background image

 

Thermostat Interface Keys 

The T600HCN-1 interface consists of five keys on 
the front cover and one configuration key 
(see Figure 7) that is accessed by removing the 
front cover. The functions of the keys are as 
follows. Use the: 

• 

YES key to confirm a selection and move onto the 
next menu item 

• 

NO key when you do not desire a parameter 
change, and to advance to the next menu item 

• 

MENU key to access the Main User Menu or exit 
the menu 

• 

down arrow key to scroll through menu selections 
or adjust values 

• 

up arrow/SCROLL key to: 

− 

scroll through menu selections or adjust 
values 

− 

stop the Status Display Menu from scrolling 
and to manually scroll to the next parameter 
on the menu. When left unattended for 
45 seconds, the display resumes scrolling 

Configuration

Key

 

Figure 7: Configuration Key Location 

Backlit Liquid Crystal Display (LCD) 

The T600HCN-1 uses a two-line, eight-character 
backlit display. Low level backlighting is present during 
normal operation and it brightens when any user 
interface key is pressed. The backlight returns to the 
lower level when the thermostat is left unattended for 
45 seconds. 

Light-Emitting Diodes (LED)s 

Three LEDs are used to indicate the status of the fan, 
call for heat, or call for cooling. When: 

• 

the fan is on, the FAN LED lights up 

• 

heating is on, the HEAT LED lights up 

• 

cooling is on, the COOL LED lights up 

Programming Overview 

There are three menus used to view, program, and 
configure the T600HCN-1 thermostat. 

The 

Status Display Menu 

is the menu that displays 

during normal thermostat operation. The menu 
continually scrolls through the following parameters 
(see Figure 6). 

• 

Room Temperature 

• 

System Mode 

• 

Schedule Status (Occupied/Unoccupied 
[see Note]) 

• 

Outdoor Temperature (providing sensor is 
connected and functional) 

• 

Applicable Alarms (the backlight lights up as an 
alarm condition is displayed) 

To temporarily stop the scrolling, press the up 
arrow/SCROLL key. 

Note: 

Displayed only if Digital Input (DI1 or DI2) is 

configured for remote Night Setback (NSB). 

The 

Main User Menu

 is used to access and change 

the thermostat’s basic operating parameters. Access 
the menu by pressing the MENU key during normal 
thermostat operation. 

The 

Installer Configuration Menu 

is used to set up 

the thermostat for application specific operation. 
Access the menu by removing the front cover and 
pressing the configuration key, labeled CONFIG 
(see Figure 7). 

Configuring the T600HCN-1 

The T600HCN-1 ships from the factory with default 
settings for all configurable parameters. The default 
settings are shown in Table 1. To reconfigure the 
parameters, follow the steps in this section for the 
corresponding parameters. The parameters must be 
set up by accessing the Installer Configuration Menu. 
Access the Installer Configuration Menu by removing 
the front cover and pressing the configuration key 
(see Figure 7). 

Exit the Installer Configuration Menu anytime by 
pressing the MENU key and, at the exit prompt, 
pressing the YES key. To pass over a parameter 
without changing it, press the NO key. 

When the thermostat is in the Installer Configuration 
Menu and left unattended for 45 seconds, it reverts to 
the Status Display Menu. 

4    

T600HCN-1 Non-Programmable Thermostat Installation Instructions 

Содержание T600HCN-1

Страница 1: ...the thermostat cover see Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs to the right see Figure 2 Open the thermostat s PCB to the left 3 Pull out approximatel...

Страница 2: ...e the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire back into wall plug the wall hole with...

Страница 3: ...24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stage Configurable digital input Configurable digital input Remote room sensor Sensor common Outdoor air s...

Страница 4: ...uring normal thermostat operation The menu continually scrolls through the following parameters see Figure 6 Room Temperature System Mode Schedule Status Occupied Unoccupied see Note Outdoor Temperatu...

Страница 5: ...Maximum Cooling Cycles per Hour Cool cph Sets the Minimum Heating Cooling Deadband Default 2 0 F 1 1 C See Setting the Heating Cooling Deadband Deadband Determines how the Fan Activates in Response to...

Страница 6: ...nfigure Digital Input 2 or NO to advance to the keypad lockout setup prompt 4 Use the UP DOWN arrow keys to locate the desired function for the Digital Input 2 Press YES to select the desired function...

Страница 7: ...ows the minimum cooling setpoint prompt See the Setting the Minimum Cooling Setpoint Cool min section for instructions Setting the Minimum Cooling Setpoint Cool min The minimum cooling setpoint establ...

Страница 8: ...hes the minimum difference between the heating and cooling setpoints The range is adjustable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in th...

Страница 9: ...the display Press YES to enter the outdoor sensor calibration menu 2 Use the UP DOWN arrow keys to adjust the correction that should be applied to the sensor reading Press YES to store the offset The...

Страница 10: ...de schedule prompt only appears when the thermostat is in the unoccupied state This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the...

Страница 11: ...et prompt appears in the display it may be the first prompt Press YES to enter temperature setting menu Press YES to change occupied cooling setpoint Press NO to advance to occupied heating setpoint m...

Страница 12: ...rn to the Status Display Menu or NO to return to the fan mode selection menu Setting Permanent Hold Note Displayed only if Digital Input DI1 or DI2 is configured for remote NSB This menu is used to se...

Страница 13: ...d to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interferenc...

Отзывы: