12 Diagnostic and Administrative Functions
JetWeb
96
Jetter AG
12.2
Response of Digital Outputs to
Timeout
In case of a timeout in system bus communication, each of the outputs can be set to
an error status to be defined by the user.
The user can specify whether an output should maintain its state or whether it is to
be set or reset in case of an error..
The error status of outputs can be defined using register array element 50 "Outputs
- Error Mode", and 51 "Outputs - Error Status".
Fig. 29: Definition of output error statuses
Re-initialization of JX2-IO16 following timeout
Once a timeout error has occurred, the module is in STOP state. Thus, without re-
initialization it can no longer be addressed.
There are two ways to re-initialize the module:
• Initialization # 1:
The module is re-initialized from the controller using a command or a special
function.
• Initialization # 2:
The module is re-initialized by switching the controller and the module off and,
then, on again.
Error mode
Error state
Output state
Signal at the output
Error
Note!
The controller saves the last output state of the JX2-IO16 module before the
timeout has occurred. If the output state has changed as a result of an error status
on the JX2-IO16 module, the output state, which has been saved by the controller
for the JX2-IO16, is no longer applicable.
Содержание JX2-IO16
Страница 10: ...Table of Contents JetWeb 10 Jetter AG...
Страница 18: ...1 Safety Instructions JetWeb 18 Jetter AG...
Страница 22: ...2 Introduction JetWeb 22 Jetter AG...
Страница 23: ...JX2 IO16 Jetter AG 23 3 Mounting Dimensions Fig 3 Front View JX2 IO16 Fig 4 Side View JX2 IO16...
Страница 24: ...3 Mounting Dimensions JetWeb 24 Jetter AG Fig 5 Top View JX2 IO16...
Страница 56: ...6 Installation Guide JetWeb 56 Jetter AG...
Страница 68: ...9 Fast inputs Software filter JetWeb 68 Jetter AG...
Страница 82: ...10 Pulse stretching JetWeb 82 Jetter AG...
Страница 105: ...JX2 IO16 Appendix Jetter AG 105 Appendices...
Страница 106: ...Appendices JetWeb 106 Jetter AG...
Страница 123: ...JX2 IO16 Appendix Jetter AG 123...