5 Technical Data
JetWeb
30
Jetter AG
5.2
Digital Inputs
Technical Data of Digital Inputs
8 digital inputs
DC 24 V
Type
pnp
Input terminals
Three-level terminal blocks (screw plugs)
LEDs, inputs 1 - 8
DC 24 V are applied to the input. Pick-off
method: Hardware-triggered signal
Signal Voltage
DC 0 .. 30 V
Maximum current carrying capacity
of sensor supply per input
200 mA
Typical input current with signal
voltage ON
Approx. 8 mA
Input resistance
3.0 k
Ω
Input delay time of inputs 1 - 4
Fixed value of 2.8 ms (from 0 to 1, and
from 1 to 0)
Input delay time of inputs 5 - 8 (fast
inputs)
Fixed value of 180 ms (from 0 to 1, and
from 1 to 0) with a resolution of 128 µs
Signal voltage ON
Minimum DC 16 V
Signal voltage OFF
Maximum DC 5 V
Signal processing
Dynamic
Electrical isolation
None
Pulse stretching
Yes (for all inputs) Each input can
indiviually be parameterized
Single-channel counter
Quantity
4 (via inputs 5 - 8, DC 24 V)
Minimum pulse length (high or low
pulse)
250 µs
Maximum counting frequency at 50
% duty cycle
2 kHz
Dual-channel counter
Quantity
1 (via inputs 5 - 6, DC 24 V)
Edge evaluation
Quadruple evaluation
Max. counting frequency
1 kHz
Содержание JX2-IO16
Страница 10: ...Table of Contents JetWeb 10 Jetter AG...
Страница 18: ...1 Safety Instructions JetWeb 18 Jetter AG...
Страница 22: ...2 Introduction JetWeb 22 Jetter AG...
Страница 23: ...JX2 IO16 Jetter AG 23 3 Mounting Dimensions Fig 3 Front View JX2 IO16 Fig 4 Side View JX2 IO16...
Страница 24: ...3 Mounting Dimensions JetWeb 24 Jetter AG Fig 5 Top View JX2 IO16...
Страница 56: ...6 Installation Guide JetWeb 56 Jetter AG...
Страница 68: ...9 Fast inputs Software filter JetWeb 68 Jetter AG...
Страница 82: ...10 Pulse stretching JetWeb 82 Jetter AG...
Страница 105: ...JX2 IO16 Appendix Jetter AG 105 Appendices...
Страница 106: ...Appendices JetWeb 106 Jetter AG...
Страница 123: ...JX2 IO16 Appendix Jetter AG 123...