Operation Guideline
Product Model: KONOzw
Copyright
Johnson Controls Inc 2019
All Rights Reserved
Page 15 of 19
(skip if System Type =
Furnace)
B: B Valve
10
Minimum On/Off Time
5: 5 minutes
2: 2 minutes
5
11
Swing
±0.25°F (±0.14°C)
±0.50°F (±0.28°C)
±1.00°F (±0.56°C)
±2.25°F (±1.25°C)
0.25
0
F
12
Stage 2 offset (show
only if systemType =
Furnace & avMode !=
Cool only)
OFF ;
-1.0°F (-0.6°C)
-2.0°F (-1.1°C)
-3.0°F (-1.7°C)
-4.0°F (-2.2°C)
-5.0°F (-2.8°C)
OFF / 1°F
(depends on
terminal
detection)
13
Stage Aux offset (show
only if systemType = HP)
OFF ;
-1.0°F (-0.6°C)
-2.0°F (-1.1°C)
-3.0°F (-1.7°C)
-4.0°F (-2.2°C)
-5.0°F (-2.8°C)
OFF / 2°F
(depends on
terminal
detection)
15
Backlight always on?
(skip if it is battery
powered)
OFF: turns off after 10s
ON: always ON
OFF
16
Filter Life
(Skip if systemType =
boiler without fan &
avMode = Heat Only)
OFF
30 days
60 days
90 days
120 days
180 days
365 days
OFF
98
Compressor protection
bypass
NO: no action
Yes: suspends minimum off time
for next 10 mins
NO
99
Ex-Factory Reset
NO
YES
NO