Operating Parameters (EMC) - Immunity to
Interference of Housing
Parameter
Value
Reference
Magnetic Field with
Mains Frequency
50 Hz, 60 Hz
30 A/m
DIN EN 61000-6-2
DIN EN 61000-4-8
RF Field, amplitude-
modulated
Frequency band 27 - 1000 MHz
Test field strength 10 V/m
AM 80 % with 1 kHz
Criterion A
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-3
ESD
Discharge through air:
Test peak voltage 15 kV
(Humidity Rating RH-2 / ESD-4)
Contact Discharge:
Test peak voltage 4 kV
(severity level 2)
Criterion A
DIN EN 61000-6-2
DIN EN 61131-2
DIN EN 61000-4-2
EMC - Immunity to Interference Operating Parameters
Signal Ports
Parameter
Value
Reference
Asymmetric RF,
amplitude-modulated
Frequency band 0.15 - 80 MHz
Test voltage 10 V
AM 80 % with 1 kHz
Source impedance 150 Ohm
Criterion A
DIN EN 61000-6-2
DIN EN 61000-4-6
Burst (fast transients)
Test voltage 1 kV
tr/tn 5/50 ns
Repetition rate 5 kHz
Criterion A
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-4
Содержание JX2-IO16
Страница 10: ...Table of Contents JetWeb 10 Jetter AG...
Страница 18: ...1 Safety Instructions JetWeb 18 Jetter AG...
Страница 22: ...2 Introduction JetWeb 22 Jetter AG...
Страница 23: ...JX2 IO16 Jetter AG 23 3 Mounting Dimensions Fig 3 Front View JX2 IO16 Fig 4 Side View JX2 IO16...
Страница 24: ...3 Mounting Dimensions JetWeb 24 Jetter AG Fig 5 Top View JX2 IO16...
Страница 56: ...6 Installation Guide JetWeb 56 Jetter AG...
Страница 68: ...9 Fast inputs Software filter JetWeb 68 Jetter AG...
Страница 82: ...10 Pulse stretching JetWeb 82 Jetter AG...
Страница 105: ...JX2 IO16 Appendix Jetter AG 105 Appendices...
Страница 106: ...Appendices JetWeb 106 Jetter AG...
Страница 123: ...JX2 IO16 Appendix Jetter AG 123...