 
heating setpoint. 

 

 

 

*

Use the UP/DOWN arrow keys to 
set temperature. Press YES to store 
value and advance to next menu. 

 

*

Press YES to change the 
unoccupied heating setpoint. Press 
NO to advance to temperature 
display units. 

 

*

Use the UP/DOWN arrow keys to 
set temperature. Press YES to store 
value and advance to next menu. 

 

Press YES to set the display units to 

°

F or 

°

C. Press NO to advance to 

temperature setpoint type menu. 

 

Press YES to select the setpoint type 
(permanent or temporary). 

 

Using the UP/DOWN arrow keys, 
select the setpoint type (see 

Setpoint 

Type

 section for a description of 

choices). Press YES to enter the 
choice. 

 

Press YES to return to the Status 
Display Menu or NO to re-enter the 
temperature setting menu. 

*  Displayed only if Digital Input DI1 or DI2 is configured 

for remote NSB. 

RoomTemp 
75.0

°

Unocc CL 
80.0

°

Unocc HT 
set? Y/N 

Temperat 
set? Y/N 

Unocc HT 
62.0

°

F

 

Cooling 
set? Y/N 

°

F/

°

set? Y/N 

Cooling 
75.0

°

Setpoint
type Y/N 

Heating 
set? Y/N 

Setpoint
permnent 

Heating 
68.0

°

Exit?
 Y/N 

Unocc CL 
set? Y/N

 

T600HCN-1 Non-Programmable Thermostat Installation Instructions    

11

 

Содержание T600HCN-1

Страница 1: ...the thermostat cover see Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs to the right see Figure 2 Open the thermostat s PCB to the left 3 Pull out approximatel...

Страница 2: ...e the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire back into wall plug the wall hole with...

Страница 3: ...24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stage Configurable digital input Configurable digital input Remote room sensor Sensor common Outdoor air s...

Страница 4: ...uring normal thermostat operation The menu continually scrolls through the following parameters see Figure 6 Room Temperature System Mode Schedule Status Occupied Unoccupied see Note Outdoor Temperatu...

Страница 5: ...Maximum Cooling Cycles per Hour Cool cph Sets the Minimum Heating Cooling Deadband Default 2 0 F 1 1 C See Setting the Heating Cooling Deadband Deadband Determines how the Fan Activates in Response to...

Страница 6: ...nfigure Digital Input 2 or NO to advance to the keypad lockout setup prompt 4 Use the UP DOWN arrow keys to locate the desired function for the Digital Input 2 Press YES to select the desired function...

Страница 7: ...ows the minimum cooling setpoint prompt See the Setting the Minimum Cooling Setpoint Cool min section for instructions Setting the Minimum Cooling Setpoint Cool min The minimum cooling setpoint establ...

Страница 8: ...hes the minimum difference between the heating and cooling setpoints The range is adjustable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in th...

Страница 9: ...the display Press YES to enter the outdoor sensor calibration menu 2 Use the UP DOWN arrow keys to adjust the correction that should be applied to the sensor reading Press YES to store the offset The...

Страница 10: ...de schedule prompt only appears when the thermostat is in the unoccupied state This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the...

Страница 11: ...et prompt appears in the display it may be the first prompt Press YES to enter temperature setting menu Press YES to change occupied cooling setpoint Press NO to advance to occupied heating setpoint m...

Страница 12: ...rn to the Status Display Menu or NO to return to the fan mode selection menu Setting Permanent Hold Note Displayed only if Digital Input DI1 or DI2 is configured for remote NSB This menu is used to se...

Страница 13: ...d to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interferenc...

Отзывы: