JX2-IO16
Jetter AG
25
4
Operating Conditions
Operating Parameters: Power Rating
Parameter
Value
Reference
Power Rating
DC 24 V (DC 20 V ... 30 V)
Residual ripple: <= 5 %
SELV power supply
Power consumption: max. 5.775
A
Voltage dips
Duration of voltage dips
≤
10 ms
Time interval between two
voltage dips
≥
1 s
Severity level PS2
DIN EN 61131-2
Environmental Operating Parameters
Parameter
Value
Reference
Operating
Temperature Range
0 °C - +50 °C
-
Storage Temperature
Range
-25 °C - +70 °C
DIN EN 61131-2
DIN EN 60068-2-1
DIN EN 60068-2-2
Air Humidity
10 % - 95 % (non-condensing)
DIN EN 61131-2
Pollution Degree
2
DIN EN 61131
Corrosion immunity/
chemical resistance
No special protection against
corrosion. Ambient air must be
free from higher concentrations
of acids, alcaline solutions,
corrosive agents, salts, metal
vapours, or other corrosive or
electroconductive contaminants
-
Atmospheric
pressure
2,000 m
DIN EN 61131-2
Содержание JX2-IO16
Страница 10: ...Table of Contents JetWeb 10 Jetter AG...
Страница 18: ...1 Safety Instructions JetWeb 18 Jetter AG...
Страница 22: ...2 Introduction JetWeb 22 Jetter AG...
Страница 23: ...JX2 IO16 Jetter AG 23 3 Mounting Dimensions Fig 3 Front View JX2 IO16 Fig 4 Side View JX2 IO16...
Страница 24: ...3 Mounting Dimensions JetWeb 24 Jetter AG Fig 5 Top View JX2 IO16...
Страница 56: ...6 Installation Guide JetWeb 56 Jetter AG...
Страница 68: ...9 Fast inputs Software filter JetWeb 68 Jetter AG...
Страница 82: ...10 Pulse stretching JetWeb 82 Jetter AG...
Страница 105: ...JX2 IO16 Appendix Jetter AG 105 Appendices...
Страница 106: ...Appendices JetWeb 106 Jetter AG...
Страница 123: ...JX2 IO16 Appendix Jetter AG 123...