Telephone: 01604 762881
9.
ELECTRICAL
WARNING: THIS APPLIANCE MUST BE EARTHED!
9.1
MAINS
9.1.1 The heater is supplied with mains cable (PVC sheathed, heat resisting to 85˚C), 3 core: Brown; Blue; Green/Yellow,
6A, 0.75mm²), connected to a terminal block and exiting through the heater at the right hand top. The cable is
suitable for a 230V 50Hz supply and requires connection to the fixed wiring using a double pole switched, fused
spur with a contact separation of at least 3mm in ALL poles. The fuse fitted must be rated 5A to BS 1362.
Connections must also be in accordance with the current edition of I.E.E Regulations BS 7671.
NOTE:
If, for any reason, the heater is re-wired, then 3 core cable that meets the above specification MUST be used. Under
NO circumstances, should 5 core cable be used for the combined purpose of supplying power to the heater and
connecting the thermista-stat!
9.1.2 Fan delay and overheat (limit controls) are not adjustable and are factory set so that the limit switch opens at 80˚C
and closes at 40˚C.
9.1.3. An electronic controller (thermista-stat) is supplied which acts like a room thermostat.
9.2
THERMISTA-STAT AND ITS LOCATION.
9.2.1 The thermista-stat should be located where there is free air circulation and positioned approx. 1.5m (5ft) from the
floor.
9.2.2 Avoid the following locations:
a. In a room where temperature is greatly affected by the sun or any other heat source, e.g. radiant fire, wall light
fittings or TV set.
b. Near an outside door or windows, or on an outside wall.
c. Where it will be affected by warm air ducts, diffusers, waste pipes or the heater itself.
d. Where it will be subjected to vibration.
9.2.3 Connect the thermista-stat wires to terminals ‘8’ and ‘9’ on the terminal block (see Figures 13 & 14).
10. GAS
(See BS 5864 and BS 6891)
10.1
The local gas supply conditions MUST be adequate for the specified burner pressures as stated in the technical data
(paragraph 1.3)
10.2
An independent gas supply pipe from the meter is to be preferred wherever possible. Where this is not possible, the pipe
must be capable of taking the complete input of the heater and all other gas appliances being served by the same pipe.
This supply should be suitably sized to conform to British Standards requirements of no more than 1.0 mbar (0.4” wg)
pressure drop (See table of discharge in BS 6891).
10.3
The ½” union gas cock (supplied) MUST be fitted to the gas inlet of the heater for easy isolation during servicing. The gas
pipe should be fitted and installed so as to be durable, substantial and gas tight. To assist in determining where a gas
connection may not be tight, a leak detection fluid should be applied around the connection. Under no circumstances
should a flame be used to locate a gas leak. Gas entry to the air heater is through either side or the base, to a Rc½ (½”
BSP. external [taper] thread).
11. AIR HEATER COMMISSIONING
11.1 PREPARATION
After installation of the appliance, you MUST do the following:
11.1.1 Test for gas leakage using proprietary detection fluid and seal any leaks found.
11.1.2 Carry out preliminary electrical system checks.
11.1.3 Ensure that:
a. filter, fan and fan compartments are free from obstructions.
b. all registers or grilles are open and conform to design specifications.
c. return, relief and ventilation air installations are adequate.
11.2 SYSTEM BALANCING
11.2.1 Set the air heater electrical supply ON.
11.2.2 Set the thermista-stat to the “SUMMER AIRFLOW” position.
11.2.3 Balance the system to provide the required volume proportions at the warm air outlets.
NOTE
If the system includes ceiling diffusers, the air through these should be NOT LESS THAN 1.5m/s (300ft/min), except for
very small rooms, (i.e. bathrooms etc.). Outlet faces may require partial blanking in order to achieve this.
11.3 LIGHTING IGNITION AND MAIN BURNER
11.3.1 Turn on the gas supply to the heater.
11.3.2 Set both the “AIR HEATER” and “WATER HEATER” switches on the time control unit to the “OFF” position.
11.3.3 Set the thermista-stat to “9”.
Содержание ECONOMAIRE 32
Страница 19: ...19 Telephone 01604 762881 FIGURE 12 CONTROL FLOWCHART 17 DIAGNOSIS FLOWCHARTS...
Страница 20: ...www johnsonandstarley co uk 20 FIGURE 13 AIR HEATER DIAGNOSIS FLOWCHART...
Страница 21: ...21 Telephone 01604 762881 FIGURE 14 CONTROL FLOWCHART...
Страница 22: ...www johnsonandstarley co uk 22 18 LOGIC DIAGRAM FIGURE 15 LOGIC DIAGRAM...
Страница 23: ...23 Telephone 01604 762881 3 19 SCHEMATIC DIAGRAM FIGURE 16 SCHEMATIC DIAGRAM...
Страница 25: ...25 Telephone 01604 762881 21 DIMENSIONS FIGURE 18 DIMENSIONS...
Страница 27: ...27 Telephone 01604 762881 FIGURE 19 EXPLODED DIAGRAM 23 EXPLODED DIAGRAM...
Страница 31: ......