Operation Guideline
Product Model: KONOzw
Copyright
Johnson Controls Inc 2019
All Rights Reserved
Page 11 of 19
Configuration Command Class :
KONOzw supports the following configuration parameters:
Parameter
ID
Parameter
Size (Byte)
Parameter Name
Parameter Values
Default
Value
Description
1
2
User Temperature Calibration
-250 to 250, step-
size = 10
0
in steps of 0.1°C
2
1
Temperature Unit (C/F)
0 : C
1 : F
1
3
1
Available Control mode
0-4
0
0: Heat and Cool, Auto
1: Heat Only
2: CoolOnly
3: Heat and Cool, no Auto
4: reserved
4
1
System Type
0-4
0
0: Furnace Gas
1: Furnace Electric
2: Heat Pump
3: Boiler no fan
4: reserved
5
1
Reversal valve Type in Heat Pump
0 – O-valve
1 – B-valve
0
6
reserved
7
reserved
8
2
Temperature Limit - Heat Max
60.00F-90.00F (16C-
32C)
90F
(32C)
9
2
Temperature Limit - Heat Min
45.00F-60.00F (7C-
16C)
45F (7C)
10
2
Temperature Limit - Cool Max
60F-95F
(16C-35C)
95F
(35C)
Note: The actual allowable
range is dependent on the heat
set point limit
11
2
Temperature Limit - Cool Min
50F-75F
(10C-24C)
50F
(10C)
Note: The actual allowable
range is dependent on the heat
set point limit
12
2
Temperature Minimum Setpoint
Deadband
100 to 250, stepsize
= 10
200
(0xC8)
in a step of 0.1C
13