Johnson & Starley ECONOMAIRE 32 Скачать руководство пользователя страница 5

Telephone: 01604 762881

5.5 

In under-stairs installations, the compartment must comply with the relevant section of BS 5864, provided that in 
addition all internal surfaces (including the base) are non-combustible or lined with non-combustible material. This 
requirement is applicable only to dwellings of  more than two storeys.

5.6   In free-standing installations, (see instructions packed with TC32 or TC32R top closure kit), only one or two walls 

will be in close proximity to the air heater; these must be non-combustible.

5.7 

Where the air heater is to be installed onto a combustible surface and under-floor ducting used, a suitable 
base tray (BT32) MUST be used in order to provide insulation. NB where a base plenum is used no base tray is 
required!

6.  VENTILATION  AIR

6.1   When installed in a compartment two permanent ventilation openings into the compartment are required, one at high level 

and one at low level. The minimum effective areas specified in Table 1 are related to the rated heat input of the air heater 
and assume that an INTEJAN circulator is fitted. 

7.  DUCT SYSTEM

(See British Design Manual - Gas fired Warm Air Heating)

7.1  RETURN AIR

7.1.1  Room-sealed appliances may be installed without return air ducting, provided that the path between the return air 

grille and the appliance return air inlet is protected in such a manner that the required air-flow will be maintained 
at all times. The return air grille MUST have a free area of not less than 860cm²  (137in²). It is recommended that 
the return air duct not be routed directly from the main living area, but from a convenient central area serving the 
remainder of the dwelling.

7.1.2   The return air system should be constructed of fire-resistant material. The flue shall not be run through an area 

serving as a return air plenum. It is extremely important that the correct size of return air grilles and ducting is 
used. For heaters on maximum output the return air duct size should not be less than the equivalent of 250mm x 
200mm (10” x 8”). If flexible duct is used the duct diameter should not be less than 300mm (12”) diameter. The 
return air grille should have a free area of not less than 860cm² (137in²).

7.1.3   An adequate and unobstructed return air path is essential from areas not served by a directly ducted return and to 

which warm air is delivered. All such rooms should be fitted with relief grilles which have a free area of 0.0088m²/
kW (1in²/250Btu/h) of heat supplied to the room. The only exceptions are kitchens, bathrooms and WC.’s.

7.1.4   The return air duct should allow for ease of removal for access to the flue.  

7.1.5   All duct work in the room or internal space in which the heater is installed shall be mechanically secured and 

sealed with ducting tape.

7.2  WARM DELIVERED AIR

7.2.1   All duct work, including riser ducts, should be fully insulated with 50mm (2”) fibreglass or similar. If short extended 

duct runs are taken below floor level these should be similarly insulated and in addition wrapped with a sound 
vapour proof barrier. They must also be protected from crushing.

7.2.2   The duct system should be carefully designed (as given in the guidelines in the British System Design Manual) to 

suit the needs of specific heating requirements and building layout. The type of duct system (e.g. radial/extended 
plenum/ stepped) should be installed using the least number of fittings to minimise airflow resistance. The base 
duct, which equalises the air pressure to supply ducts, must be constructed to support the weight of the heater, 
which must be sealed using self-adhesive foam strip, ducting tape or sealing compound. All ducting and blanking 
plates must be mechanically secured and sealed. 

VENTILATED FROM INSIDE BUILDING

Low level grille 162cm² (25in²)

High level grille 162cm² (25in²)

VENTILATED FROM OUTSIDE BUILDING

Low level grille 81cm² (13in²)

High level grille 81cm² (13in²)

TABLE 1
MINIMUM EFFECTIVE AREAS

Содержание ECONOMAIRE 32

Страница 1: ...k Publication No ZZ 1088 12 April 2010 ECONOMAIRE 32 WARM AIR HEATER with Intejan Water Circulator INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS G C NUMBERS Air Heater 42 416 14 Water Circulator 5...

Страница 2: ...nt for their needs that it is installed commissioned and serviced in accordance with the manufacturer s instructions by competent persons and that it meets the requirements of the appropriate Building...

Страница 3: ...for retro fit to the ECONOMAIRE 32 2 2 The air heater output can be adjusted between 7 3kW 26 4MJ h 25 000 Btu h and 9 4kW 33 8MJ h 32 000 Btu h summer air circulation of unheated air is available by...

Страница 4: ...n existing base duct warm air plenum always ensure that installation is carried out such that the rear left hand corner of the heater is aligned with the rear left hand corner of the base duct so that...

Страница 5: ...t size of return air grilles and ducting is used For heaters on maximum output the return air duct size should not be less than the equivalent of 250mm x 200mm 10 x 8 If flexible duct is used the duct...

Страница 6: ...larly under a balcony or immediately adjacent to a drain pipe 8 2 3 The terminal position must ensure that combustion products cannot enter the building in which the heater is installed or any adjacen...

Страница 7: ...From a vertical drain pipe or soil pipe 150mm H From an internal or external corner Greater than 450mm protrusion 300mm I Above ground roof or balcony level 300mm J From a surface facing the terminal...

Страница 8: ...al Terminal Support Bracket 1 1000 0014980 Terrcotta 7 Lead Pitched Roof Flashing Collar 1 1000 0014890 Anthracite 8 Lead Pitched Roof Flashing Collar 1 1000 0014990 Terracotta 9 Aluminium Flat Roof F...

Страница 9: ...chnical data paragraph 1 3 10 2 An independent gas supply pipe from the meter is to be preferred wherever possible Where this is not possible the pipe must be capable of taking the complete input of t...

Страница 10: ...green LED ON light on the indicator panel will illuminate After a period of approx 5 seconds the module will move on to stage 6 indicated by 6 on the LED NOTE Regardless of when the burner ignites dur...

Страница 11: ...chmark Checklist located on the inside back pages of this document prior to handing over the appliance to the occupier 11 6 SAFETY CHECK In order to check the correct operation of the control module r...

Страница 12: ...maintained you MUST ensure that flow and return pipes into the sealed compartment are sealed with the supplied grommets 12 2 WATER CONNECTIONS NOTE Both flow and return connections are Rp in BSP fema...

Страница 13: ...main burner SHOULD ignite and the igniter will stop 13 2 9 When the control module reaches stage 8 indicated by 8 on the LED power is fed to the gas valve and the green LED ON light on the indicator p...

Страница 14: ...ntrol thermista stat and the SUMMER AIRFLOW switch 14 2 4 That the time control must be reset following a power failure 14 2 5 How to use the circulator thermostat to set the water temperature 14 2 6...

Страница 15: ...nction control remove the relevant burner assembly fixing screws 15 2 7 Break the gas supply at the gas union and remove the gas feed pipe fixing screw 15 2 8 Whilst supporting the assembly carefully...

Страница 16: ...e cover plate screws 15 7 10 Re establish electrical supply 15 7 11 Commission air heater and water circulator as described in the relevant sections above 15 8 TIME CONTROL SWITCH AND LED INDICATOR DA...

Страница 17: ...embly as detailed at paragraph 15 2 15 11 5 Remove the multifunctional control for the water circulator IF FITTED 15 11 6 Release the 4 x screws securing the combustion chamber heat shield and withdra...

Страница 18: ...water circulator will override those for the air heater therefore LED displays 8 and 9 will override 5 and 6 For this reason it is strongly recommended that the air heater and water circulator be comm...

Страница 19: ...19 Telephone 01604 762881 FIGURE 12 CONTROL FLOWCHART 17 DIAGNOSIS FLOWCHARTS...

Страница 20: ...www johnsonandstarley co uk 20 FIGURE 13 AIR HEATER DIAGNOSIS FLOWCHART...

Страница 21: ...21 Telephone 01604 762881 FIGURE 14 CONTROL FLOWCHART...

Страница 22: ...www johnsonandstarley co uk 22 18 LOGIC DIAGRAM FIGURE 15 LOGIC DIAGRAM...

Страница 23: ...23 Telephone 01604 762881 3 19 SCHEMATIC DIAGRAM FIGURE 16 SCHEMATIC DIAGRAM...

Страница 24: ...www johnsonandstarley co uk 24 FIGURE 17 CIRCUIT DIAGRAM 20 CIRCUIT DIAGRAM Showing connections of an external controller...

Страница 25: ...25 Telephone 01604 762881 21 DIMENSIONS FIGURE 18 DIMENSIONS...

Страница 26: ...1 23 381 712 1000 0705140 Ignition Burner Injector No 36 1 392935 1000 0701260 Ignition Burner Injector No 27 from serial number 54000501 1 24 E69653 1000 1507310 Gasket 1 25 E95 494 S01159 Air Press...

Страница 27: ...27 Telephone 01604 762881 FIGURE 19 EXPLODED DIAGRAM 23 EXPLODED DIAGRAM...

Страница 28: ...from Johnson Starley Ltd Telephone the Sales Office for further information ECONOMAIRE 32 ANCILLARY S Description Product Code 1 Cleanflow Air Filter ECF32 2 Return Air Plenums RAP32 3 Side Return Ai...

Страница 29: ...29 Telephone 01604 762881 This Log Book should be filled out at each annual service ECONOMAIRE 32 LOG BOOK WARM AIR HEATER AND WATER CIRCULATOR COMMISSIONING CHECKLIST...

Страница 30: ...ty but does not affect statutory rights Customer Name Address Telephone Number Warm Air Unit Make and Model Warm Air Unit Serial Number Commissioned by print name Gas Safe Reg No Company Name Telephon...

Страница 31: ......

Страница 32: ...les Telephone 01604 707012 Fax 01604 764879 Service Telephone 01604 707011 Fax 01604 707017 Warm Air Upgrade Enquiry Service Telephone 01604 707026 Fax 01604 707017 COMMERCIAL INDUSTRIAL H V SOLUTIONS...

Отзывы: