JX2-IO16
Jetter AG
65
Controller
Meaning of the individual bits:
Bit 8:
Time-out - Reaction (only for commissioning)
This feature is for defining the reation to a time-out in system bus
communication (becomes immediately effective). See chapter 12
"Diagnostic and Administrative Functions", page 93.
The module is to remain addressable
Once the communication error is eliminated, IOs and registers can be
addressed as before.
This function makes sense only if the communication problem can be
resolved without switching off the logic voltage for controller and module.
If this function is used, it is not allowed to enter an error state, which is
defined via register array elements 50 and 51, into one of the outputs.
Module is to assume stop state
In this mode, the module has to be re-initialized first before IOs and
registers can be re-addressed. If this function is used, an error state,
which is defined via register array elements 50 and 51, can be entered
into one of the outputs.
0 = The module remains addressable
(only for commissioning
purposes)
1 = The module assumes stop state and has to be re-initialized
Value following reset: 1
Bit 9:
Output initialization
Initialization of digital outputs in case of a warm restart (re-initialization of
the JX2-IO16 module via controller without de-energizing and re-
energizing the JX2-IO16 module). This function immediately becomes
effective. See also chapter 12 "Diagnostic and Administrative Functions",
page 93.
This bit is automatically set when a time-out in system bus communication
occurs. It remains set until it is reset by the user.
This bit can be used by the user irrespective of a time-out.
0 = With a warm restart, outputs are set to 0.
1 = With a warm restart, outputs maintain the last state.
Value following reset: 0
Содержание JX2-IO16
Страница 10: ...Table of Contents JetWeb 10 Jetter AG...
Страница 18: ...1 Safety Instructions JetWeb 18 Jetter AG...
Страница 22: ...2 Introduction JetWeb 22 Jetter AG...
Страница 23: ...JX2 IO16 Jetter AG 23 3 Mounting Dimensions Fig 3 Front View JX2 IO16 Fig 4 Side View JX2 IO16...
Страница 24: ...3 Mounting Dimensions JetWeb 24 Jetter AG Fig 5 Top View JX2 IO16...
Страница 56: ...6 Installation Guide JetWeb 56 Jetter AG...
Страница 68: ...9 Fast inputs Software filter JetWeb 68 Jetter AG...
Страница 82: ...10 Pulse stretching JetWeb 82 Jetter AG...
Страница 105: ...JX2 IO16 Appendix Jetter AG 105 Appendices...
Страница 106: ...Appendices JetWeb 106 Jetter AG...
Страница 123: ...JX2 IO16 Appendix Jetter AG 123...