25
Inverter
AC
output
over
current
Inverter
shutdown
and will
restart
automaticall
y after the
fault
disappears.
1. Power
capacity of
pump motor
is higher
than rated
output.
2. Pump
motor
locked-roto
r, or
damaged.
3. Pipe
system
design is
not
reasonable.
1. Please
inspect whether
pump motor is
normal.
2. Please
inspect whether
pipeline system
is in accordance
with water pump
or not.
3. If this happen
frequently,
please contact
SUPPLIER.
Output
phase
lose
Inverter
shutdown
and will
restart
automaticall
y after the
fault
disappears.
Phase loss
in inverter
output.
1. Please check
if the output
wires are proper
connected and
fixed.
2. If this happen
frequently,
please contact
the supplier.
Warn
light on
Busbar
voltage
undervo
ltage
Inverter
shutdown
and will
restart
automaticall
y after the
fault
PV array
output
changes;
pump
damage;
inverter
hardware
1. Please check
the input
voltage from
array and make
sure this voltage
inside inverter
input voltage