JX2-IO16
12.2 Response of Digital Outputs to Timeout
Jetter AG
97
The output state is influenced by these two ways of initialization differently:
• Initialization # 1:
The output error status, which has been set due to the communication
error, is maintained in the JX2-IO16 module.
To do so, the JX2-IO16
automatically sets control bit 8 "Output initialization" in register 3xx0 "Status /
Controller". For more information refer to chapter 8 "Status and Control
Functions", page 63. During re-initialization the output state saved by the
controller for the JX2-IO16 module is also set to the output state of the JX2-IO16.
For more information refer to Fig. 30.
• Initialization # 2:
The output state within the module, as well as in the controller is set to 0. For more
information refer to Fig. 30