www.johnsonandstarley.co.uk
3. IMPORTANT INFORMATION
Installation shall be in accordance with the current editions of:-
Building Standards (Scotland) (Consolidation) Regulations
Building Regulations
Gas Safety (Installation and Use) Regulations (as amended)
BS 7671 Institute of Electrical Engineers (I.E.E.) Wiring Regulations
BS 6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS 5440 Pt.1 (Flues for Gas Appliances)
BS 5440 Pt.2 (Air Supply for Gas Appliances)
BS 5864 Installation of Gas Fired Ducted Air Heaters
British System Design Manual “Gas Fired Warm Air Heating”
Model and Local Authority Bye-laws
BS 5546 Installation of Domestic Hot Water Supplies.
IT IS A
STATUTORY REQUIREMENT THAT ALL GAS APPLIANCES MUST BE INSTALLED BY COMPETENT PERSONS,
(i.e. GAS SAFE REGISTERED INSTALLERS. GAS SAFE MEMBERSHIP ENQUIRIES - TEL: 0800 408 5500) IN
ACCORDANCE WITH THE GAS SAFETY (INSTALLATION AND USE) REGULATIONS (CURRENT EDITION). FAILURE
TO COMPLY WITH THESE REGULATIONS MAY LEAD TO PROSECUTION.
4. TECHNICAL DATA
ECONOMAIRE 32
ECONOMAIRE 32 INTEJAN
WATER CIRCULATOR
WEIGHT
54kg
61kg
GAS
G20
GAS SUPPLY PRESSURE
20mbar
GA CATEGORY
I 2H
COUNTRIES OF INSTALLATION
GB & IE
ELECTRICAL SUPPLY
230V ~ 50Hz fused 5A 250W
NOX CLASS
1
MAXIMUM WATER SIDE OPERATING PRESSURE
(PMS)
N/A
3 bar
OPEN VENTED SYSTEM
N/A
YES
SEALED SYSTEM
N/A
YES
5. HEATER COMPARTMENT AND CLEARANCES
(See BS 5864)
5.1
IMPORTANT:
If the heater is to be fitted to an existing base duct (warm air plenum), always ensure that installation
is carried out such that the rear left hand corner of the heater is aligned with the rear left hand corner of the base duct,
so that any overhang or blanking off will be at the front and/or right hand side. In any event, blanking plates must be
mechanically secured and all joints sealed.
5.2 When the heater is fitted into a compartment, a minimum clearance from the compartment walls of 3mm (
1
/
8
”) at the
sides and rear and 75mm (3”) at the front must be left. Consideration should also be given to the space required for
the removal and replacement of the filter tray and the entry of the gas, water and electrical supplies. If gas and /or water
connections are made from a side entry, a minimum clearance of 75mm (3”) is required at that side.
5.3 For service access, a minimum of 450mm (18”) is required at the front of the heater. Space must also be allowed, in a
compartment installation, to permit the removal of the heater. The clearance between the appliance and the compartment
should be not less than 75mm (3”). However, if clearances are less than 75mm, the internal surface of the compartment
must be lined with non-combustible material and the compartment must be of a fixed rigid structure.
5.4 In airing cupboard installations, the part used as the air heater compartment must comply with the relevant section of
BS 5864 and must be completely separated by either a non-combustible partition or a perforated metal partition with the
perforations not exceeding 13mm (½”). The secondary flue must be a tight fit where it passes through the partition and
must be suitably protected (see BS 5440: Part 1).
Содержание ECONOMAIRE 32
Страница 19: ...19 Telephone 01604 762881 FIGURE 12 CONTROL FLOWCHART 17 DIAGNOSIS FLOWCHARTS...
Страница 20: ...www johnsonandstarley co uk 20 FIGURE 13 AIR HEATER DIAGNOSIS FLOWCHART...
Страница 21: ...21 Telephone 01604 762881 FIGURE 14 CONTROL FLOWCHART...
Страница 22: ...www johnsonandstarley co uk 22 18 LOGIC DIAGRAM FIGURE 15 LOGIC DIAGRAM...
Страница 23: ...23 Telephone 01604 762881 3 19 SCHEMATIC DIAGRAM FIGURE 16 SCHEMATIC DIAGRAM...
Страница 25: ...25 Telephone 01604 762881 21 DIMENSIONS FIGURE 18 DIMENSIONS...
Страница 27: ...27 Telephone 01604 762881 FIGURE 19 EXPLODED DIAGRAM 23 EXPLODED DIAGRAM...
Страница 31: ......